Troubleshooting
When a fault described in the table appears, the unit indicates
of the fault with a fault signal relay, indicator light and LED on the
circuit board. The number of blinks reveals the fault in question
Led
blinks Problem
Repair
1
Supply air sensor after the HR cell is faulty Check the sensor and conductors, replace if needed
2
Extract air sensor is faulty
Check the sensor and conductors, replace if needed
3
Supply air sensor is faulty
Check the sensor and conductors, replace if needed
4
Exhaust air sensor is faulty
Check the sensor and conductors, replace if needed
5
Outdoor air sensor is faulty
Check the sensor and conductors, replace if needed
6
Supply air fan has stopped
Check the wiring of the fan, replace the fan if needed
7
Extract air fan has stopped
Check the wiring of the fan, replace the fan if needed
8
EEPROM faulty
Replace the circuit board of the unit with a new one
Содержание 096 MC R