Thermo H plus

4 Functions of the heater

4

Functions of the heater

4.1

General functional description of the 

heater

The Thermo H plus hybrid heater integrates two different 

and independent each other coolant heating systems:

1. Generation of heat by burning liquid fuel via the diesel 

burner head - further referred to as D heater.

2. Generation of heat by electrically operated heating 

cartridges via the HV control head - further referred to 

as HV heater.

Both transmit heat to the coolant circuit via the common 

heat exchanger.

Also the function and control of the two systems is inde

-

pendent of each other and is therefore also explained 

separately for the systems.

4.2

HV heater

NOTE:

The following functional sequence applies to the opera

-

tion of the HV heater with AC or DC or both.

4.2.1 Switching on

24V DC must be connected to the HV control wiring 

harness according to the valid wiring diagram for external 

control by an operating or control element (for example, 

switch, relay, pre-selection timer) installed on the vehicle 

in order to switch on the HV heater.

This power is fed to the load contactor(s), the control ther

-

mostat and the overheat protection (see 

3.2

).

They constitute the control loop of the HV control head.

If all of the following three conditions are met:

1. 24V DC is applied to the external control input,

2. The control thermostat has not yet reached the upper 

switching threshold / has fallen below the lower swit

-

ching threshold,

3. The overheating protection has not yet reached the 

upper switching threshold, 

the respective contactor is activated, the moving core 

attracts and closes the main contacts.

In this way the heating cartridges connected to the 

contactor are powered.  

The heating cartridges now convert the electrical energy 

into heat.

4.2.2 Heating operation

The control thermostat opens its contact at 75°C and 

closes it again at 68°C. In this way, the heating operation 

is regulated.

The overheat protection opens its contact at 125°C and 

must be mechanically reset by service personnel.

ATTENTION:

After the overheating protection has been triggered, 

the cause of the overheating must first be removed 

before it is reset.

4.2.3 Switching off

When the 24V DC control voltage at the external control 

terminal is interrupted by a vehicle installed control 

element (e.g. switch, relay, pre-selection timer), the load 

contactor opens and the voltage supply of the heating 

cartridges is switched off.

The circulating pump in the coolant circuit continues its 

operation for approx. 120s.

Содержание Thermo H 160

Страница 1: ...Rev 02 2021 Id No DOK50065 001 Thermo H 160 Thermo H 230 Thermo H 300 Thermo H 350 Workshop Manual HEATING SYSTEMS...

Страница 2: ...burner head 304 4 Functions of the heater 4 1 General functional description of the heater 401 4 2 HV heater 401 4 2 1 Switching on 401 4 2 2 Heating operation 401 4 2 3 Switching off 401 4 3 D heater...

Страница 3: ...removal installation 804 8 2 6 HV DC wiring harness removal installation 806 8 2 7 HV AC wiring harness removal installation 806 8 2 8 LV DC control wiring harness removal installation 807 8 3 Diesel...

Страница 4: ...procedures are carried out incorrectly or entirely disregarded ATTENTION This caption points to actions which may cause ma terial damage NOTE This caption is used to draw attention to an important fe...

Страница 5: ...acc to DIN VDE 0105 100 and this state must be ensured for the duration of the work The following safety precautions must be observed switch off the power supply to the heater ensure it cannot be swi...

Страница 6: ...eat exchanger l 7 Minimum water flow l h 1500 Minimum capacity of the water system l 35 Antifreeze ratio in the cooling system 30 up to 60 Depending on the heat flow taken by the vehicle a minimum bur...

Страница 7: ...ENTION While using the fuels their operating limits must be considered and if necessary suitable measures nozzle preheating electrical heated filter should be applied If fuel is supplied from the vehi...

Страница 8: ...addi tional cross beam The hybrid function of the heater includes the generation of heat a by burning liquid fuel and b by electric current The diesel burner head see Fig 301 is responsible for heat...

Страница 9: ...xchanger 8 3 1 1 Small distribution board The small distribution board 3 Fig 302 includes the components required for the electrical part of the heater which are mounted on a 35mm top hat rail The top...

Страница 10: ...e front has receiving openings with threads for the heating cartridges At the rear the Diesel burner head is fixed 3 2 1 Combustion chamber The combustion chamber 8 Fig 303 is located inside the heat...

Страница 11: ...diesel burner head is used to generate the diesel air mixture which is burned in the combustion chamber Components for the control of the combustion process are integrated Further information can be f...

Страница 12: ...rotection see 3 2 They constitute the control loop of the HV control head If all of the following three conditions are met 1 24V DC is applied to the external control input 2 The control thermostat ha...

Страница 13: ...ignition spark The flame is monitored by a flame detector integrated into the control device Depending on the equipment the heater is switched on and off using a digital timer switch or climate contr...

Страница 14: ...e The burner motor does not run during the entire preheating time It starts at the latest 12 seconds before the expiry of the determined preheating time with the initial cycle The time of the initial...

Страница 15: ...smoke formation A minimum burner combustion period of 120 second is targeted For ambient and operating conditions this target is not always achieved In order to achieve the minimum combustion period t...

Страница 16: ...id valve No start No flame detection within 15 seconds after opening the solenoid valve Temperature sensor delivers unacceptable tempera ture values Burner motor speed signal faulty Voltage falls shor...

Страница 17: ...or interruption of electrical compo nents Solenoid valve Flameguard Overheating protection the temperature sensor overheat protection water temperature sensor is unplugged Flame is not expired within...

Страница 18: ...the HV control wiring harness 24V defective or contact not established Plug of the temperature sensors not connected Temperature sensors defective HV small distribution board defective HVIL Interloop...

Страница 19: ...t does not transmit a HVIL signal HVIL contact is not established Hood not correctly mounted HV cable not connected HV control wiring harness 24V not connected or cable defective Heating power too low...

Страница 20: ...tallation given in the Thermo H Installation and operating instructi on The document is available for download at www va leo thermalbus com eu_en Service Downloads Heating systems Thermo H plus With t...

Страница 21: ...602 Thermo H plus 6 Wiring diagrams HV heater Fig 601 Housing removal for devices Thermo H plus DC DC 7 0 7 0 kW heater ident no acc to model plate 11143458A and 11143457A...

Страница 22: ...603 Thermo H plus 6 Wiring diagrams HV heater Fig 602 Housing removal for devices Thermo H plus AC 20 0 kW heater ident no acc to model plate 11139571A and 11143481A...

Страница 23: ...s 6 Wiring diagrams HV heater Fig 603 Housing removal for devices Thermo H plus DC 20 0 kW heater ident no acc to model plate 11139574A and 11142595A HV Cable Id no Heater Id no 11124288 11139574A 111...

Страница 24: ...605 Thermo H plus 6 Wiring diagrams HV heater Fig 604 Housing removal for devices Thermo H plus AC 20 0 kW heater ident no acc to model plate 11142671A...

Страница 25: ...606 Thermo H plus 6 Wiring diagrams HV heater Fig 605 Housing removal for devices Thermo H plus AC 7 0 kW heater ident no acc to model plate 11142686A...

Страница 26: ...AC 20 0 kW heater ident no acc to model plate 11139571A 11143481A and 11142671A 1 2 3 4 5 6 7 8 9 HLP DC Connecting HLP Anschluss HLP HLP orange cable oranges Kabel blue cable blaues Kabel 1 DC2 DC3 4...

Страница 27: ...for devices Thermo H plus AC 7 0 kW heater ident no acc to model plate 11142686A 1 2 3 4 5 6 7 8 9 HLP DC Connecting HLP Anschluss HLP HLP orange cable oranges Kabel blue cable blaues Kabel 1 DC16 DC...

Страница 28: ...in front of the heater Note for F2 The max possible for the design value is shown The fuse is to be adapt under circumstances acc to the smaller cable cross section of the connected circulating pump...

Страница 29: ...ax 25A min 7 5A because of DVW Terminal 30 permanent plus Terminal 31 ground Overheat protection Coolant temperature sensor Terminal 61 D SG 1589 BM UP 1 U V W 1 2 4 3 4 1 2 2 1 2 3 1 1 5 2 2 6 3 3 8...

Страница 30: ...ZFG Electronic ignition unit in the heater MV Solenoid valve in the heater BM Combustion air motor in the heater Legend for wiring diagrams Connector Description C To vehicle Power C1 Terminal 30 UP D...

Страница 31: ...unning while the heater is switched on for tests inspections 7 2 HV heater servicing The necessary service work can be found in the main tenance plan for the Thermo AC DC heater series This can be dow...

Страница 32: ...hile the heater is installed in the vehicle assuming that sufficient space is available and no components will be damaged NOTE If components are disassembled to a degree not covered in this workshop m...

Страница 33: ...cap 4 of the temperature limiter 2 back until it can be put in its installation position 4 Position temperature limiter 2 in the reception neck 5 and push in the retaining clip 3 ATTENTION The retaini...

Страница 34: ...errated washer 10 and vehicle grounding cable lug 7 Remove nuts 16 and washers 15 NOTE During the next step pay attention that the cables are not jammed or are still connected Danger of damage 8 Remov...

Страница 35: ...ctions to be established refer to wiring diagrams in Chapter 6 depending on the heater version Compare the heater ident number under the wiring diagram with that on the model plate of your heater 5 In...

Страница 36: ...805 HV Control head Removal and Installation of components 1 2 3 4 7 8 9 10 11 12 13 14 15 16 17 18 19 8 1 Nm 1 5 0 3 Nm 16 1 Nm 15 1 Nm 5 1 Nm 2 0 5 Nm 10 1 Nm 10 1 Nm 8 1 Nm 27 28 20 21 23 22 24 15...

Страница 37: ...nnected Danger of damage 8 Loosen cable gland 17 Fig 805 and screw it with the appropriate cable harness from out the housing 12 Installation NOTE During the next step pay attention that the cables ar...

Страница 38: ...all supply cables from vehicle electrical system 3 Remove hood see 8 2 2 4 Remove housing see 8 2 3 5 If necessary disconnect connectors from the HVIL socket Fig 808 6 Remove ties wich bundle disconne...

Страница 39: ...e heater and secure it for duration of the work Observe 1 6 3 2 If necessary disconnect the combustion air intake line from the heater 3 If required disconnect heater wiring harness plug from control...

Страница 40: ...tection Risk of injuries if coolant temperature is increased Removal 1 Establish voltage free state of the heater and secure it for duration of the work Observe 1 6 3 2 Disconnect the temperature sens...

Страница 41: ...between 2 and 10 o clock not upwards Fig 811 A position change during maintenance is permissible and affects the expected service life of the combustion chamber positively Position the cut outs in the...

Страница 42: ...gs 21 refer to 8 2 5 3 Screw the plug screw 7 Fig 809 in and tighten it 4 Install the screw in socket 8 Fig 801 and tighten it 5 Install the stud bolts 18 using new gasket rings 13 and tighten them 6...

Страница 43: ...Place the heater into the installation position and secure with 4 nuts and 4 washers via the vibration damper 4 Fig 811 to the vehicle Tighten nuts as required 3 Reconnect the fuel lines for fuel sup...

Страница 44: ...acturer specification Risk of scalds if coolant temperature is increased The Aquavent 5000 U4814 and Aquavent 6000S U4855 circulating pumps may only be switched on for bleeding after dry operation can...

Страница 45: ...retrofits 9 Modifications and retrofits 9 1 General For further optimization the heaters are continuously improved Units in the field can usually be upgraded or retrofitted For this purpose respectiv...

Страница 46: ...sure that handling transport and storage will not damage them ATTENTION If a complete heater is sent back it must be comple tely drained While packaging and or shipping it must be ensured that no fuel...

Страница 47: ...memos...

Страница 48: ...rcial Vehicles Germany GmbH Friedrichshafener Str 7 82205 Gilching Germany Tel 49 8105 7721 0 Fax 49 8105 7721 889 www valeo thermalbus com service valeobus valeo com Valeo Thermal Commercial Vehicles...

Отзывы: