35

Installation Manual recoVAIR/3 0020062918_03

7 Troubleshooting

The faults listed below may only be rectified by an ex-
pert technician.
•  Make sure the parts are correctly fitted and that their 

original position and alignment are retained.

Malfunction

Cause

Remedy

The unit does not op-
erate

Temporary interruption of the mains voltage sup-
ply or no supply at all. Power supply circuit break-
er tripped. Electricity disconnector was activated.
Fuse F1 in the unit is defective.

After a mains failure the unit automatically restarts once the 
mains voltage is re-established. Re-set circuit breaker in 
mains distribution board. Check that all cables are properly 
connected and undamaged. If necessary, replace the fuse F1 
on the PCB.

Unit operation is very 
loud even at the mini-
mum fan speed

No silencers in the fresh air and exhaust air ducts.
Wrong silencers, or silencers are too short. Filters 
are extremely soiled.
Ventilators are defective or heavily soiled.

Mount additional silencers in accordance with the system de-
sign.
Reduce the air quantity to the minimum fan stage. Clean or 
replace filters.
Replace or clean ventilators, check the reason of soiling.

None or insufficient 
fresh air supply

Filters are extremely soiled.
Fresh air valves/grilles closed too much.
Exhaust air or fresh air ducts obstructed.
Fresh air input louvre too small.
Incorrect wiring.
Fan defective.

Clean the filter.
Open the fresh air valves/grilles. Adjust the system again.
Clean the exhaust air and fresh air ducts.
Fit a larger louvre.
Check the wiring.
Replace the fan if necessary.

No or insufficient
exhaust air flow 
(i.e. in the bathroom 
the mirror stays 
fogged up)

Filters are extremely soiled.
Exhaust air valves closed too much.
Exhaust air or fresh air ducts obstructed.
Fresh air input louvre too small.
Incorrect wiring.
Fan defective.

Clean the filter.
Open the exhaust air valves. Adjust the system again.
Clean the exhaust air and fresh air ducts.
Fit a larger louvre.
Check the wiring.
Replace the fan if necessary.

Bypass summer mode 
does not work

Bypass function not activated or set days for 
summer mode expired.
Incorrect positioning of the temperature sensor.
Flap position and/or motor for bypass defective. 
Defective bypass motor wiring.

In the programming level of the remote control, set or acti-
vate the bypass function.
Correctly position the temperature sensor.
Check the flap position and the motor and, if required, re-
place them.
Check that the plug to the flap motor is correctly positioned. 
Check in the Service/Diagnostics menu whether the sensors 
are detected at the remote control. See section 5.1.2

Noise in the conden-
sation water drain 
trap

Drain trap incorrectly connected.

Connect the drain in accordance with section 4.5.3.

Water dripping from 
the unit

Exhaust air and fresh air ducts are not vapour-
sealed.

Insulate exhaust air and fresh air ducts, make ducts air-tight 
or use specially insulated pipes.

Fresh air too cold

Exhaust air and fresh air flows not balanced.
Wrong flap position and bypass motor defective.

Adjust the unit in accordance with section 5.2.
Check the flap and motor, 
Clean the flap and bracket, 
if necessary, replace the bypass.

No fresh air or ex-
haust air (only one 
fan running)

Frost protection activated.
With outside temperatures below -7 °C, correct 
operation.
The frost protection sensor will not work at a dis-
charge air temperature above 3 °C.

Check the resistance of the frost protection sensor based on 
table 7.3.
If necessary, replace the frost protection sensor.

Odours from the 
kitchen/WC enter into 
other rooms

Outlets for fresh air and exhaust air are too close 
to each other.

Extend the distance between the outlets for fresh air and ex-
haust air. We recommend to position these junctions in differ-
ent parts of the roof.

Sound transmitted be-
tween the rooms

No crosstalk absorbers mounted.

Additionally install crosstalk absorbers.
Adjust the unit in accordance with section 5.2.

Planned air flow not 
reached at the start-
up

System is not air-tight.

Seal all pipe connections properly if necessary.

Noise in the unit after 
replacing the fan.

Wrong mounting of the fans.

Check the correct positioning of the fans.

Table 7.1 Troubleshooting

•  Troubleshooting is successful if the unit operates cor-

rectly.

•  Only use genuine spare parts for repairs.

Troubleshooting 7

Содержание recoVAIR/3 SERIES

Страница 1: ...For the owner and expert technician Operating and Installation Manual recoVAIR 3 Domestic ventilation unit with heat recovery and remote control recoVAIR VAR 275 3 recoVAIR VAR 350 3 GB...

Страница 2: ......

Страница 3: ...ng 6 3 4 Recycling and Disposal 6 3 4 1 Device 6 3 4 2 Packing 6 3 5 Energy Saving Tips 7 4 Handling 7 4 1 Assembling of the Domestic Ventilation Unit 7 4 2 Bypass optional 7 4 3 Switching on and off...

Страница 4: ...positioned below the unit 1 Notes on the documentation The following notes serve as a guide for the entire doc umentation Other documents are valid in connection with this oper ating manual We accept...

Страница 5: ...gas leakage from the combustion equipment 2 1 2 Operation Note that the device can only be used if all ventilation pipes of the device are connected and the entire device is closed The unit must only...

Страница 6: ...d for controlling the domestic ventilation unit as described in these instructions it is not designed for any other purpose Any other or additional use is considered to be improp er The domestic venti...

Страница 7: ...ing mode during the summer months with the outside temperature falling below room tem perature during the night The cooler outside tempera ture will not be warmed by the device before it was blown int...

Страница 8: ...e night mode Static Cooling required Flashing Bypass open summer mode Off Bypass not fitted or closed Automatic mode Day mode 2nd fan stage Night mode 1st fan stage Mode with fan stage holidays minimu...

Страница 9: ...ear clock Press the dial several times in order to se lect the day the month and the year If the clock is not activated this point will be left out Turn Turn the dial in order to change the day the mo...

Страница 10: ...s you can start the individual special functions You select the function by pressing the F button several times hNote After the necessary settings have been made no confirmation is required 10 seconds...

Страница 11: ...aily program Table 4 7 Information level time time time 6 00 22 00 17 00 10 00 6 00 22 00 2 00 2 00 6 00 22 00 17 00 10 00 2 00 17 00 10 00 Energy saving 5h Automatic mode Advance function Energy savi...

Страница 12: ...on levels how often the fil ters must be cleaned or replaced We recommend to regularly check the filters during the initial operational period and asses the need to clean them e g every three months I...

Страница 13: ...n to any legal warranty cover and shall not re place or restrict your legal claims under the Sale of Goods Act This warranty shall become effective from the day of installation or 2 years after the ma...

Страница 14: ......

Страница 15: ...cal Connection of the Bypass optional 24 4 8 Assembly and Installation of the Remote Control 25 4 8 1 Establishment of Electrical Connection of the Remote Control 26 4 9 Establishment of Electrical Co...

Страница 16: ...he CE label shows that this unit complies with the fol lowing directives Low voltage Directive 73 23 EEC modified with Directive 93 68 EEC EMC Directive 89 336 EEC modified by the Directive 91 263 EEC...

Страница 17: ...AR 275 3 4 x air duct connections 150 mm or alternative 160 mm and 180 mm recoVAIR VAR 350 3 4 x air duct connections 180 mm or alternative 200 mm Condensed water drain G 3 4 connection for the con de...

Страница 18: ...consisting of Fixing brackets 405 x 60 mm Condensate drain trap Accessories optional Bypass recoVAIR Filtersets 4 2 Installation Site Requirements The installation site of the domestic ventilation uni...

Страница 19: ...and the air duct ing and reduce annoyance by noise Keep the air supply inlet at a sufficient distance from discharge air exhaust air and drain ventilation Com ply with the legal building rules and reg...

Страница 20: ...s 1 2 3 Fig 4 3 Bypass Installation Key 1 Filter 2 Ventilation flap 3 Air inlet from outside Vaillant GmbH Remscheid Germany Serial no 1234567890xxxxxx Bypass VAR 275 VAR 350 12 V DC P Max 3 W IPX2 nu...

Страница 21: ...4 5 Measurements recoVAIR VAR 275 3 and 350 3 recoVAIR VAR 275 3 recoVAIR VAR 350 3 Remarks A 77 127 B 471 521 C 150 160 178 180 198 Pipe diameter to be selected for all 4 air connections D 150 160 17...

Страница 22: ...f the installation site Drill the holes for the fixing screws and position the wall plugs Screw the fixing bracket horizontally to the wall 4 5 2 Mounting of the Domestic Ventilation Unit d Danger If...

Страница 23: ...ffusion resistant 4 6 Opening and Closing the Domestic Ventilation Unit The domestic ventilation unit is equipped with a fixed front cladding with a pivoting door to the left Behind this door there ar...

Страница 24: ...herefore it is absolutely mandatory to have a competent person com plete the electric installation hNote The bypass must be first electrically connected because the electric lines are not accessible a...

Страница 25: ...all at a height of about 1 5 m There the controller is able to detect the circulat ing ambient air clearly and unimpeded from furniture curtains or other external influences The position should be sel...

Страница 26: ...ccidents electric installation can only be carried out by a qualified expert techni cian The remote control is connected to the domestic venti lation unit via a two core cable Communication is done vi...

Страница 27: ...5 X 6 X 17 X 7 X 8 Switch 1 Alarm input Alarm output Switch 2 BUS connection 0 10 V Control signal analog Mains connection M Control signal Control signal Analog PC connection Error In Err Out D O H...

Страница 28: ...is undone with an external potential free switching contact break contact both fans will be switched off On the display of the remote control you will find the message LOCK e Danger Risk of fatal elec...

Страница 29: ...tart Up The start up and the operation of the unit as well as in struction to the user must be done by a competent per son Please note that the device can only be started up if all ventilation pipes o...

Страница 30: ...own on the re mote control display Alarm output is closed Click POL1 POL2 No function Table 5 1 Functions in the Installer Level continued Action Display Meaning Click C AIR Set volume flow correction...

Страница 31: ...conds to reset the control ler to the default setting As soon as the display lights up twice the controller is completely re set to its default settings This means that you will have to perform all in...

Страница 32: ...d personnel The functional operation of the domestic ventilation unit requires it to be serviced once per year This includes the following Check the general condition of the unit Remove any dirt and s...

Страница 33: ...er back into the unit Take care that the heat exchanger correctly fits into the guide rails at the top and bottom of the housing and that it is not installed off centre a Caution The heat exchanger mu...

Страница 34: ...of the unit Check that the unit casing is correctly closed Insert the mains plug into the plug socket and start the unit Check the correct function of the unit Check the correct function of the remote...

Страница 35: ...n not activated or set days for summer mode expired Incorrect positioning of the temperature sensor Flap position and or motor for bypass defective Defective bypass motor wiring In the programming lev...

Страница 36: ...e EAI Err Temperature sensor exhaust air Temperature sensor defective interrupted or short circuited Wiring interrupted Contact Vaillant Customer Service EAO Err Temperature sensor discharge air Tempe...

Страница 37: ...k under warranty shall never cause an extension of the warranty period This warranty shall only cover material or manufactur ing defects The warranty shall not be applicable to such faults or defects...

Страница 38: ...max air volume flow W 55 165 m3 h 61Pa 85 165 m3 h 61Pa Power consumption at max air volume flow W 175 275 m3 h 170Pa 295 350 m3 h 265Pa Minimum power consumption W 21 30 Maximum power consumption W 2...

Страница 39: ...haust air Fresh air System characteristic Recommended design range Air 2 Fig 9 1 Performance diagram recoVAIR VAR 275 3 Air 1 Air 2 High 500 600 400 300 200 100 0 0 25 50 75 100 125 150 175 200 225 25...

Страница 40: ...0 Templates 10 1 Templates Start up measuring report Fresh air flow Room Grille louvre size 1 measurement 2nd measurement 3rd measurement Total Exhaust air flow Room Grille louvre size 1 measurement 2...

Страница 41: ...41 Installation Manual recoVAIR 3 0020062918_03 10 2 Template Filter replacement report Date Operating hours next change Name Templates 10...

Страница 42: ...Installation Manual recoVAIR 3 0020062918_03 42 10 3 Template Hygiene check report Date Operating hours opt Impression filter Visual check of the unit swept clean Name 10 Templates...

Страница 43: ......

Страница 44: ...0020062918_03 GB 062009 Subject to alterations...

Отзывы: