![Val Controls IDC24 Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/val-controls/idc24/idc24_user-manual_849423020.webp)
DID-UM-004
Val Controls A/S
•
Limfjordsvej 3
•
DK-6715 Esbjerg N
•
Tel. +45 7547 0600
•
Fax +45 7547 0611
•
www.valcontrols.com
Revision: 3
20/25
Range: 0-12000000
Divider: 1000
Unit: sec
Description: Low limit for breakaway
time warning
43344
2 RW
U32
Breakaway time high
Default: 00000
Range: 0-12000000
Divider: 1000
Unit: sec
Description: High limit for breakaway
time warning
43356
1 RW
U16
Breakaway pressure low
Default: 00000
Range: 0-65535
Divider: 100
Unit: bar
Description: Low limit for breakaway
pressure low
43357
1 RW
U16
Breakaway pressure high
Default: 00000
Range: 0-65535
Divider: 100
Unit: bar
Description: High limit for breakaway
pressure high
43346
2 RW
U32
PST time low
Default: 00000
Range: 0-12000000
Divider: 1000
Unit: sec
Description: Low limit for partial
stroke time warning
43348
2 RW
U32
PST time high
Default: 00000
Range: 0-12000000
Divider: 1000
Unit: sec
Description: High limit for partial
stroke time warning
43350
2 RW
U32
PST total time low
Default: 00000
Range: 0-12000000
Divider: 1000
Unit: sec
Description: Low limit for total time
warning
43352
2 RW
U32
PST total time high
Default: 00000
Range: 0-12000000
Divider: 1000
Unit: sec
Description: High limit for total time
warning
43355
1 RW
U16
Travel low
Default: 1500
Range: 0-10000
Divider: 100
Unit: %
Description: Low limit for stroke
warning
43354
1 RW
U16
Travel high
Default: 2500
Range: 0-10000
Divider: 100
Unit: %
Description: High limit for stroke
warning
Register Len Access
Type
Name
Parameter Range/Units/Notes
FST error parameters
43461
1 RW
U16
Enable errors
Default: 00002
Range: 00002: Yes;00001: No;