Liquid flow  dm

3

/s.

Temperature of geothermal liquid leaving radiator 

°

C

Temperature of geothermal liquid coming to radiator 

°

C

Air flows d

m

3

/s

© Vallox • We reserve the right to make changes without prior notice.

FILTERING, HEAT RECOVERY, HEATING/MLV RADIATOR

12

Filtering

Efficient filtering of outdoor air (G4 + F7) prevents harmful particles
from entering the ductwork and rooms via the unit. Good filtering
of extract air (G4) diminishes the contamination of the unit and
ensures efficient heat recovery and extract air fan operation.
Clogging of the supply/extract air filters and of the ductwork can
be monitored by equipping the unit with a pressure difference
switch.

Heat recovery and heating

With efficient heat recovery, most of the heat in dirty extract air
can be transferred to the outdoor air that is taken inside. The
efficiency of the heat recovery cell is about 80%. If outdoor air

does not get sufficiently warm in the heat recovery cells, it can be
heated with a water-circulating or electric post-heating unit. The
automatic heat recovery bypass function in the unit ensures that
there is no need to heat outdoor air in summer. The unit also has
an automatic defrost function for the water-circulating post-heating
unit (VKL model).

Defrost

When exhaust air temperature goes below the threshold value set,
the automatic defrost function of the heat recovery cell switches
the preheating unit on. If the power of the preheating unit is not
enough, the unit momentarily stops the supply air fan.

VALLOX 200 SE

0.06

0.08

0.1

0

0.5

1.0

1.5

2.0

MLV unit cooling power

0.04

0.10

10.0

20.0

30.0

40.0

50.0

60.0

70.0

80.0

90.0

Pressure loss in liquid circulation of MLV unit

0.06

0.08

MLV unit heating power

0.06

0.08

0.1

0

0.5

1.0

1.5

2.0

Cooling of geothermal liquid of MLV radiator

-2

-10

0

2

4

-12

65

4

6

2

0

6

150

-8

-6

-4

-4

150

65

-2

8

Power and pressure loss in liquid circulation of MLV preheating/cooling unit

Air flow = 150 dm

3

/s

Heating power

, kW

Air flow = 110 dm

3

/s

Air flow = 65 dm

3

/s

Liquid flow dm

3

/s

- liquid = ethylene glycol 25%
- air coming to the unit = -12 

°

C

- liquid coming to the unit = 5 

°

C

Cooling power

, kW

Air flow
= 140 dm

3

/s

Air flow
= 60 dm

3

/s

Liquid flow dm

3

/s.

- liquid = ethylene glycol 25%
- air coming to the unit = 25 

°

C

- liquid coming to the unit = 5 

°

C

Heating power

, kW

Ethylene glycol 25% Flow 0.075 dm

3

/s

Air coming in -12 

°

C

Air coming in -30 

°

C

Liquid flow dm

3

/s

Air flow = 60 dm

3

/s

Temperature of geothermal liquid coming to radiator 

°

C

Temperature of geothermal liquid leaving radiator 

°

C

Содержание 3527800

Страница 1: ...iency 60 B Supply air efficiency 84 Specific Fan Power SFP 1 3 125 dm3 s B Filters Supply air G4 F7 Extract air G4 Heat recovery bypass Automatic Weight 146 kg Comes standard with control Vallox Digit...

Страница 2: ...overy cell Heat recovery bypass Supply air filter F7 Extract air filter G4 Outdoor air filter G4 Condensing water outlet Electrical connection lead ins Control panel Measurement outlets behind the cov...

Страница 3: ...ON AIR FLOW 63 125 250 500 1000 2000 4000 8000 LW dB LWA dB A Hz ADJUSTMENT POSITION AIR FLOWS supply extract A weighted sound pressure level dB A coming from the unit through the envelope in the room...

Страница 4: ...Herz ADJUSTMENT POSITION AIR FLOW Sound power level going from the unit to the extract air ductwork by octave band Lw dB ADJUSTMENT POSITION AIR FLOW ADJUSTMENT POSITION AIR FLOWS supply extract A wei...

Страница 5: ...xtract A weighted sound pressure level dB A coming from the unit through the envelope in the rooms where the unit has been installed 10 m2 sound absorption PERFORMANCE Vallox 200 SE MLV electric 5 63...

Страница 6: ...IR FLOWS supply extract A weighted sound pressure level dB A coming from the unit through the envelope in the rooms where the unit has been installed 10 m2 sound absorption PERFORMANCE Vallox 200 SE M...

Страница 7: ...sorption LpA A painotettu nenpainetaso 10 m2 n nenabsorptio 63 125 250 500 1000 2000 4000 8000 Lw dB LwA dB A Hz LpA dB A 2 70 77 4 96 l s 2 63 l s 2 95 l s 4 125 l s 6 161 s 8 174 l s PERFORMANCE WIT...

Страница 8: ...ay contact signal is issued It is possible to manage the whole operation of the unit via remote monitoring control by using a Vallox LON or KNX converter that is available as an option Week clock cont...

Страница 9: ...terminal block of the con nection box by connecting the first hu midity sensor to RH1 in place of the 6K8 resistor in the terminal block re move the resistor in this case and the second humidity sens...

Страница 10: ...W DC PF EXHAUST AIR FAN 2 X 117 W DC H INTERFERENCE SUPPRESSOR K CHOKE FG DAMPER MOTOR 24 VAC TE TEMPERATURE SENSORS R1 AUXLIARY RESISTOR 6 8 KOHM TR TRANSFORMER 1 3 A 16 V F MOTHERBOARD FUSE 800 mA S...

Страница 11: ...L ME HUMIDITY SENSOR 2 OPTION HUMIDITY SENSOR 1 OPTION REMOVE THE RESISTOR WHEN CONNECTING THE FIRST HUMIDITY SENSOR TO THE UNIT BOOST SWITCH FIREPLACE SWITCH Additional control option FAN CONTROL Vol...

Страница 12: ...unit also has an automatic defrost function for the water circulating post heating unit VKL model Defrost When exhaust air temperature goes below the threshold value set the automatic defrost function...

Страница 13: ...flow Temperature of air coming to the radiator ta1 15 C Temperature of water coming to the radiator tf1 55 C Total power of radiator kW 0 100 dm3 s 0 050 dm3 s 0 020 dm3 s Water flow 160 dm3 s 120 dm...

Страница 14: ...ior notice HEATING VKL WATER RADIATOR 14 VKL WATER RADIATOR PRESSURE LOSS IN WATER CIRCULATION Defined for 100 water Water flow Total pressure loss kPa dm3 s 100 90 80 70 60 50 40 30 20 10 9 8 7 6 5 4...

Страница 15: ...DIOXIDE SENSOR 5 AT MOST CONTROL PANEL 3 AT MOST HUMIDITY SENSOR 2 AT MOST VENTILATION ZONE ALARM OPERATION MODE CONTROL MEASUREMENT ADJUSTMENT FIREPLACE BOOSTER SWITCH POST HEATING UNIT WATER LP2 SI...

Страница 16: ...ir temperature at the temperature value set on control panel H 10 30 C Heat recovery bypass Heat recovery is enabled whenever post heating has been switched on Automatic heat recovery bypass is active...

Страница 17: ...LECTRICAL AND CONTROL CONNECTIONS PRESSURE DIFFERENCE SWITCH LON CONVERTER DISTRIBUTION PANEL CARBON DIOXIDE SENSOR 5 AT MOST CONTROL PANEL 3 AT MOST HUMIDITY SENSOR 2 AT MOST VENTILATION ZONE REMOTE...

Страница 18: ...ating unit LP2 on the basis of the measurement data given by extract air sensor TE4 aiming at keeping extract air temperature at the temperature value set on control panel H 10 30 C Heat recovery bypa...

Страница 19: ...the screwed terminal block as specified in the connection instructions The external connection diagram is shown in these instructions and inside the cover of the electrical connection box The interna...

Страница 20: ...tions Water condensing from extract air going through the unit can be removed from the bottom tank in two ways When the humidity content of extract air is high as for example in washing rooms the cond...

Страница 21: ...et The unit also issues an alarm of freezing risk at the controller It is recommended to have e g a spring actuated check valve E in the outdoor air duct and possibly also in the exhaust air duct This...

Страница 22: ...ith no condensation insulation should not go below 16 20 C P Circulation pump not included in the delivery Because of the risk of condensation the pump should be suitable for pumping a liquid that is...

Страница 23: ...ure Mount the lead in pipes included in the delivery for cables in place by pushing them first through the lead in seals located at the top of the silencer unit and then through the lead in seals loca...

Страница 24: ...Vallox We reserve the right to make changes without prior notice www vallox com Vallox Oy Myllykyl ntie 9 11 32200 Loimaa FINLAND 358 10 7732 200 1 09 280bFIN 24 9 2015 PDF...

Отзывы: