Functional description

26

Operating instructions VRC 470 0020116689_00 

5

Three modes are possible:

 

–  

ECO 

(factory setting)

:

 The heating function is 

switched off and the controller monitors the outside 
temperature. 
If the outside temperature falls below 3 °C, the con-
troller switches the heating function on after the end 
of the  frost protection delay time and brings the room 
temperature to the set desired "Night" temperature. 
Even though the heating function is on, the burner is 
only active as required. 
If the outside temperature rises above 4 °C, the con-
troller switches the heating function off, but contin-
ues to monitor the outside temperature.

 

–  

Frost protection:

 The heating function is off and the 

frost protection function is active.

 

–  

Set-back temperature:

 The heating function is on 

and the controller brings the room temperature to the 
set desired "Night" temperature.

When installing your controller, the heating engineer can 
specify the control functions for the times outside the 
periods and the heating curve.

 

>

Discuss with the heating engineer which settings are 
optimum for you.

Summer mode
Mode 

¬

 (current mode) 

¬

  Summer mode

or where applicable

Menu 

¬

 Basic settings 

¬

 Mode 

¬

 HEATING 1 and, if 

relevant, HEATING 2 

¬

 (current mode)

The heating function is switched off for the selected 
heating circuit and the frost protection function is 
active. Hot water production and circulation are regu-
lated by the controller in accordance with the periods 
set.

 Comfort mode
Mode 

¬

 (current operating mode) 

¬

 Comfort mode

or where applicable

Menu 

¬

 Basic settings 

¬

 Mode 

¬

 HEATING 1 and, if 

relevant, HEATING 2 

¬

 (current mode) 

¬

 Comfort 

mode

The "Comfort mode" controls "HEATING 1" and, if rele-
vant, "HEATING 2" at the set desired "Day" tempera-
tures without taking periods into account. 

Set-back mode
Mode 

¬

 (current mode) 

¬

  Set-back mode

or where applicable

Menu 

¬

 Basic settings 

¬

 Mode 

¬

 HEATING 1 and, if 

relevant, HEATING 2 

¬

 (current mode) 

¬

 Set-back 

mode

The "Set-back mode" controls "HEATING 1" and, if rele-
vant, "HEATING 2" at the set desired "Night" tempera-
tures without taking periods into account. 

System OFF
Mode 

¬

 (current mode) 

¬

  System OFF

or where applicable

Menu 

¬

 Basic settings 

¬

 Mode 

¬

 HEATING 1 and, if 

relevant, HEATING 2 

¬

 (current Mode) 

¬

 System OFF

The heating function is switched off. The frost protection 
function is activated.

5.2.2  

Modes for hot water production and 
circulation

i

  The mode for hot water production and circu-

lation depends on the set mode for heating 
circuits "HEATING 1" and, if relevant, "HEAT-
ING 2". No other mode can be set.

i

  If you have assigned different functions, 

modes or advanced functions to two inde-
pendent heating circuits, then the controller 
assigns the mode with the greater heat 
requirement to hot water production and cir-
culation (

¬

 Tab. 5.1

).

If the heating system is equipped with one heating cir-
cuit, the controller regulates the hot water production 
and, if relevant, the circulation in accordance with the 
mode for this heating circuit. 
If the heating system is equipped with two heating cir-
cuits, the heating engineer can define which heating cir-
cuit controls the hot water production and, if relevant, 
the circulation.

Automatic mode and  Summer mode

 Automatic mode and Summer mode control the hot 
water production in accordance with the set desired 
temperature for "hot water" and the set periods. In the 
"Time programmes" function, you have set periods for 
hot water production. If you have not set any periods, 
the controller uses the period set in the factory settings 
for hot water production (

¬

 Tab. 4.2

).

Within the period, hot water production is switched on 
and keeps the hot water in the domestic hot water cylin-
der at the set temperature. Outside the period, hot 
water production is deactivated.
Automatic mode and Summer mode control the circula-
tion of hot water in the hot water pipes in accordance 
with the set periods.
Within the periods, circulation is activated and outside 
the periods it is deactivated.

 Comfort mode

Comfort mode controls hot water production in accord-
ance with the set desired temperature for hot water 
without taking periods into account.
Circulation is activated and the periods for circulation 
are not observed.

Содержание VRC 470

Страница 1: ...Operating instructions For the operator GB IE Operating instructions VRC 470f Weather compensator with radio data transmis sion...

Страница 2: ...1 Reading information 19 5 1 2 Setting desired temperatures 20 5 1 3 Setting timer programmes 21 5 1 4 Days away from home scheduling 23 5 1 5 Days at home scheduling 23 5 1 6 Language selection 23 5...

Страница 3: ...d The symbols used in the text are explained below i Useful instructions and information Required actions 1 4 Identification plate The identification plate is located inside the controller and is not...

Страница 4: ...damage to the unit and other property may occur The VRC 470 controller controls a Vaillant heating sys tem in a weather compensated and time dependent manner The controller is connected to a Vaillant...

Страница 5: ...tar get temperature is a mixing valve incorporated in the heating sys tem as protection against scalding what do you have to do to avoid scalding Preventing a malfunction Only operate the heating ins...

Страница 6: ...ature The frost protection function protects the heating sys tem and dwelling against frost damage The frost protection function monitors the outside tem perature If the outside temperature falls belo...

Страница 7: ...nu structure The setting level is accessed from the lowest selection level 3 3 2 Basic display The basic display is the permanently visible display on the screen The basic display shows the current se...

Страница 8: ...nding on the mode the desired temperature 6 may be greyed out on the display This is the case for example in Summer mode As heating is not opera tional in Summer mode and therefore the heating cir cui...

Страница 9: ...sic dis play appears in the display again 4 1 1 Operation in the basic display From the basic display you can change the Desired day temperature directly for the current day by turning the control kno...

Страница 10: ...hted Menu Day away from home scheduling Day at home scheduling Basic settings Back Select Fig 4 4 Selection level 1 Basic settings Press the right function key Select Basic settings Language Date Time...

Страница 11: ...01 10 Off Back Change Fig 4 9 Setting level Change saved Press the left function key Back several times to switch back to the next selection level up and to access the basic display from selection le...

Страница 12: ...Select Desired temperatures HEATING 1 HEATING 2 Domestic hot water Back Select Domestic hot water Domestic hot water Cancel Ok System Collector temp Solar yield Reset solar yield 76 C 4500kWh No Back...

Страница 13: ...ck Select Days away from home scheduling Start End Temperature Back Change 01 02 10 03 04 10 15 0 C 02 10 Menu Days away from home scheduling Days at home scheduling Basic settings Back Select Menu Da...

Страница 14: ...u or the heating engineer have set 4 3 1 Overview of modes The right function key can be used to navigate from the basic display directly to the settings under Mode The currently activated mode is sta...

Страница 15: ...NG 1 Day tempera ture Current value C 0 5 20 5 30 Night tempera ture Current value C 0 5 15 5 30 Room tempera ture3 Current value C Auto day temp until Current value h min away from Current value dd m...

Страница 16: ...10 min HEATING 2 2 Individual days and blocks Mon Tue Wed Thu Fri Sat Sun and Mon Fri Sat Sun Mon Sun Mon to Fri 06 00 22 00 Sat 07 30 23 30 Sun 07 30 22 00 and Mon Fri 06 00 22 00 Sat Sun 7 30 23 30...

Страница 17: ...dd mm yy Day Month Year 01 01 10 Temperature Frost protec tion or 5 30 C 0 5 C Frost protec tion Days at home scheduling HEATING 1 Start 01 01 00 31 12 99 dd mm yy Day Month Year 01 01 10 End 01 01 0...

Страница 18: ...ot active Automatic mode active Cylinder boost Active Not active Not active Party function Active Not active Not active 1 day away from home Active Not active Not active 1 day at home Active Not activ...

Страница 19: ...ribed in the following sec tions i The Room temperature list entry is only shown under System status if a remote con trol unit VR 81 2 is connected i HEATING 2 is only shown under System status if a m...

Страница 20: ...es adequate frost protection You can set two different desired temperatures for the heating circuits The desired day temperature is the temperature you wish to have in the rooms during the day or when...

Страница 21: ...ating circuit Set the period for the heating circuit so that each period starts approx 30 minutes before the time at which the rooms should reach the desired Day tempera ture ends approx 30 minutes be...

Страница 22: ...gramme message The set times for the block marked with can be viewed and changed if you press the right function key Ok in the display For the heating circuits Menu Time programmes HEATING 1 and if re...

Страница 23: ...or if you cancel the function the heating system returns to the pre set mode i HEATING 2 is only shown under Days at home scheduling if a mixer module VR 61 2 is connected HEATING 2 has the same read...

Страница 24: ...e difference Inputting a correction value affects the room tempera ture compensator 5 1 12 Setting the offset outside temperature Menu Basic settings Display Offset outside temp The thermometer in the...

Страница 25: ...right function key Mode to set the mode directly The set mode only applies to the heating circuit that has been pre set by the heating engineer HEAT ING 1 or HEATING 2 or HEATING 1 and HEATING 2 Only...

Страница 26: ...ING 2 at the set desired Night tempera tures without taking periods into account System OFF Mode current mode System OFF or where applicable Menu Basic settings Mode HEATING 1 and if relevant HEATING...

Страница 27: ...roduction and circulation Heating circuit 2 Heating circuit 1 Auto Day Set back Summer 1 day at home 1 Day away from home Days at home schedul ing Days away from home schedul ing Party function Auto A...

Страница 28: ...period then activate the Cylinder boost advanced function The advanced function heats the water in the domestic hot water cylinder once until the set desired hot water temperature is reached or until...

Страница 29: ...settings Mode HEATING 1 and if relevant HEATING 2 1 day at home If you are spending a week day at home e g on a public holiday then activate the 1 day at home advanced function The advanced function...

Страница 30: ...rating elements or the display 6 3 Detecting and rectifying malfunctions If a fault occurs in the heating system the controller dis plays an error message in the display b Caution Risk of damage to th...

Страница 31: ...m climate and energy saving operation Thermostatic radiator valves and room temperature compensated controller Thermostatic radiator valves on the radiators maintain the room temperature exactly once...

Страница 32: ...dance with Vaillant instructions The system owner will be granted a warranty in accordance with theVaillant terms and conditions All requests for work during the guarantee period must be made to Vaill...

Страница 33: ...ried out by a heating engi neer 9 2 Recycling and disposal The controller and the associated transport packaging consists largely of recyclable materials Unit Neither the controller or any of its acce...

Страница 34: ...escription Unit VRC 470 Operating voltage Umax V 24 Current consumption mA 50 Cross section of supply lines mm2 0 75 1 5 Protection type IP 20 Protection class III Maximum permissible ambient temperat...

Страница 35: ...ng installation heats up the dwelling and pro duces hot water Hot water production The water in the domestic hot water cylinder is heated by the boiler to the selected desired hot water temper ature I...

Страница 36: ...ve reduces the heating water flow rate If the room temperature falls below the pre set value the thermostatic radiator valve opens and the heating water flow rate increases and the room temper ature r...

Страница 37: ...on delay time 26 Frost protection function 6 Function key 8 Functions 19 H HEATING 1 6 HEATING 2 6 Heating circuit comfort mode 26 Heating circuits 6 Heating circuit summer mode 26 Heating circuit sys...

Страница 38: ...ection levels 8 Serial number 3 Service 30 Set back mode 26 Setting desired temperatures 20 Setting level 8 Setting the date 23 Setting the display contrast 24 Setting the operating mode 8 Setting the...

Страница 39: ......

Страница 40: ...0020116689_00 GBIE 042011 Subject to change Supplier Manufacturer 2702408_rev0...

Отзывы: