Unit: sec
Description: Depressurising time,
only available with pressure sensor
43679
2 RO
U32
EST total time
Range: 0-12000000
Divider: 1000
Unit: sec
Description: Total time
5.5
Configuration
Register Len Access
Type
Name
Parameter Range/Units/Notes
PST error parameters
43311
1 RW
U16
Enable errors
Default: 00002
Range: 00002: Yes;00001: No;
Description: Show PST errors
43318
1 RW
U16
Start pressure low
Default: 00000
Range: 0-65535
Divider: 100
Unit: bar
Description: Start pressure low for the
partial stroke
43319
1 RW
U16
Start pressure high
Default: 00000
Range: 0-65535
Divider: 100
Unit: bar
Description: Start pressure high for
the partial stroke
43312
2 RW
U32
Breakaway timeout
Default: 00000
Range: 0-12000000
Divider: 1000
Unit: sec
Description: Breakaway timeout for
the partial stroke test
43321
1 RW
U16
Minimum breakaway pressure
Default: 00000
Range: 0-65535
Divider: 100
Unit: bar
Description: Minimum allowed
pressure before breakaway is detected
43314
2 RW
U32
PST timeout
Default: 00000
Range: 0-12000000
Divider: 1000
Unit: sec
Description: Partial stroke timeout
43316
2 RW
U32
PST total timeout
Default: 00000
Range: 0-12000000
Divider: 1000
Unit: sec
Description: Total timeout for the
partial stroke
43320
1 RW
U16
Minimum allowed pressure
Default: 00000
Range: 0-65535
Divider: 100
Unit: bar
Description: Minimum allowed
pressure during the partial stroke
PST warning parameters
43341
1 RW
U16
Enable warnings
Default: 00001
Range: 00002: Yes;00001: No;
Description: Show PST warnings
43342
2 RW
U32
Breakaway time low
Default: 00000