background image

VALLOX 90K SC

INSTRUCTIONS FOR USE

5

2.3. Heat recovery bypass

In winter use the heat recovery cell of VALLOX 90K SC recovers heat from the air leaving
the dwelling and uses it to heat the air coming from the outside.
In summer use when it is warm outside, it is unnecessary to heat outdoor air. The heat recovery
cell is bypassed in VALLOX 90K SC with the standard damper (A). The position of the damper
can be changed by opening the damper release (B) and then moving the summer/winter
damper in another position. In the summer position air flow through the cell is prevented,
and heat recovery bypass is activated.

2.4. Air filtering

VALLOX 90K SC features coarse filtering of both extract and supply air before the fans. The
supply air side includes a G3 class coarse filter (C) and the extract air side a G3 class coarse
filter (D). The unit can also be equipped with an F7 fine filter (E), which captures fine dust
and pollen as well dust not seen to the eye. The filters need to be in place in the unit whenever
ventilation is in operation.

2.5. Defrosting

Water condensing from extract air may freeze in the heat recovery cell. Freezing can be
prevented by stopping the supply air fan, or the unit can be equipped with an optional
preheating resistor, which is switched on as needed.

2.6. Stopping the supply air fan

Defrost thermostat T1 stops the supply air fan whenever the temperature of extract air goes
below +5 

°

C after the cell. The fan restarts when temperature has risen by circa three degrees,

i.e. to +8 

°

C. The limit of the thermostat (F) can be adjusted at the back of the heat recovery

cell. If the unit includes a preheating radiator (G), the supply air fan cannot be stopped.

2.7. Outdoor air preheating

The unit may have been equipped with a preheating radiator at the factory. If this is the case,
defrost thermostat T1 switches the preheating radiator on whenever the temperature of extract
air goes below +5 

°

C after the cell. The preheating radiator switches off when temperature

has risen by circa three degrees, i.e. to +8 

°

C. The preheating radiator heats outdoor air

before the cell and prevents it from freezing. In very cold temperatures the preheating radiator
is not enough to heat maximum air flow to a sufficient degree (in a temperature of -30 

°

C,

maximum air flow is 30 dm

3

/s, which corresponds to speed 2). The limit of the thermostat

can be adjusted at the back of the heat recovery cell.

2.8. Post-heating

For most of the year, heat recovered from the air being extracted is enough to warm the cold
air coming from the outside to a suitable temperature. If the heat of extract air is not enough,
air coming from the outside may be heated further with a radiator installed outside of the
unit (for instance VALLOX 1000 supply air heater).

F

G

Preheating radiator (G)

Preheating radiator is lo-
cated behind a shield.

Summer/winter damper
in winter position

Summer/winter damper
in summer position.

You can switch the summer/winter damper to
winter position by pushing the damper behind
the holder.

A

B

C

D

E

G

Defrost thermostat (F)

First remove the heat recovery
cell, then the cap protecting the
adjusting screw of the thermostat.

F

Содержание 90k SC

Страница 1: ...nges without prior notification 1 09 347E 30 08 06 Code 3522 VALLOX INSTRUCTIONS FOR USE AND MAINTENANCE SUPPLY AND EXTRACT AIR VENTILATION WITH HEAT RECOVERY SC Code 3522 VALLOX 90K SC R 3295200 VALL...

Страница 2: ...adjustment p 4 2 2 Selection of fan speed p 4 2 3 Heat recovery bypass p 5 2 4 Air filtering p 5 2 5 Defrosting p 5 2 6 Stopping the supply air fan p 5 2 7 Outdoor air preheating p 5 2 8 Post heating...

Страница 3: ...t of the indoor air stay at a healthy level Recommended humidity content of good indoor air is approximately 45 Humidity content is lower in winter and higher in summer and autumn Dust mites thrive in...

Страница 4: ...ly pressured air in the dwelling penetrates the outer envelope of the building and between windows which may cause humidity damage during the heating season In normal conditions basic ventilation with...

Страница 5: ...s risen by circa three degrees i e to 8 C The limit of the thermostat F can be adjusted at the back of the heat recovery cell If the unit includes a preheating radiator G the supply air fan cannot be...

Страница 6: ...oothly Do not handle the filters with force When washing is done properly filters stand cleaning 3 to 4 times In other words you have to replace them at least every two years The fine filter E is not...

Страница 7: ...flow out from the ventilation unit without hindrance In connection with maintenance e g in autumn before the beginning of the heating season make sure that the condensing water outlet L in the bottom...

Страница 8: ...ing resistor see section 2 6 Defrosting on page 5 You can turn the defrost thermostat clockwise In this case there will probably be no freezing but extract air can be too warm when going out The defro...

Отзывы: