background image

OM-MP80 E V1.15

January 29, 2015

Page 7

MP80

THIS UNIT MAY BE INSTALLED AS FOLLOWS:
1. 

AS AN INDEPENDENT FORCED AIR FURNACE EQUIPPED WITH A HAC 900 CFM FAN AS 
SHOWN IN DIAGRAM “A” BELOW.

2. 

AS A DOWN STREAM SERIES DUCT ADD-ON TO ANY OF THE FOLLOWING FURNACES:
A. 

OIL FURNACE HAVING OIL INPUT, AS SHOWN ON ORIGINAL NAMEPLATE, BETWEEN  

 

.81 USGPH & 1.2 USGPH (MAX.).  DIAGRAM “B”.

B. 

A GAS FIRED FORCED AIR FURNACE HAVING A GAS INPUT, AS SHOWN ON ORIGINAL  

 

NAMEPLATE, BETWEEN 60,000 MINIMUM AND 120,000 MAXIMUM BTU (17-35 kW)  AND A

 

39-56°C(70-100°F) AIR TEMPERATURE RISE.  MINIMUM FAN SIZE OF 900 CFM.

 DIAGRAM 

“B”.

C. 

ELECTRIC FORCED AIR FURNACE RATED AT 10 KW TO 25 KW INPUT.  MINIMUM FAN  

 

SIZE 900 CFM.  DIAGRAM “B”.

CHIMNEY REQUIREMENTS:

ALL  FUEL CHIMNEY WITH MINIMUM SIZE OF 29 sq. in. (1820 sq. mm.).  DO NOT CONNECT THIS 
FURNACE TO A CHIMNEY SERVING A GAS APPLIANCE.

MINIMUM CLEARANCE:

WOOD CHARGING END   

 

 

48 in. 

(1200 mm)

ONE 

SIDE 

    6 

in. 

(150 

mm)

OTHER SIDE (FOR SERVICING) 

 

 

18 in. 

(460 mm)

FLUE  

(COMBUSTIBLES, ELECTRICAL WIRE

 

AND ELECTRIC FURNACE) 

 

18 in. 

(460 mm)

PLENUM & FIRST 6 ft. OF DUCT 

 

 

2 in. 

(50 mm)

MINIMUM INTERCONNECT DUCT SIZE FOR ADD ON USE 12 in. (300 mm) x 18 in. (460 mm).
NOTE - NOT APPROVED FOR PARALLEL OR SPLIT PLENUM (ADD-ON SERIES ONLY APPROVED)
IF INSTALLED ON COMBUSTIBLE FLOOR THE FLOOR MUST BE PROTECTED 18 in. (460 mm) IN 
FRONT OF WOOD CHARGING END.  REFER TO INSTALLATION INSTRUCTIONS

INSTALLED BY  

ADDRESS  

DATE  

OPERATING INSTRUCTIONS:

REFER TO DETAILED MANUFACTURER’S INSTRUCTIONS
1. 

BURN WOOD ONLY

2. 

LOAD FUEL CAREFULLY OR DAMAGE MAY RESULT

3. 

FILL TO BOTTOM OF DOOR ONLY.

4. 

DO NOT ATTEMPT TO LIGHT A FIRE WHEN THERE IS OIL OR GAS VAPOUR PRESENT.

5. 

DO NOT USE CHEMICALS OR FLUIDS TO START FIRE.

CAUTIONS:

1. 

DO NOT CONNECT DUCTWORK SO THAT A REVERSE FLOW IS POSSIBLE.

2. 

OPERATE OIL /GAS / ELECTRIC FURNACE UNIT PERIODICALLY TO ENSURE THAT IT WILL 
OPERATE SATISFACTORILY WHEN NEEDED.

3. 

DO NOT RELOCATE OR BYPASS ANY OF THE SAFETY CONTROLS OF THE ORIGINAL 
FURNACE INSTALLATION.

4. 

DISCONNECT ELECTRIC POWER FROM BOTH ADD-ON FURNACE AND ELECTRIC/GAS/OIL 
UNIT  BEFORE SERVICING

5. 

DO NOT BURN GARBAGE, NAPTHA, GASOLINE OR ENGINE OIL UNDER ANY 
CIRCUMSTANCES.

6. 

KEEP THE FIRE DOOR TIGHTLY CLOSED.

7. 

IN THE EVENT OF A RUNAWAY FIRE OR CHIMNEY FIRE, CLOSE ALL COMBUSTION AIR, THE 
DAMPER CHAIN CAN BE UNHOOKED FROM THE CAM TO MANUALLY CLOSE THE DRAFT.  
CALL THE FIRE DEPARTMENT AND BE PREPARED TO EVACUATE THE HOUSE.  CORRECT 
THE PROBLEM BEFORE REFIRING.

8. 

CLEAN HEAT EXCHANGER, FLUE PIPE AND CHIMNEY REGULARLY TO PREVENT A BUILDUP 
OF SOOT OR CREOSOTE.  APPLIANCE FLUE MUST BE IN GOOD CONDITION.

9. 

STORE ALL FUEL OR COMBUSTIBLES OUTSIDE OF THE CLEARANCES LISTED AS 
“CLEARANCE TO COMBUSTIBLES”

10. 

IN THE EVENT OF A POWER FAILURE KEEP FIRE LOW - CLOSE DRAFT AIR, REMOVE 
BLOWER CABINET DOOR AND AIR FILTERS TO ASSIST FLOW - OPEN ALL REGISTERS.

11. 

SYSTEM SHOULD BE INSTALLED AND INSPECTED ANNUALLY BY A QUALIFIED PERSON.

12. 

DISCONNECT POWER BEFORE SERVICING.

13. 

“MAINTAIN COMBUSTION AIR TO BOTH FURNACES - AIR STARVATION IS DANGEROUS”.

14. 

A FRESH AIR OPENING OF AT LEAST 3.3 mm

2

/w (1 1/2 in

/ 1000btu/h) SHALL BE PROVIDED.

APPROVED ELECTRICAL COMPONENTS:

THERMOSTAT - 

WHITE RODGERS :  1E78-140

DAMPER MOTOR - 

HONEYWELL:  M847A1049B OR WHITE RODGERS 2070-5

FAN LIMIT(3) - 

WHITE RODGERS:  5D51-78

CERTIFIED TO / CERTIFIÉE SELON:  CSA Std B366.1-11

MODEL MP-80 LISTED SOLID FUEL FURNACE

MADE IN CANADA BY

Valley Comfort Systems Inc.

1290 Commercial Way, Penticton, BC, V2A 3H5

DO NOT REMOVE 

THIS LABEL

SERIAL WH

CETTE UNITÉ PEUT ÊTRE INSTALLEE COMME INDIQUÉ CI-DESSOUS:
1. 

FOURNAISE INDEPENDANTE A CIRCULATION D’AIR PULSÉ EQUIPPÉE D’UN VENTILATEUR 
HAC 900 CFM, COMME DÉMONTRÉ DANS LE DIAGRAMME “A’ CI-DESSOUS.

2. 

SÉRIE FOURNAISE COMBINÉE  AVEC CONDUITS EN AVAL, EN COMBINAISON AVEC 
N’IMPORTE QUELLE DES FOURNAISES SUIVANTES:
A. 

FOURNAISE A MAZOUT AYANT UNE CONSOMMATION DE MAZOUT TEL QU’INDIQUE  

 

SUR LA PLAQUE SIGNALETIQUE DU FABRICANT ORIGINAL, ENTRE .81 USGPH ET 1.2  

 

USGPH (MAX) DIAGRAMME “B’.

B. 

FOURNAISE A GAZ A CIRCULATION D’AIR FORCÉE AVEC UNE CAPACITE entre  

 

60000 BTU Minimum et 120,000 BTU MAXIMUM (17-35 kW) , comme affi ché sur la  

 

plaque signalétique,  avec une augmentation de température de l’air entre 39-56°C(70-100°F). 

 

LE VENTILATEUR Doit pouvoir fournir un débit de 900 CFM MINIMUM, DIAGRAMME “B’

C. 

FOURNAISE ELECTRIQUE A  AIR FORCÉE D’UNE  PUISSANCE MINIMUM DE 10  

 

KW A 25 KW, AVEC VENTILATEUR  900 CFM MINIMUM. DIAGRAM “B’.

EXIGENCES REQUISES POUR LA CHEMINÉE:

CHEMINEE POUR TOUT COMBUSTIBLE 29 po. ca. (1820 mm. ca.). NE PAS BRANCHER CETTE 
FOURNAISE A UNE CHEMINÉE QUI  EST DÉJÀ UTILISÉE  PAR UN APPAREIL AU GAZ.

EXIGENCES ELECTRIQUES REQUISES:

 120 V AC 15 A CRKT. CONTROL DU VENTILATEUR 2000 VA. 

DÉGAGEMENTS MINIMUM: 

EXTRIMITÉ POUR LE  CHARGEMENT DU BOIS 

 

48 po. 

(1200 mm)

UN 

COTE 

    6 

po. 

(150 

mm)

COTE OPPOSE (POUR L’ENTRETIEN)  

 

18 po. 

(460 mm)

TUYAU  

(MATERIAUX COMBUSTIBLES, FIL ELECTRIQUE

 

ET FOURNAISE ELECTRIQUE) 

 

18 po. 

(460 mm)

PLENUM ET 6 PREMIERS PIEDS DE TUYAU 

 

2 po. 

(50 mm)

DIMENSION MINIMUM DU RACCORDEMENT DES TUYAUX 12 po. (300 mm) x 18 po. (460 mm). NOTE 
- PAS APPROUVE POUR PLENUM PARALLELE OU DIVISÉ  (SÉRIE DES COMBINÉS APPROUVÉS 
SEULEMENT). SI INSTALLÉ SUR UN PLANCHER COMBUSTIBLE ON DOIT AJOUTER UN PROTECTION 
DE PLANCHER  MINIMUM 18 po. (460 mm) EN AVANT DE L’APPAREIL  SECTION DU CHARGEMENT. 
VOIR INSTRUCTIONS D’INSTALLATION.

INSTALLEE PAR  

ADRESSE  

DATE  

INSTRUCTIONS DE FONCTIONNEMENT:

VOIR INSTRUCTIONS DÉTAILLÉES DU FABRICANT.
1. 

BRULER DU BOIS SEULEMENT.

2. 

CHARGER LE BOIS AVEC PRUDENCE AFIN D’EVITER DES  DOMMAGES.

3. 

NE PAS CHARGER LE BOIS PLUS HAUT QUE LE BAS DE LA PORTE DE CHARGEMENT.

4. 

NE PAS ALLUMER UN FEU S’IL Y A DES VAPEURS DE MAZOUT, GAZ À PROXIMITE DE LA 
FOURNAISE.

5. 

NE PAS EMPLOYER DES PRODUITS CHIMIQUES OU DES FLUIDES POUR ALLUMER LE FEU. 

ATTENTION:

1. 

NE PAS RACCORDER DE CONDUITS DE SORTE QU’UN FLUX REVERSIBLE SOIT POSSIBLE.

2. 

FAIRE FONCTIONNER LA FOURNAISE HUILE/GAZ/ÉLECTRIQUE PÉRIODIQUEMENT AFIN DE 
VOUS ASSURER QU’ELLE FONCTIONNERA ADÉQUATEMENT LORSQUE NÉCESSAIRE.

3. 

NE PAS RELOCALISER OU CONTOURNER LES CONTRÔLES DE SÉCURITÉ À L’INSTALLATION 
DE  LA FOURNAISE ORIGINALE.

4. 

DÉBRANCHER LE COURANT ÉLECTRIQUE FOURNAISE AU BOIS ET ÉLECTRIQUE/GAZ/HUILE 
AVANT DE FAIRE L’ENTRETIEN.

5. 

NE PAS BRÛLER DE REBUT, NAPTHA, GAZ, HUILE MOTEUR EN AUCUN CAS.

6. 

GARDER LA PORTE DE CHARGEMENT HERMÉTIQUEMENT FERMÉE.

7. 

EN CAS D’UN FEU HORS DE CONTROLE OU UN FEU DE CHEMINEE, FERMER TOUTES 
LES ENTREES D’AIR DE LA FOURNAISE. POUR FERMER LE REGISTRE D’AIR A LA MAIN, 
DÉCROCHER LA CHAINE DU VOLET DU REGISTRE APPELER LES POMPIERS ET SE 
PREPARER A QUITTER LA MAISON, AVANT DE COMMENCER UN AUTRE FEU DANS LA 
FOURNAISE, CORRIGER LE PROBLEME.

8. 

NETTOYER REGULIEREMENT LES CONDUITS DE CHALEUR, LES TUYAUX ET LA CHEMINEE 
AFIN D’EVITER LA FORMATION DE CREOSOTE IL FAUT GARDER LES TUYAUX ET LA 
FOURNAISE. EN BONNE CONDITION DE FONCTIONNEMENT.

9. 

REMISER LE BOIS ET TOUT AUTRE MATERIAU COMBUSTIBLE EN RESPECTANT 
LES DÉGAGEMENTS NOTEES COMME “DEGAGEMENTS MINIMUMS DE MATERIAUX 
COMBUSTIBLES’.

10. 

EN CAS DE PANNE D’ELECTRICITE GARDER LE FEU FAIBLE - FERMER L’ACCES 
D’AIR.  ENLEVEZ LA PORTE DU VENTILATEUR ET LES FILTRES D’AIR POUR AIDER A LA 
CIRCULATION D’AIR. OUVRIR TOUS LES REGISTRES. 

11. 

LE SYSTEME DOIT ETRE INSTALLE ET INSPECTÉ TOUS LES ANS PAR UNE PERSONNE 
QUALIFIEE.

12. 

COUPER L’ALIMENTATION DU COURANT AVANT DE FAIRE L’ENTRETIEN DE LA FOURNAISE.

13. 

IL FAUT FOURNIR D’AIR A COMBUSTION AUX DEUX FOURNAISES EN TOUT TEMPS.

14. 

IL FAUT FOURNIR UNE OUVERTURE D’AIR FRAIS D’AU MOINS 3.3 mm

2

/w (1 1/2 po

/ 1000btu/h)

COMPOSANTS ELECTRIQUES APPROUVÉS:

THERMOSTAT - 

 

WHITE RODGERS:  1E78-140

MOTEUR DU VOLET - 

 

HONEYWELL :  M847A1049B OU WHITE RODGERS 2070-5

LIMITE / VENTILATEUR(3) - 

WHITE RODGERS:  5D51-78

DIAGRAM B

DIAGRAM A

4011009

CERTIFICATION LABEL

Содержание MP80

Страница 1: ...and free of cracks Before installing this unit contact the local building or fire or other authority having jurisdiction and follow their guidelines Operate only with the doors tightly closed Do not...

Страница 2: ...AN LIMIT INSTALLATION 15 THERMOSTATS 15 DOOR AND LATCH INSTALLATION 15 GENERAL CONSIDERATIONS FOR ADD ON TO GAS OIL ELECTRIC FURNACES 16 ADD ON TO ELECTRIC FURNACE 16 ADD ON TO GAS FURNACE 18 ADD ON T...

Страница 3: ...ld be inspected before use and at least annually by a qualified service person More frequent cleaning may be required due to excessive lint from carpeting bedding material etc the appliance area must...

Страница 4: ...ire door opening 12 x 13 Firebox length 26 Firebox width 14 Firebox height 19 Fire box capacity 4 cu ft Recommended Fuel length 24 Firebox design features Distributed draft system with preheated prima...

Страница 5: ...OM MP80 E V1 15 January 29 2015 Page 5 MP80 APPLIANCE DIMENSIONS...

Страница 6: ...MP80 E V1 15 January 29 2015 Page 6 MP80 PRODUCT INFORMATION Damper motor Combustion air flap Loading door Cast liners Cutaway view Combustion air vents Adjustable door latch catch Stainless steel baf...

Страница 7: ...QUELLE DES FOURNAISES SUIVANTES A FOURNAISE A MAZOUT AYANT UNE CONSOMMATION DE MAZOUT TEL QU INDIQUE SUR LA PLAQUE SIGNALETIQUE DU FABRICANT ORIGINAL ENTRE 81 USGPH ET 1 2 USGPH MAX DIAGRAMME B B FOUR...

Страница 8: ...L TIMES WET INSULATION WILL PRODUCE AN ODOUR WHEN THE APPLIANCE IS USED THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED CHILDREN AND PETS MUST BE KEPT FROM TOUCHING THE APP...

Страница 9: ...a certified appliance see not to clause 6 4 7 Add on Furnace B 139 10 Add on a solid fuel burning appliance that is designed to share the heat distribution system connected to an oil gas or electric h...

Страница 10: ...Poker 5 Ash shovel 6 Owner s manual 7 Insulation hold back strips OPTIONAL EQUIPMENT 1 Blower and cabinet for independent use 900 cfm to 1200 cfm see STAND ALONE INSTALLATION on page 21 2 CF6 kit for...

Страница 11: ...1 5 7851 5 3 180 7 51 7 27 5 3 180 27 5 72 286 03 5 7851 5 3 180 27 5 72 286 2817 5 2 6 75 25 2 03 5 7851 5 3 180 27 5 72 286 2817 5 2 6 75 25 2 22 2817 5 2 167 7 21 5 48 5 6 7 237 21 127 1 7 6 21 85...

Страница 12: ...E THE FURNACE Appliance connector shall be 24 ga black iron pipe 24 ga stainless steel pipe or double wall smoke pipe installed as per B365 10 or manufactures certified instructions NOTE double wall p...

Страница 13: ...prevent sparks from falling onto the combustible floor See CSA B365 M87 It is not required to be a heat protective covering This furnace must be installed in compliance with all local codes and regul...

Страница 14: ...mbustion air allowing for all other exhausting type appliances in the dwelling range hoods dryers etc In airtight houses it is recommended to install a fresh air inlet into the basement room where the...

Страница 15: ...surface Installation of wiring must be by a qualified electrician See specific add on type instructions for wiring diagrams that apply Wire between the junction box and the damper motor should be rou...

Страница 16: ...be at least 900 cfm Electric furnaces approved for installation in any position can be inverted and used in a down flow position using an adapter duct between the furnace and the add on as indicated i...

Страница 17: ...OM MP80 E V1 15 January 29 2015 Page 17 MP80 Fig 21 ELECTRICAL CONNECTIONS WOOD ELECTRIC WITH R AND G CONNECTIONS INSTALLATION INSTRUCTIONS cont...

Страница 18: ...HE INSTALLATION OF THE GAS FURNACE SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF CSA B365 AND IF CHANGES ARE MADE TO THE INSTALLATION OF THE GAS FURNACE INCLUDING CLEARANCES FOR SERVICING THESE SHA...

Страница 19: ...f your electrical connections Limit switches and relays may be laid out differently than shown The words and letters marked on the switches and relays should be followed and connections made to the pr...

Страница 20: ...electrical connections Fig 23 ELECTRICAL CONNECTIONS INDEPENDENT WOOD When installing in a stand alone configuration with an add on blower only 2 out of the three limit switches are used The middle l...

Страница 21: ...t for the following models Blaze King Apex CBT Valley Comfort MP80 VC120 Wood Furnace Stand Alone Applications HOT AIR PLENUM MP80 heat registers PLENUM RETURN AIR HOUSE FROM TO HOUSE VB1000 Fig 24 1...

Страница 22: ...y that it maintains a fire overnight on standby but not using high amounts of wood NOTE WOOD QUALITY AND MOISTURE CONTENT IS OF UTMOST IMPORTANCE WHEN IT COMES TO SATISFACTORY OVERNIGHT BURNS BASICALL...

Страница 23: ...mell There are many different ways to start a fire review the hints and warnings in this section to ensure the fire is started properly LIGHTING THE FIRE O O OM O OM M MP8 P80 0 E E V1 V1 1 15 5 Ja Ja...

Страница 24: ...RE NOT DRAWN INTO AND CIRCULATED BY THE AIR CIRCULATION SYSTEM THE FLUE PIPE AND CHIMNEY MUST BE INSPECTED FREQUENTLY AND CLEANED REGULARLY TO REMOVE ACCUMULATED CREOSOTE AND ASH UNDER CERTAIN CONDITI...

Страница 25: ...fire If necessary spray with a fire extinguisher or water from a garden hose 4 Do not operate the appliance again until you are certain the chimney has not been damaged CREOSOTE FORMATION AND REMOVAL...

Страница 26: ...R DRIED SEASONED HARDWOODS AS COMPARED TO SOFT WOODS OR TOO GREEN OR FRESHLY CUT WOODS BURNING WET UNSEASONED WOOD CAN CAUSE EXCESSIVE CREOSOTE ACCUMULATION WHEN IGNITED IT CAN CAUSE A CHIMNEY FIRE TH...

Страница 27: ...HIMNEY FIRE FREQUENTLY EXAMINE ALL DOOR SEALS GASKETS REPLACE IF WORN FAILURE TO SHUT FIREBOX DOOR TIGHTLY AND IGNORING LEAKING GASKETS CAN RESULT IN EXTREME OVER FIRING CONDITIONS DO NOT PROP COMBUST...

Страница 28: ...olt 1 4 20 x 3 4 FLT HD PHOS 35 4 0038 Nut 1 4 Flanged For liner bolts 38 5 0517 Fan Limit Adjustable 3 6 8008 Stainless Steel Baffle 1 7 dmpmtr Damper Motor 1 8 KS10 VC95 MP80 Cast Piece 2 9 KS13 VC9...

Страница 29: ...d User except as noted for replacement parts Warranty Period Components Covered Parts Labor Wood 1 Year X All parts materials and surface finishes flaking and peeling Subject to Conditions Exclusion a...

Страница 30: ...urchaser Please see the exclusions and limitation section below as certain restrictions and exclusions apply to this warranty How the Warranty Works 1 All warranties by the manufacturer are set herein...

Страница 31: ...King will not be responsible for inadequate performance caused by environmental conditions 10 The Limited Warranty does not cover installation and operational related problems such as use of downdraf...

Страница 32: ...hich the defect is brought to the attention of Blaze King During the 2nd year purchaser pays 20 3rd year purchaser pays 40 4th year purchaser pays 60 5th year purchaser pays 80 25 If a defect or probl...

Страница 33: ...CERTIFY THAT I HAVE INSTRUCTED THE HOMEOWNER ON PROPER FIREWOOD HANDLING YES Installer Please complete the following information Dealer Name Address ___________________________________________________...

Страница 34: ...OM MP80 E V1 15 January 29 2015 Page 34 MP80 NOTES...

Страница 35: ...OM MP80 E V1 15 January 29 2015 Page 35 MP80 NOTES cont...

Страница 36: ...OM MP80 E V1 15 January 29 2015 Page 36 MP80 NOTES cont...

Отзывы: