8.6.4 Floor Protection
OPTION INSTALLATION TYPE
R FACTOR
REQUIRED
A
B
C
#1
On floor level
Yes (1.00)
16"
(406 mm)
36 ¾"
(933 mm)
8"
(203 mm)
#2
Raised base of less than 4"
Yes (1.00)
16"
(406 mm)
36 ¾»
(933 mm)
8"
(203 mm)
#3
Raised base of 4" or more
No
16"
(406 mm)
36 ¾»
(933 mm)
8"
(203 mm)
Regardless of the installation type, there must
be at least 8" (203 mm) on each side of the
fireplace door opening
(C)
.
Floor protection must be a continuous non-
combustible surface such as ceramic, concrete
board, brick or other equivalent material
approved as floor protection. If the ceramic
is used, it must be placed on a continuous
non-combustible panel to prevent spills from
being brought into contact with the floor
through cracks or gaps in the ceramic slurry.
Alternatives approved by the local building
code may also be used.
Do not leave carpets under the floor
protection.