background image

ALWAYS PRIMARILY FOLLOW THE CONNECTION PLAN PREPARED BY THE HVAC PLANNER OR
THE HEAT PUMP MANUFACTURER.

See the adjoining example of connecting an MLV unit to the ground collector. The supply pipe of the MLV circuit is connected to the pipe

returning from the collector. The liquid returning from the MLV circuit is taken back to the return pipe of the ground collector. If the internal

 pressure losses of the heat pump in the ground collector are known to be high, it is recommended to bypass the heat pump. The liquid then circulates when the heat pump is stopped. In this case the

pressure loss of the bypass non-return valve has to be lower than that of the heat pump. When the conditions for starting the heating or cooling function have been met, the control function of the unit

opens the solenoid valve (MV) and starts the pump (P). The components of the MLV circuit mentioned in the diagram are not included in the delivery. Observe the freeze resistance of the liquid used in the

ground collector. The connection pipes of the MLV radiator have to insulated against condensation. If there is an open expansion tank in the heat pump, it must be at the highest point in the network. Note!

Because of the risk of humidity damage, supply air temperature in a duct with no condensation insulation should not go below +16...20 

°

C.

RADIATOR HEATING

HEAT PUMP

UNDERFLOOR HEATING

Heating water

adjustment

© Vallox • We reserve the right to make changes without prior notice.

Vallox 200 SE MLV Connection of MLV preheating/
cooling radiator to the ground collector
of ground-source heat pump

Vallox 200 SE Connection of VKL post-heating radiator
Sample connection: direct connection to underfloor heating or radiator network

21

RADIATOR CONNECTIONS

P    Circulation pump, not included in the delivery. Because

of the risk of condensing the pump should be suitable
for pumping liquid that is colder than the ambient
temperature (such as Grundfos Magna 1 25-80).

MV Solenoid valve, not included in the delivery. The valve

has to be suitable for the liquid in the ground collector
(for example ELV05006, Stig Wahlström).

Y    Non-return valve, not included in the delivery.
R Stop valve, not included in the delivery
IP Air bleeder, not included in the delivery. Air bleeder is

placed after the pump and at the highest point in the
network.

Y2 Non-return valve, not included in the delivery. The

pressure loss of the valve has to be lower than that of
the heat pump.

It is sometimes convenient to connect the unit directly into the heating network. The connection involves a risk of freezing for the radiator although efforts have been made in the unit to minimise the risk

of freezing of the radiator. The unit stops if supply air temperature goes below the set temperature and automatically starts as soon as temperature rises above the value set. The unit also issues an alarm

of freezing risk at the controller. It is recommended to have e.g. a spring-actuated check valve (E) in the outdoor air duct (and possibly also in the exhaust air duct). This valve closes the duct from the

unit to outdoor air and prevents cold air from flowing into the unit while it is stopped. he base volume of water flow into the radiator of the unit can be adjusted with valves (S), which can also act as stop

valves. No water must be led into the radiator of the unit until the system has been adjusted for operation and heating is on in the heating network, or other measures have been taken to ensure that the

radiator will not freeze. Water circulation in the heating network connected to the unit and the circulation pump must not be stopped during the heating season.

P Circulation pump, not included in the delivery.

Because of the risk of condenstion, the pump
should be suitable for pumping a liquid that is
cooler than the surroundings (for example
Grundfos Magna 1 25-80).

MV Solenoid valve, not included in the delivery.

The valve  has to be suitable for the liquid in
the ground collector (for example  ELV05006,
Stig Wahlström).

Y Non-return valve, not included in the delivery.
R Stop valve, not included in the delivery.
S

Control valve, not included in the delivery.

IP    Air bleeder, not included in the delivery. Air

bleeder is placed after the pump, at the highest
point in the network.

T     2-way control valve, is included in the unit

delivery.

E    Check valve, not included in the delivery.
Y2   Non-return valve, not included in the delivery.

The pressure loss of the valve has to be lower
than that of the heat pump.

ALWAYS PRIMARILY FOLLOW THE CONNECTION PLAN PREPARED BY THE HVAC PLANNER OR THE HEAT PUMP MANUFACTURER.

See the adjoining example of connecting an MLV unit to the ground collector. The supply pipe of the MLV circuit is connected to the pipe returning from the ground collector. The liquid returning from the

MLV circuit is taken back to the return pipe of the ground collector. If the internal pressure losses of the heat pump in the ground collector are known to be high, it is recommended to bypass the heat pump.

The liquid then circulates when the heat pump is stopped. In this case the pressure loss of the bypass non-return valve has to be lower than that of the heat pump. When the conditions for starting the

heating or cooling function have been met, the control function of the unit opens the solenoid valve (MV) and starts the pump (P). The components of the MLV circuit mentioned in the diagram are not

included in the delivery. Observe the freeze resistance of the liquid used in the ground collector. The connection pipes of the MLV radiator have to insulated against condensation. If there is an open

expansion tank in the heat pump, it must be at the highest point in the network. Note! Because of the risk of humidity damage, supply air temperature in a duct with no condensation insulation should not

go below +16...20 

°

C.

VALLOX 200 SE

HEAT PUMP

GROUND COLLECTOR

Содержание 3527800

Страница 1: ...iency 60 B Supply air efficiency 84 Specific Fan Power SFP 1 3 125 dm3 s B Filters Supply air G4 F7 Extract air G4 Heat recovery bypass Automatic Weight 146 kg Comes standard with control Vallox Digit...

Страница 2: ...overy cell Heat recovery bypass Supply air filter F7 Extract air filter G4 Outdoor air filter G4 Condensing water outlet Electrical connection lead ins Control panel Measurement outlets behind the cov...

Страница 3: ...ON AIR FLOW 63 125 250 500 1000 2000 4000 8000 LW dB LWA dB A Hz ADJUSTMENT POSITION AIR FLOWS supply extract A weighted sound pressure level dB A coming from the unit through the envelope in the room...

Страница 4: ...Herz ADJUSTMENT POSITION AIR FLOW Sound power level going from the unit to the extract air ductwork by octave band Lw dB ADJUSTMENT POSITION AIR FLOW ADJUSTMENT POSITION AIR FLOWS supply extract A wei...

Страница 5: ...xtract A weighted sound pressure level dB A coming from the unit through the envelope in the rooms where the unit has been installed 10 m2 sound absorption PERFORMANCE Vallox 200 SE MLV electric 5 63...

Страница 6: ...IR FLOWS supply extract A weighted sound pressure level dB A coming from the unit through the envelope in the rooms where the unit has been installed 10 m2 sound absorption PERFORMANCE Vallox 200 SE M...

Страница 7: ...sorption LpA A painotettu nenpainetaso 10 m2 n nenabsorptio 63 125 250 500 1000 2000 4000 8000 Lw dB LwA dB A Hz LpA dB A 2 70 77 4 96 l s 2 63 l s 2 95 l s 4 125 l s 6 161 s 8 174 l s PERFORMANCE WIT...

Страница 8: ...ay contact signal is issued It is possible to manage the whole operation of the unit via remote monitoring control by using a Vallox LON or KNX converter that is available as an option Week clock cont...

Страница 9: ...terminal block of the con nection box by connecting the first hu midity sensor to RH1 in place of the 6K8 resistor in the terminal block re move the resistor in this case and the second humidity sens...

Страница 10: ...W DC PF EXHAUST AIR FAN 2 X 117 W DC H INTERFERENCE SUPPRESSOR K CHOKE FG DAMPER MOTOR 24 VAC TE TEMPERATURE SENSORS R1 AUXLIARY RESISTOR 6 8 KOHM TR TRANSFORMER 1 3 A 16 V F MOTHERBOARD FUSE 800 mA S...

Страница 11: ...L ME HUMIDITY SENSOR 2 OPTION HUMIDITY SENSOR 1 OPTION REMOVE THE RESISTOR WHEN CONNECTING THE FIRST HUMIDITY SENSOR TO THE UNIT BOOST SWITCH FIREPLACE SWITCH Additional control option FAN CONTROL Vol...

Страница 12: ...unit also has an automatic defrost function for the water circulating post heating unit VKL model Defrost When exhaust air temperature goes below the threshold value set the automatic defrost function...

Страница 13: ...flow Temperature of air coming to the radiator ta1 15 C Temperature of water coming to the radiator tf1 55 C Total power of radiator kW 0 100 dm3 s 0 050 dm3 s 0 020 dm3 s Water flow 160 dm3 s 120 dm...

Страница 14: ...ior notice HEATING VKL WATER RADIATOR 14 VKL WATER RADIATOR PRESSURE LOSS IN WATER CIRCULATION Defined for 100 water Water flow Total pressure loss kPa dm3 s 100 90 80 70 60 50 40 30 20 10 9 8 7 6 5 4...

Страница 15: ...DIOXIDE SENSOR 5 AT MOST CONTROL PANEL 3 AT MOST HUMIDITY SENSOR 2 AT MOST VENTILATION ZONE ALARM OPERATION MODE CONTROL MEASUREMENT ADJUSTMENT FIREPLACE BOOSTER SWITCH POST HEATING UNIT WATER LP2 SI...

Страница 16: ...ir temperature at the temperature value set on control panel H 10 30 C Heat recovery bypass Heat recovery is enabled whenever post heating has been switched on Automatic heat recovery bypass is active...

Страница 17: ...LECTRICAL AND CONTROL CONNECTIONS PRESSURE DIFFERENCE SWITCH LON CONVERTER DISTRIBUTION PANEL CARBON DIOXIDE SENSOR 5 AT MOST CONTROL PANEL 3 AT MOST HUMIDITY SENSOR 2 AT MOST VENTILATION ZONE REMOTE...

Страница 18: ...ating unit LP2 on the basis of the measurement data given by extract air sensor TE4 aiming at keeping extract air temperature at the temperature value set on control panel H 10 30 C Heat recovery bypa...

Страница 19: ...the screwed terminal block as specified in the connection instructions The external connection diagram is shown in these instructions and inside the cover of the electrical connection box The interna...

Страница 20: ...tions Water condensing from extract air going through the unit can be removed from the bottom tank in two ways When the humidity content of extract air is high as for example in washing rooms the cond...

Страница 21: ...et The unit also issues an alarm of freezing risk at the controller It is recommended to have e g a spring actuated check valve E in the outdoor air duct and possibly also in the exhaust air duct This...

Страница 22: ...ith no condensation insulation should not go below 16 20 C P Circulation pump not included in the delivery Because of the risk of condensation the pump should be suitable for pumping a liquid that is...

Страница 23: ...ure Mount the lead in pipes included in the delivery for cables in place by pushing them first through the lead in seals located at the top of the silencer unit and then through the lead in seals loca...

Страница 24: ...Vallox We reserve the right to make changes without prior notice www vallox com Vallox Oy Myllykyl ntie 9 11 32200 Loimaa FINLAND 358 10 7732 200 1 09 280bFIN 24 9 2015 PDF...

Отзывы: