![Val Controls IDC24 Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/val-controls/idc24/idc24_user-manual_849423017.webp)
DID-UM-004
Val Controls A/S
•
Limfjordsvej 3
•
DK-6715 Esbjerg N
•
Tel. +45 7547 0600
•
Fax +45 7547 0611
•
www.valcontrols.com
Revision: 3
17/25
Reference test
Description: Full stroke reference
measurements
43431
2 RO
TIME
Time
Description: Time for last reference
full stroke
43433
2 RO
DATE Date
Description: Date for last reference
full stroke
43451
1 RO
U16
Start pressure
Range: 0-65535
Divider: 100
Unit: bar
Description: Start pressure
43443
2 RO
U32
SOV reaction time
Range: 0-12000000
Divider: 1000
Unit: sec
Description: SOV reaction time, only
available with pressure sensor
43435
2 RO
U32
Breakaway time
Range: 0-12000000
Divider: 1000
Unit: sec
Description: Breakaway time
43452
1 RO
U16
Breakaway pressure
Range: 0-65535
Divider: 100
Unit: bar
Description: Breakaway pressure
43437
2 RO
U32
FST time
Range: 0-12000000
Divider: 1000
Unit: sec
Description: FST time
43445
2 RO
U32
FST depressurising time
Range: 0-12000000
Divider: 1000
Unit: sec
Description: Depressurising time,
only available with pressure sensor
43447
2 RO
U32
FST pressurising time
Range: 0-12000000
Divider: 1000
Unit: sec
Description: Pressurising time
43439
2 RO
U32
FST return time
Range: 0-12000000
Divider: 1000
Unit: sec
Description: FST return time
43449
2 RO
U32
Actuator fill time
Range: 0-12000000
Divider: 1000
Unit: sec
Description: Actuator fill time, only
available with pressure sensor
43441
2 RO
U32
FST total time
Range: 0-12000000
Divider: 1000
Unit: sec
Description: Total time
Solenoid test
Last test
Description: Last solenoid test
measurements
43551
2 RO
TIME
Time
Description: Time for last solenoid
test
43553
2 RO
DATE Date
Description: Date for last solenoid
test
43555
1 RO
U16
Start pressure
Range: 0-65535
Divider: 100
Unit: bar
Description: Start pressure
43556
2 RO
U32
Reaction time
Range: 0-12000000
Divider: 1000
Unit: sec