Surface mounting
Wiring
© Vallox • We reserve the right to make changes without prior notification.
What the units include can vary depending on the sales area.
VALLOX 200SE
Cable:
NOMAK 2 x 2 x 0.5 mm
2
+ 0.5 mm
2
Base plate of the CO
2
sensor
NOTE!
Faulty coupling of the (+) wire destroys
the carbon dioxide sensor!
1 = orange 1
= +
2 = white 1
= –
3 = orange 2
= A
4 = white 2
= B
5 = metal
= signal ground
ca. 21 VDC
}
14
125
38
76
1
+
B
2
-
4
B
3
A
5
M
S +
6
MOUNTING OF CONTROL PANEL AND SENSORS
Surface mounting
of control panel
A control panel is mounted
on the wall or on a 1-part
instrument box.
Wiring
Width
90 mm
Height
110 mm
Depth
23 mm
Electronics board of control panel
1 = orange 1
= +
2 = white 1
= –
3 = orange 2
= A
4 = white 2
= B
5 = metal
= signal ground
ca. 21 VDC
}
Cable:
NOMAK 2 x 2 x 0.5 mm
2
+ 0.5 mm
2
NOTE!
Faulty coupling of the (+) wire
destroys the control panel!
1 2 3 4 5
+ – A B M
HUMIDITY SENSORS
• If humidity sensors are used, connect
them to the terminal block of the con-
nection box by connecting the first hu-
midity sensor to %RH1, in place of the
6K8 resistor in the terminal block (re-
move the resistor in this case), and the
second humidity sensor to %RH2. See
the electrical diagram.
CARBON DIOXIDE SENSORS
• Carbon dioxide sensors are connected
individually.
• When the first carbon dioxide sensor has
been connected to the system, the unit is
switched on. After this, the unit gives the
sensor an address. Follow the same steps
for other carbon dioxide sensors.
The sensor is wired straight from the electrical connection box of the unit.
The CO
2
sensor is connected directly from the connection box of the unit, or in series with
another CO
2
sensor or control panel (see External electrical connections on page 7).
Surface mounting
Wiring
Cable:
2 x 0.5 mm
2
Electronics board of
%RH sensor
Base plate
of sensor
14
125
38
76
Mounting and wiring of humidity sensor
Mounting and wiring of carbon dioxide sensor
Electronics card of the CO
2
sensor (model may vary)