l/s
© Vallox • We reserve the right to make changes without prior notification.
What the units include can vary depending on the sales area.
Air volumes
SUPPLY (G4 + F7)/EXTRACT (G4) AIR VOLUMES
Measuring points after the
connection outlet.
Fan curves indicate the total
pressure available for duct
losses.
Extract air
Supply air
The measurement outlets in the
unit enable the measurement of
total pressure in the supply and
extract air ductworks (see page
16).
Compressed air readings indica-
te air flows based on the at-
tached performance curves.
Note!
When the system is being
adjusted, post-heating must be
selected (winter setting).
Sound power level from the ventilation unit
to supply air ducts by octave band Lw, dB
Medium
frequency of
the octave
band, Hz
ADJUSTMENT POSITION/AIR FLOW
Sound power level from the ventilation unit
to extract air ducts by octave band Lw, dB
ADJUSTMENT POSITION/AIR FLOW
ADJUSTMENT POSITION/AIR FLOWS (supply/extract)
A-weighted sound pressure level dB (A) coming from the
unit through the envelope to the rooms where the unit
has been installed (10 m
2
sound absorption)
Abluft
VALLOX 200SE
PERFORMANCE
3
Sound values
63
125
250
500
1000
2000
4000
8000
L
W
, dB
L
WA
, dB(A)
Hz
L
pA
, dB(A)
2
81 l/s
66
55
43
42
40
27
66
46
4
124 l/s
72
63
51
48
46
36
21
73
53
6
151 l/s
77
68
56
54
50
41
26
78
58
8
177 l/s
80
73
61
58
52
45
31
81
62
2
109 l/s
67
55
44
41
37
30
16
67
46
4
154 l/s
71
63
52
48
43
37
25
72
52
6
196 l/s
76
68
57
53
47
43
31
77
57
8
214 l/s
78
72
60
56
49
47
35
25
79
60
2
78/97
33
4
114/134
40
6
154/172
45
8
191/202
48
1
2
3
4
5
6
7
8
Fan speeds
Total input
power
W
71
97
108
132
152
172
200
230
49
73
99
140
188
261
353
451
Extract
air flow
(l/s)
Fan curves
= extract air fan
= supply air fan
Volume flow
Vallox 200 SE
Pressure loss in ducts. T
otal pressure
S
E
P
esU
, kW/(m
3
/s) 2,0
Pa
dm
3
/s
P
esU
, kW/(m
3
/s) 1,5
S1
E1
S3
E3 S4
E4
S5
S6
E5
E6
S7
E7
S8
E8
20
40
60
80
100
120
140
160
180
200
100
150
200
250
50
220
300
240
RECOMMENDED
OPERATING RANGE