Val6 FIR-X5 Скачать руководство пользователя страница 9

Result

Cause

Remedy

How to check

Phenomenon

2

D. Display「A3」

Failure of overheat protection

Replace overheat protection

Disconnection of overheat
protection cord.

Replace overheat protection cord

Lack of burner packing

Add burner packing

Deterioration of burner packingReplace burner packing

Failure of burner controller.

Replace burner controller

E.

Display「A4」

※Tip-over detector operation.

Failure of tip-over switch
cord

Replace tip-over switch cord

Failure of burner controller

Replace burner controller

F. Display「A5」

Does not rotate or it move slowly

Combustion fan is locked

Cancel the lock or replace combustion fan

DC 170V

Failure of combustion fan

Replace combution fan

DC 0V

Failure of burner controller

Replace burner controlller

G. Display「A6」

Lower than AC70V

Supplied voltage is too low

Operate with appropriate power source

Failure of burner controller

Replace burner controller

H. Display「HV」

Measure the voltage of AC outlet

More than AC 145V

Supplied voltage is too high

Operate with appropriate power source

Failure of burner controller.

Replace burner controller

I. Display「A7」

Failure of burner controller.

Replace burner controller

3

Display「A1」

A. Fuel pump does not operate at all.

∞Ω

Failure of fuel pump.

※High voltage detection.

「A7」is not displayed
 (A ambient temperature is displayed)

Disconnection of fuel pump
connector

「A3」is not displayed
 (A ambient temperature is displayed)

Plug connector (CN11) firmly

Disconnection of overheat
protection connector.

Plug connector (CN3) firmly

Normal indication after 3
consecutive misfire

Plug connector (CN11) firmly

Replace tip-over switch

※When overheat protection is operated

Plug connector (CN5) firmly

Disconnection of fuel pump
connector

-

※Low voltage stop.

Standard: black-black : Conduction in horizontal(0Ω) ⇒
Figure3 (P.17)

※3 consecutive misfire.

※Combustion fan abnomality detection .

Plug connector (CN1) firmly

「A5」is not displayed
 (A ambient temperature is displayed)

standard: AC 120V ⇒ Figure4 (P.17)

「A6」is not displayed
 (A ambient temperature is displayed)

「A3」is not displayed
 (A ambient temperature is displayed)

Replug in combustion fan connector (CN 3) and then
turn on

Replug in tip-over detector connector (CN 11), and
then turn on

standard: AC 120V ⇒ Figure 4 (P.17)

Unplug the fuel pump (CN 5)  from burner controller,
then measure resistance values

Replug in power cable(CN1), and then turn on

Replug in the fuel pump connector (CN 5), and then
turn on

Measure the voltage of AC outlet

Turn off the operation switch, and then plug the power
cable again

※When it does not correspond to the above content

※When it does not correspond to the above content.

※When it does not correspond to the above content

Measure the voltage at CN3 terminal on burner controller

Unplug tip-over detector connector (CN 11),
and then check lead with multimeter

Confirmation of burner packing ⇒ Figure15 (P.23)

※When it does not correspond to the above content

「A1」is not displayed
 (A ambient temperature is
displayed)

※When it does not correspond to the above content

Replug overheat protection connector (CN 11) , and
then turn on

The heater does not ignite.

Unplug overheat protection connector (CN 11), and
then check conduction with multimeter

The heater does not start.

Standard: red-red : Conduction(0Ω) ⇒ Figure3
(P.17)

Turn the combustion fan by hand

standard: DC 170V ⇒ Figure4 (P.17)

It does not conduct when operation
switch is turned on(∞Ω)
(Overheat protection is not
detected)
It does not conduct when operation
switch is turned on(∞Ω)
(Overheat protection is detected)

Disconnection of tip-over
connector

Failure of tip-over switch

Disconnection of combustion fan
connector.

Disconnection of power
source connector

It does not conduct in horizontal

Replace pump

standard: blue-blue:about 88Ω ⇒ Figure3 (P.17)

Содержание FIR-X5

Страница 1: ...15 7 Troubleshooting Standard resistance Voltage Check Repair Names of Components Safety Devices Error Code Sequence Time Chart Wiring Diagram Specifications 6 9 8 5 ED2 2021 08 Contents 1 2 4 3 Main...

Страница 2: ...ol mode lamp 7 Fuel tank 22 Fuel preheater 36 Auto control mode lamp 8 Fuel gauge 23 Fuse 37 Off timer setting button 9 Fuel tank cap 24 Preheating lamp 38 Continuous Conbustion lamp 10 Burner cover B...

Страница 3: ...e A2 is displayed When it pasted 60 minutes after the heater detects a out of fuel The error code A2 is displayed and Post purge sequence runs for 5 minutes Overheat protection When the heater overhea...

Страница 4: ...elay timer e Stable time Solenoid valve delay timer Fuel pre heater When the power cord is connected the heater preheats for 3 minutes if the outside temperature is less than 41 50sec e 300sec Post pu...

Страница 5: ...ower Supply AC 120V 60Hz Power Consumption Igniting 65W Burning 45W Lv 5 41W Lv 4 37W Lv 3 34W Lv 2 31W Lv 1 44W When Preheater is operating Electric Fuse 3A 250 Operating Noise Level 56 dBA Lv 5 55dB...

Страница 6: ...4 3 10 The heater does not start The heater does not ignition Smoke comes out Fuse blows out Smell of fuel comes out 8 7 Combustion is not stable Misfire within 40 seconds after ignition 7 Display LV...

Страница 7: ...ce values Unplug igniter connector CN 4 from electrode then measure coil resistance values of the high voltage side Fuse does not blow out standard red red about 1 8k Figure 3 P 17 Unplug fuel pump co...

Страница 8: ...ure of burner controller Disconnection of operation switch connector Disconnection of operation switch cord When power outage safety device is operated It works normally Lamps is lit standard yellow y...

Страница 9: ...horizontal 0 Figure3 P 17 3 consecutive misfire Combustion fan abnomality detection Plug connector CN1 firmly A5 is not displayed A ambient temperature is displayed standard AC 120V Figure4 P 17 A6 is...

Страница 10: ...fuel other than diesel and kerosene Low quality fuel Operate with appropriate fuel Be mixed with water Diesel and kerosenel goes bad Measure the alignment of electrode Part is out of standard positio...

Страница 11: ...f tip over detector connector Replace tip over switch cord Disconnection of tip over connector Plug connector CN11 firmly Ambient temperature is too high Failure of flame monitor Ignition not detected...

Страница 12: ...gen concentration is low Check the fuel Figure 8 P 19 Use fuel except diesel and kerosene Low quality fuel Operate with appropriate fuel Be mixed with water Diesel and kerosenel goes bad 8 Fuel leaks...

Страница 13: ...e fuel Be mixed with water Diesel and kerosenel goes bad 11 Combustion is not stable Check looseness of each joints The connection has become loose Air is coming Fasten joints more tightly An oxygen c...

Страница 14: ...on Voltage Memo CN1 Black White 120 CN4 Black Black Input side 120 CN3 Red Blue DC 170V CN5 Blue Blue about DC 50V 4 8PIN White White Input side 120 CN2 1 2PIN Red Red Output1 about 12 5V 5 6PIN Yello...

Страница 15: ...g a fuel pump Positioning a electrode Cleaning a flame monitor Checking a burner cone Whirl vane Stabilizer Adjusting an air inlet opening of fan motor Overheat protection system Burner packing P 19 P...

Страница 16: ...rner cover off Removing a burner unit Figure Disconnect the 4 connectors from the burner controller Overheat prevention Tip over switch Fuel sensor Operation board connector Temperature sensor refer t...

Страница 17: ...r code Make sure the power cord is disconnected Make sure the power cord isdisconnected when measuring resistance Operate the heater Turn on the multimeter and set AC voltage range partially direct cu...

Страница 18: ...hen take the cover cover off 2 Take out the fuse from the fuse holder 3 Replace with a new one 4 Close the fuse holder 5 Put the burner cover back and then tighten screws Figure Figure Take out the op...

Страница 19: ...e fuel tank until the fuel is completely drained out of the tank At the same time be careful not to lose the drain bolt packing only into a can or other container approved in your Next use a 24mm wren...

Страница 20: ...hen check whether or not fuel comes out Please be careful because the fuel strongly comes out Positioning a electrode Take out a burner and check each clearance as below Figure9 Figure10 Fuel outlet 9...

Страница 21: ...and check whether or not its lens is dirty foul If the lens is dirty foul clean the surface of the lens with a soft coton swab or cloth untill it is clear Replace the flame monitor Then securely repl...

Страница 22: ...nd cover take off the overheat protection system installed inside burner main body Burner section Pre heater section Figure13 Loosen a screw and then extend narrow an air inlet opening Also trial oper...

Страница 23: ...packing 1 and Burner packing 2 Check if Burner packing 1 and Burner packing 2 are not damaged Take out the burner cover and unit from main body as detailed in Figure 1 and 2 Figure15 Burner packing 1...