background image

Valcom Master Clock 

(V2)

 

 

Page 19 

 

“1” = 58

th

 minute (1) - The hourly correction for 55 seconds every hour from XX:58:05 to XX:59:00. 

 

The daily correction (5 a.m. & 5 p.m.) is ten correction cycles sent to the relay (each for 95 seconds) 

 

beginning at 5:05:00, 5:07:00, 5:09:00, 5:11:00, 5:13:00, 5:15:00, 5:17:00, 5:19:00, 5:21:00, 

 and 

5:23:00. 

 

“2” = 58

th

 minute (2) - The hourly correction for 60 seconds every hour from XX:58:00 to XX:59:00. 

 

The daily correction (5 a.m. & 5 p.m.) is twelve correction cycles sent to the relay (each for 65 sec-

 

onds on and 25 seconds off) beginning at 5:05:00 to 5:22:35. 

 

“3” = 58

th

 minute (3) - The hourly correction for 60 seconds every hour from XX:58:00 to XX:59:00. 

 

The daily correction (5 a.m. & 5 p.m.) is twelve correction cycles sent to the relay (each for one min-

 

ute on and two minutes off) beginning at 5:06:00. 

 

“4” = 58th minute (4) - The hourly correction for 55 seconds every hour from xx:58:05 to XX:59:00.  

 

The daily correction (5 a.m. & 5 p.m.) is 12 correction cycles for 55 seconds.  The timings will be 

 

05:03:05, 05:07:05, 05:11:05, 05:15:05, 05:19:05, 05:23:05, 05:27:05, 05:31:05, 05:35:05, 

 

05:39:05, 05:43:05 and 05:47:05. 

 

“5” = 59

th

 minute - The hourly correction for 8 seconds every hour from XX:57:54 to XX:58:02. The 

 

daily correction (5 a.m. & 5 p.m.) is a 14 second pulse from 5:57:54 to 5:58:08. 

 

“6” - National Time & Rauland_1 – The hourly correction is for 25 seconds every hour from XX:00:00 

 

to XX:00:25.  The daily correction (6 a.m. & 6 p.m.) is 25 seconds on, 35 seconds off every minute 

 

for 24 minutes. 

 

“7” = National Time & Rauland_2 – The hourly correction is for 25 seconds every hour from  

 

XX:00:00 to XX:00:25.  This option only has hourly corrections. 

 

“8” - Once a Day Pulse - The Once a Day Pulse allows the user to manually configure when the relay 

 

will close and for how long it needs to close for.  If this option is selected on either option 20 or 25, 

 

and the top button is pressed, a new set of parameters may be accessed to set the Once a Day clo-

 

sure settings.  They are the following: 

 

Option 21 (Clock 1) & Option 26 (Clock 2) = Set Hour for relay to close 

    Option 22 (Clock 1) & Option 27 (Clock 2) = Set Minutes for relay to close 

    Option 23 (Clock 1) & Option 28 (Clock 2)= Set Seconds for relay to close 

     Option 24 (Clock 1) & Option 29 (Clock 2) = Set Duration for relay to close 

 

 

 

  “9” - Rauland Digital - The relay closes for a half second for every minute that it needs to advance. 

 

System Connections - Wired Systems 

Sync-Wire Communication - Protocol Definitions 

Содержание V-WMCA

Страница 1: ...Valcom Master Clock V2 V WMCA V GPSA V GPS TX Valcom Inc 5614 Hollins Road Roanoke VA 24019...

Страница 2: ...Output Setting Clock 2 Relay Output Setting the Primary Input Setting the Secondary Input Setting the Offset Setting the Bias Seconds Setting Once a Day Pulse Input Sending Diagnostics Sync Wire Proto...

Страница 3: ...at the designated markings from step 1 4 Install the four anchors in the holes that were just drilled 5 Install the first two screws in the top holes leaving 1 8 of the thread exposed 6 Line up the t...

Страница 4: ...32 port is used for debugging only Power Input This power outlet is used to power up the Valcom master clock 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 9 10 Installing the Master Clock with the Line Cord Recepta...

Страница 5: ...nections Wired Systems 2 Wire Communication V CCU V C6124P 24 volt outputs 24 VDC IN DATA IN 19 18 2 Wire Digital Output to Clocks V D2425 or V D2440 V A2412 or V A2416 Orange Yellow Black White V C61...

Страница 6: ...Valcom Master Clock V2 Page 6 System Connections Wired Systems Sync Wire Communication via Clock 1 or 2 10 Amp Contact Rating...

Страница 7: ...Hot 24VAC Neutral 24VAC Hot N O COM This system can accommodate both a primary and secondary for backup auxiliary time synchronization input The following protocols cannot be used simultaneously 59 mi...

Страница 8: ...ts Sync Wire Inputs Installation National Time Rauland Rauland Digital Dry Contact Closure 110VAC Interface 24VAC Interface 7 17 8 12 16 17 15 17 110VAC Neutral 110VAC Hot 24VAC Neutral 24VAC Hot N O...

Страница 9: ...Valcom Master Clock V2 Page 9 Inputs Sync Wire Inputs Installation Dukane Digital Once a Day Pulse Dry Contact Closure 7 17 8 12 N O COM 7 17 14 8 Minute Pulse Ground 13 Reset...

Страница 10: ...Patch Cable Installation Wall Jack to Network Fig 1 1 1 Connect a patch cable to the RJ45 port on the Valcom Master Clock as shown in Fig 1 1 2 Connect the other end of the patch cable to an Ethernet...

Страница 11: ...on the left side of the LED display This prompt allows the user to set the month Use the bottom button to scroll between 01 12 Programming the Valcom Master Clock Press both buttons on the front pane...

Страница 12: ...ry hour Press the top button to enter option 12 The num ber 12 will appear on the left side of the LED display This option allows the user to enable or disable Daylight Savings Time Press the bottom b...

Страница 13: ...side of the LED display This option allows the user to set the min utes at which the relay will close Press the bottom button to scroll through 00 59 Press the top button to enter option 20 The num be...

Страница 14: ...on the left side of the LED display This option allows the user to set the hour at which the relay will close Press the bottom button to scroll through 00 23 Press the top button to enter option 23 Th...

Страница 15: ...02 59 Minute Correction 03 58 Minute Correction 1 04 58 Minute Correction 2 05 58 Minute Correction 3 06 58 Minute Correction 4 07 National Time Rauland 08 Dukane 09 Rauland Digital 10 Wireless Repea...

Страница 16: ...et to 11 Press the top button to enter option 31 The number 31 will appear on the left side of the LED display This option allows the user to select the secondary auxiliary input Press the bottom butt...

Страница 17: ...A 00 will appear on the right side if it is not receiving an Internet Connec tion This option is a read only option Press the top button to enter option 35 The num ber 35 will appear on the left side...

Страница 18: ...ss the bottom button to scroll be tween E d Setting the option to E will enable the option and will enter diagnostic mode Setting the option to d will disable the option and upon depressing the top bu...

Страница 19: ...47 05 5 59th minute The hourly correction for 8 seconds every hour from XX 57 54 to XX 58 02 The daily correction 5 a m 5 p m is a 14 second pulse from 5 57 54 to 5 58 08 6 National Time Rauland_1 Th...

Страница 20: ...and editing events and schedule changes The default password for the user level is 1111 It can be changed in the technician level The technician level password is 6063 and gives you full access to al...

Страница 21: ...ered in 24 hour format HH MM SS After typing in the desired time click the Submit button to set the time on the unit if there is no input connected Date This field is where the current date is display...

Страница 22: ...24 hour mode enabling or disabling Daylight Savings Time and editing the standard durations for each zone Database Maintenance This link when clicked will bring the user to the Database Maintenance s...

Страница 23: ...Valcom Master Clock V2 Page 23 Web Browser Programming System Settings Page 1 1 2 3 4 5 6 7...

Страница 24: ...MT Offset This field sets the positive or negative offset for GMT time For instance eastern time zone is a nega tive five hour offset See Fig 3 1 for typical offsets Submit This button when pressed wi...

Страница 25: ...Valcom Master Clock V2 Page 25 System Settings Page 2 Web Browser Programming 1 2 3 4 5 6 7 8...

Страница 26: ...Digital and once a day Pulse An example of a configuration would be SNTP being the primary input and 58 minute correction being a secondary input Setting the primary source to 59 minute sync and the...

Страница 27: ...Valcom Master Clock V2 Page 27 IP Settings Page 1 Web Browser Programming 1 2 3 4 5 6 7 8 9...

Страница 28: ...may be needed for certain networks IP Address This field allows the user to set the IP address for the device DHCP This drop down list allows the user to turn DHCP on or off DHCP allows the master cl...

Страница 29: ...which NTP servers that the master clock will try to acquire time from Submit This button when pressed will save all of the information to the master clock Cancel This button when pressed will clear o...

Страница 30: ...he master clock IP Address This display the IP address for the master clock Device Name This displays the device name for the master clock Menu This button when pressed will bring the user back to the...

Страница 31: ...option they want The option can be disabled pre 2007 and post 2007 Pre 2007 has the old style daylight savings time format that was enacted prior to 2007 Post 2007 daylight savings time is the current...

Страница 32: ...for backup purposes Choose File This button when pressed will allow the user to browse for the saved db file that contains the saved events and schedules Download This button when pressed will downloa...

Страница 33: ...r through a cross over cable Yes the Valcom Master Clock can be accessed through a cross over cable or via a LAN connection What is the maximum length I can go with the GPS cable When the GPS option i...

Страница 34: ...an unobstructed area that is in complete view of the sky Also check to make sure the connections on each end of the cable are securely tightened Lastly verify that there are no kinks or breaks in the...

Отзывы: