Multi Split Type Installation Manual
34
16 Error Codes
Trouble Shooting
(indoor unit)
Failure Code
(Check the wired remote con-
troller)
Possible Reasons
Faulty temperature sensor
Tai
01 *
Sensor disconnected, or broken, or at
wrong position, or short circuit
Faulty temperature sensor
Tc1
T
T
02 *
Sensor disconnected, or broken, or at
wrong position, or short circuit
Faulty temperature sensor
Tc
T
T 2
03 *
Sensor disconnected, or broken, or at
wrong position, or short circuit
Faulty temperature sensor
Tm
04 *
Sensor disconnected, or broken, or at
wrong position, or short circuit
Faulty EEPROM on indoor unit PCB
05
Faulty indoor unit PCB
Abnormal communication between indo-
or and outdoor unit
06 *
Wrong connection, or the wires be dis-
connected, or wrong address setting of
indoor units, or faulty power supply or
faulty PCB
Abnormal communication between wired
controller and indoor unit PCB
07 *
Wrong connection, or use the wired con-
troller be disconnected, faulty PCB
Drainage System abnormal
08 *
Pump motor disconnected, or at wrong
position, or the float switch broken down,
or the float switch disconnected, or at
wrong position
Indoor Unit address repeated
09
Wrong setting of indoor unit address
Abnormal communication between chip
TMP/807 and chip TMP/846
0E
Faulty indoor unit PCB
Trouble Shooting
(outdoor unit)
Failure Code
(Check the wired remote con-
troller)
Possible Reasons
Faulty defrost sensor
Te
14 *
Sensor disconnected, or broken, or short circuit
Faulty sensor
Tao
15 *
Sensor disconnected, or broken, or short circuit
Faulty sensor
Ts
16 *
Sensor disconnected, or broken, or short circuit
Faulty sensor
Td
17 *
Sensor disconnected, or broken, or short circuit
Input overcurrent
19
Over current of the system, or broken of the
current sensor,or malfunction with indoor or
outdoor fan motors, or faulty PCB.
System high pressure protection
1E*
High pressure switch is disconnected, or
high pressure switch worked, or Tc too
high and faulty outdoor fan motor when
cooling, or faulty indoor fan motors when
heating, or refrigerant overabundance
16.2 Duct units