Powering CAB100
Before connecting the AC (mains) power cable, switch off the
power from the main power source.
WARNING!
Before connecting power to the device, read carefully the safety
notes in
.
CAUTION!
Connecting AC (mains) power
• Screwdriver
• Cable cutters
• Cable-stripping pliers
For the AC (mains) power connection, you need an external disconnection device (for
example, a power cable or a mains power switch).
Note the following:
• The disconnection device must be rated 16 A or 20 A at 250 VAC, and must conform to
any additional local regulations.
• The disconnection device must be visible from the cabinet, or lockable with a key to
prevent accidental switching on during installation and maintenance.
• The cabinet must not block access to the disconnection device after it has been installed.
The disconnection device must remain easy to operate.
The AC (mains) cable is not included in the delivery. Use an AC (mains) cable with a minimum
cross-section of 3 × 0.75 mm
2
(18 AWG).
1. Unscrew and remove the transparent cover plate protecting the circuit breaker and the
power supply module.
2. Lead the AC (mains) cable into the enclosure.
Lead the cable through a flange in the cabinet enclosure, following relevant safety
regulations. Take note of safe areas around safety barriers or galvanic isolators inside the
enclosure.
16
M212284EN-C
Содержание CAB100
Страница 1: ...EN DE FR ES PT JA ZH M212284EN C Quick Guide CMS Industrial Cabinet CAB100 ...
Страница 3: ...Table of contents English 5 Deutsch 21 Français 37 Español 53 Português 69 日本語 85 中文 101 3 ...
Страница 4: ...4 M212284EN C ...
Страница 87: ...安全上の理由から 1 人で設置しないでください 設置を安全に行うに は 少なくとも 2 人で作業する必要があります 注意 87 日本語 ...
Страница 95: ...筐体の寸法 400 207 6 202 1 300 418 mm 図 41 CAB100A の筐体の寸法 600 500 206 618 mm 図 42 CAB100B の筐体の寸法 95 日本語 ...
Страница 110: ...外壳尺寸 400 207 6 202 1 300 418 毫米 图 48 CAB100A 外壳尺寸 600 500 206 618 毫米 图 49 CAB100B 外壳尺寸 110 M212284EN C ...
Страница 116: ......
Страница 117: ......
Страница 118: ...www vaisala com ...