Multi Split Type Installation Manual
35
EN
Error Codes 16
Trouble Shooting
(indoor unit)
Failure Code
(Check the wired remote controller)
Possible Reasons
System low pressure
protection
1F*
Low pressure switch is disconnected, or
low pressure switch worked, or Te too
low and faulty outdoor fan motors when
heating, or faulty indoor fan motor when
cooling, or refrigerant shortage
IPM protection
20
IPM over current, or short circuit, or IPM
temperature too high, or IPM input voltage
too low,or faulty SPDU(or ISPM).
EEPROM fault
21
Faulty outdoor unit PCB
Over hot protection of compressor
22
Serious lack of refrigerant of the system,
or the ambient temperature too high, or
PMVs be blocked
Over hot protection of SPDU (or ISPM)
23
Ambient tempreatrue too high, or outdoor
fan be blocked, or bad air circulation of
outdoor unit
DC fan motor fault
24
Fan is blocked, or the terminal is disconnected
from the PCB
Faulty 4-way valve switching on
25
Coil of 4-way valve is disconnected, or
faulty outdoor PCB
Faulty sensor
Tc
26 *
Sensor disconnected, or broken, or short circuit
Faulty sensor
Toci
2A*
Sensor disconnected, or broken, or short circuit
Low voltage protection
2C
VDC<194V, too low voltage from power source
High voltage protection
2D
VDC>400V, too high voltage from power source
Abnormal communication between main
PCB and SPDU(or ISPM)
2E
Communication cables broken, or not be
well connected, or faulty main PCB, or
faulty SPDU (or ISPM)
Compressor be locked
32
Faulty compressor or SPDU(or ISPM)
Compressor vibration too big
33
Faulty compressor
Compressor lose position
34
Faulty SPDU(or ISPM)
Faulty compressor start
35
Faulty compressor or SPDU(or ISPM)
Faulty position checking circuit
37
Faulty SPDU(or ISPM)
Compressor broken
38
Faulty compressor or SPDU(or ISPM)