Error Codes 16
16.4 Outdoor units
Failure Code
State of LED
5-4-3-2-1
Trouble Shooting
Possible Reasons
1
Faulty defrost sensor Te
Sensor disconnected, or broken, or short circuit
2
Faulty defrost sensor Tao
T
T
Sensor disconnected, or broken, or short circuit
3
Faulty defrost sensor Ts
T
T
Sensor disconnected, or broken, or short circuit
4
Faulty sensor Td
Sensor disconnected, or broken, or short circuit
5
Input Overcurrent
Over current of the system, or broken of the
current sensor, or malfunction with indoor or
outdoor fan motors, or faulty PCB
6
Abnormal communication
between indoor and outdo-
or units
Wrong connection, or the wires be disconnected or
wrong address setting of indoor units, or faulty
PCB, or faulty power supply
9
System high pressure pro-
tection
High pressure switch is disconnected, or high pres-
sure switch worked, or Tc too high and faulty indo-
or fan motors when heating, or refrigerant over-
abundance
10
System low pressure pro-
tection
Low pressure switch is disconnected, or low pres-
sure switch worked, or Te too low and faulty outdo-
or fan motors when heating, or faulty indoor fan
motor when cooling, or refrigerant shortage.
11
IPM protection
IPM over current, or short circuit, or IPM tempera-
ture too high, or IPM input voltage too low, or faul-
ty SPDU (or ISPM).
12
EEPROM fault
Faulty outdoor unit PCB
13
Over hot protection of com-
pressor
Serious lack of refrigerant of the system, or the
ambient temperature too high, or PMVs be blocked
14
Over hot protection of
SPDU (or ISPM)
Ambient temperature too high, or outdoor fan be
blocked, or bad air circulation of outdoor unit
15
DC fan motor fault
Fan is blocked, or the terminal is disconnected
from the PCB
16
Faulty 4-way valve switching on Coil of 4-way valve is disconnected, or faulty outdo-
or PCB
17
Faulty sensor
Tc
Sensor disconnected, or broken, or short circuit
21
Faulty sensor
Toci
T
T
Sensor disconnected, or broken, or short circuit
23
Low voltage protection
VDC<194V, too low voltage from power source