Troubleshooting 

Motor 

Motor Symptom 

Probable Cause 

Action 

Motor doesn't start 

Blown fuse or open circuit breaker 

Replace fuse or reset circuit breaker 

Overload trips 

Check and reset overload 

Improper line connections 

Check connections on diagram supplied with motor 

Open circuit in winding or starting switch; humming 

sound from motor when switch is closed 

Replace motor 

Improper current supply 

Check that power supply agrees with motor specifications 

listed on nameplate 

Mechanical failure 

Determine that motor turns freely; if not, replace motor 

Motor overload 

Reduce load 

Power source (3-phase) may have  

one phase open 

Check line for open phase 

Motor doesn't come up  

to speed 

Motor under-designed for the application 

Replace with larger motor 

Voltage too low at motor terminals 

Check across AC line and correct if possible 

Line wiring to motor too small 

Install larger wiring 

60-Hz motor connected to 50-Hz line supply 

Replace unit with 50-Hz motor 

Motor wired for wrong voltage 

Check wiring 

Motor takes too long to 

accelerate to speed 

Excessive load 

Consult the factory 

Loose connection(s) 

Check connection and tighten where necessary 

Motor rotates in  

wrong direction 

Improperly wired to AC line;  

wrong sequence of phases 

Check wiring diagram on motor nameplate and correct; 

reverse any two motor leads at line connection 

Motor vibrates excessively 

Motor mounting bolts are loose 

Tighten mounting bolts 

Propeller is unbalanced 

Replace propeller 

Motor overheats 

Motor overloaded 

Replace with larger motor 

Motor fan may be clogged with dirt,  

preventing proper ventilation 

Remove fan cover and clean; replace fan cover 

Motor (3-phase) may have one phase open 

Check that all connections are tight 

Line voltage too high 

Check across AC line. Consult power company;  

step-down transformer may be required. 

Line voltage too low 

Check across AC line. Consult power company;  

step-up transformer may be required. 

 

 

 

Содержание 478603

Страница 1: ...MECHANICAL INSTALLATION OPERATION MAINTENANCE VRC Series IOM M2 0316 Part Number 478603...

Страница 2: ...learances 4 Lifting Procedure 4 Installation 6 Pad Installation 6 Equipment Support Installation 6 Electrical and Refrigeration Connections 8 Electrical Connections 9 Refrigeration Connections 10 Main...

Страница 3: ...before restoring power The Clean Air Act of 1990 bans the intentional venting of refrigerant CFC and HCFC as of July 1 1992 Approved methods of recovery recycling or reclaiming refrigerant must be fol...

Страница 4: ...at the top of the unit Unit must be lifted using all lifting lugs on the exterior of the unit Lifting Lug Quantities Casing Lugs 110 4 210 4 310 4 Cables or chains should be at least double the lengt...

Страница 5: ...789 8550 Part Number 478603 USE ALL PROVIDED LIFTING LUGS USE SPREADER BAR TO PREVENT DAMAGE TO UNIT CHAIN ANGLE AT POINT OF LUG MUST NEVER EXCEED 20 FROM VERTICAL TEST LIFT UNIT TO CHECK FOR PROPER...

Страница 6: ...nd the units have properly undergone the pre startup and startup routines Sound Insulation If the ventilator indoor unit is to be installed above or adjacent to a sound critical area such as an office...

Страница 7: ...rt 800 789 8550 Part Number 478603 Minimum Pad Dimensions Unit A B 110 37 75 80 25 210 49 75 110 25 310 66 50 117 00 Dimensions in inches Equipment Support Dimensions Unit A B 110 32 75 75 25 210 44 7...

Страница 8: ...ions The following diagrams show piping locations as well as suggested field penetration locations for high voltage and low voltage electrical connections Refer to the Recommended Line Sizes table on...

Страница 9: ...need to be connected between the ventilator unit and condenser Refer to the table below for required field wiring All control wiring is low voltage 24 volts or less Fan modulation signal wiring 0 10...

Страница 10: ...ge line If the discharge pipe contains multiple vertical rises and horizontal sections a drip leg must be installed at the bottom of any rise over 10 Pipe the oil drip legs as shown in the Refrigerati...

Страница 11: ...r 2 turns Low superheat and normal subcooling Under restricted Tighten TXV adjustment screw by 1 or 2 turns High superheat and high subcooling Over restricted Loosen TXV adjustment screw by 1 or 2 tur...

Страница 12: ...A oz Circuit B oz 110 5 10 7 12 5 1 0 8 15 6 17 9 1 1 10 20 2 N A 1 8 210 10 9 8 8 0 13 6 11 8 1 0 1 0 13 11 0 12 9 13 6 15 8 1 0 1 1 16 16 4 13 5 18 1 15 0 1 1 1 1 18 16 2 17 0 20 4 20 9 1 1 1 8 20 2...

Страница 13: ...ressure water can be used to clean coils Spray in the direction opposite the airflow to push dirt out the front of the coil Test the spray pressure on a small area on a corner of the coil to see how w...

Страница 14: ...rect if possible Line wiring to motor too small Install larger wiring 60 Hz motor connected to 50 Hz line supply Replace unit with 50 Hz motor Motor wired for wrong voltage Check wiring Motor takes to...

Страница 15: ...ed DX Startup Form to Valent via US Mail Valent Startup Forms 60 28th Avenue North Minneapolis MN 55411 E mail Subject Valent Startup Forms OAPservices unisoncomfort com Fax ATTN Valent Startup Forms...

Страница 16: ...System has been pressure checked to 450psi with nitrogen for 1 hr System has been evacuated to less than 500 microns before charging Condenser Startup Form Prior to starting the unit ensure that all a...

Страница 17: ...Certified Technician Startup services include verifying proper operation of the unit including proper refrigerant charge and repair of minor refrigerant leaks outside the coil At the completion of st...

Страница 18: ...ties begin at start up or 6 months after the date of shipment from the Unison factory whichever occurs first The ship date for the units noted above is Please refer to the Unison Comfort Technologies...

Страница 19: ...eration 10 Cooling coil maintenance 10 13 Curb Dimensions 7 Installation 6 Design requests 3 Ductwork dimensions 7 Installation Curb 6 Pad 6 Lifting instructions 4 Line sizes 11 Model numbers 3 Motor...

Страница 20: ...March 2016 Valent is a business of Unison Comfort Technologies For service inquiries please contact Unison Comfort Technologies Technical Service 800 789 8550 OAPservices unisoncomfort com...

Отзывы: