5 Installation

12

Installation and maintenance instructions atmoMAG 0020189893_03

4.4

Requirements for the installation site

Select the installation site so that the pipes can be easily
routed (gas supply, water supply and drain).

Do not install the product above an appliance whose use
may damage the gas-fired instantaneous water heater
(e.g. above a cooker that can emit grease vapours).

4.5

Removing/installing the product casing

4.6

Wall-mounting the product

Conditions

: The load-bearing capacity of the wall is sufficient, The fixing

material may be used for the wall

Wall-mount the product as described below.

Conditions

: The load-bearing capacity of the wall is not sufficient

Ensure that wall-mounting apparatus on-site has a suf-
ficient load-bearing capacity. Use individual stands or
primary walling, for example.

Do not wall-mount the product if you cannot provide
wall-mounting apparatus with a sufficient load-bearing
capacity.

Conditions

: The fixing material may not be used for the wall

Wall-mount the product as described as follows using
the permitted fixing material provided on-site.

1.

Drill the holes for the fixing screws while taking into
consideration the dimensions.

2.

To secure the product, depending on the installation
site, use wall anchors, hooks, bolts or threaded bolts as
the fixing material.

3.

Use suitable fixing material to install the back wall of the
unit to the wall.

5

Installation

Danger!
Risk of scalding and/or damage due to
incorrect installation leading to escaping
water.

Stresses in supply lines can cause leaks.

Install the supply lines without tension.

If you use plastic supply lines for the hot-
and cold-water connection, these must
withstand temperatures up to 95 °C and
pressures up to 1.0 MPa (10 bar).

Caution.
Risk of material damage due to the gas
leak-tightness test.

At a test pressure of >11 kPa (110 mbar), gas
leak-tightness tests may cause damage to
the gas valve.

If, during gas leak-tightness tests, you
also place the gas lines and the gas valve
in the product under pressure, use a max.
test pressure of 11 kPa (110 mbar).

If you cannot limit the test pressure to
11 kPa (110 mbar), close any gas isolator
cocks that are installed upstream from the
product before you carry out the gas leak-
tightness test.

If, during gas leak-tightness tests, you
have closed the gas isolator cock that is
installed upstream of the product, relieve
the gas line pressure before you open this
gas isolator cock.

5.1

Integration into a solar system

The inlet temperature must not exceed 45 °C.

The hot water temperature must not exceed 60 °C.

Install thermostatic 3-way valves.

Содержание MAG AT 11-0/1 GX H

Страница 1: ...nstructions atmoMAG MAG AT 0 1 GX MAG 0 1 GX MAG 0 1 XI AT CH de DE Installation and maintenance instructions Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 49 21 91 18 0...

Страница 2: ...version 13 6 3 Checking that the flue gas sensor works correctly 13 6 4 Checking the gas flow pressure 14 6 5 Checking the heat input 14 6 6 Setting the product load 17 6 7 Checking that the product f...

Страница 3: ...nce conditions listed in the instruc tions Intended use also covers installation in ac cordance with the IP class Any other use that is not specified in these instructions or use beyond that specified...

Страница 4: ...ath due to explosive and flammable materials Do not use or store explosive or flammable materials e g petrol paper paint in the installation room of the product 1 3 8 Risk of death from escaping gas W...

Страница 5: ...per son who also assumes the responsibility for installing the unit properly and commissioning it for the first time Before installing the gas fired instantaneous water heater you must consult with t...

Страница 6: ...n on the identification plate The identification plate is mounted at the front of the atmo spheric sensing device under the product casing at the fact ory Applicability Germany Austria Switzerland Inf...

Страница 7: ...hanger 5 Burner 6 Temperature selector 7 Gas valve 8 Power switch 9 Main switch 10 Electronics box with battery compartment 11 Ignition electrode 12 Monitoring electrode Applicability MAG 14 0 1 GX 2...

Страница 8: ...te 3 4 VGW symbol The VGW symbol shows that the products comply with all of the requirements for assigning the VGW symbol in accordance with the identification plate 4 Installation 4 1 Checking the sc...

Страница 9: ...Installation 4 0020189893_03 atmoMAG Installation and maintenance instructions 9 a 92 mm b 85 mm c 100 mm without thermal isolator device c 145 mm with thermal isolator device...

Страница 10: ...Installation and maintenance instructions atmoMAG 0020189893_03 4 3 Dimensions Applicability MAG 11 0 1 XI OR MAG 11 0 1 GX 224 259 115 min 20 26 50 172 5 270 min 20 120 113 3 61 4 350 52 617 658 680...

Страница 11: ...ation and maintenance instructions 11 Applicability MAG 14 0 1 XI Germany OR MAG 14 0 1 GX Germany OR MAG 14 0 1 GX Switzerland OR MAG 14 0 1 GX Austria 224 616 485 658 48 679 680 617 259 124 120 61 4...

Страница 12: ...e the product depending on the installation site use wall anchors hooks bolts or threaded bolts as the fixing material 3 Use suitable fixing material to install the back wall of the unit to the wall 5...

Страница 13: ...cordance with the operating in structions When starting up the unit proceed in accordance with the attached checklist Commissioning checklist Page 21 6 2 Gas conversion 1 Observe the applicable nation...

Страница 14: ...stria Switzerland Gas family Permissible gas flow pres sure Natural gas G20 DE AT CH G25 DE 1 7 2 5 kPa 17 25 mbar 1 7 2 5 kPa 17 25 mbar Liquid gas G31 DE AT CH 4 25 5 75 kPa 42 5 57 5 mbar Condition...

Страница 15: ...tap fully open to enable the nominal water volume Page 25 to flow After approx five minutes of the product running in con tinuous mode read off the gas flow value at the counter and compare this with...

Страница 16: ...alue with the corresponding value in the table Note Deviations of 10 are permitted Remove the pressure gauge Place the sealing screw and the seal on the measuring nipple tighten the sealing screw and...

Страница 17: ...tor how the safety devices work and where they are located 2 Inform the operator how to handle the product Answer any questions the operator may have 3 Draw special attention to the safety instruction...

Страница 18: ...burner to the back wall 4 Raise the burner slightly and carefully pull the burner forwards and out 7 4 Removing the jet holder 1 2 1 Remove the two bolts 1 in order to remove the jet holder 2 Remove...

Страница 19: ...urner rails with a soft brush and blow out any dust or dirt outside the install ation room from the outside to the inside using com pressed air 3 If the burner is extremely dirty clean it with soapy w...

Страница 20: ...minating faults in the product Clear the product of any faults by carrying out the follow ing steps Close the water tap and open it again without press ing the main switch Leave the water tap open and...

Страница 21: ...omer 11 Stick the sticker Read the operating instructions on the front of the product in the language spoken by the operator B Inspection and maintenance work Overview Note The table below lists the m...

Страница 22: ...utes after water is drawn XI only Loud over ignition XI only The battery charge is low XI only Replace the battery XI only The product cannot be star ted up The LED flashes red for up to ten minutes a...

Страница 23: ...2 Micro switch 3 Ignition electrode 4 Monitoring electrode 5 Burner 6 Red connection cable 7 Transparent connection cable 8 Safety overheat cut off device 9 Flue gas sensor 10 Red connection cable 11...

Страница 24: ...11 1 Gas valve 2 Micro switch 3 Ignition electrode 4 Monitoring electrode 5 Burner 6 Red connection cable 7 Transparent connection cable 8 Flue gas sensor 9 Red connection cable 10 Electronics box 11...

Страница 25: ...6 kPa 7 6 mbar Natural gas 2L G25 0 94 kPa 9 4 mbar 0 76 kPa 7 6 mbar Liquid gas 3P G31 DE CH 3 34 kPa 33 4 mbar AT 3 16 kPa 31 6 mbar DE CH 2 70 kPa 27 0 mbar G Technical data Technical data General...

Страница 26: ...min 9 8 kW 12 2 kW 9 8 kW 9 8 kW Max heat out put Pmax Germany 19 2 kW 19 2 kW Switzerland 19 2 kW 19 2 kW Austria 18 2 kW 22 7 kW Min heat output Pmin 8 4 kW 10 4 kW 8 4 kW 8 4 kW Control range Germa...

Страница 27: ...ey draught 1 5 Pa 1 5 Pa Min chimney draught when using a thermal flue non return flap 10 0 Pa 10 0 Pa Technical data Natural gas G20 Applicability Germany Switzerland Austria MAG AT 11 0 1 GX H MAG A...

Страница 28: ...h 23 2 m h 30 0 m h 30 0 m h Technical data Liquid gas G31 Applicability Germany Austria Switzerland MAG AT 11 0 1 GX H MAG 11 0 1 GX MAG 11 0 1 XI MAG 14 0 1 GX Gas connection value at max heat outp...

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ...llant GmbH Schweiz Suisse Svizzera Riedstrasse 12 CH 8953 Dietikon Tel 044 74429 29 Fax 044 74429 28 Kundendienst 044 74429 29 Techn Vertriebssupport 044 74429 19 info vaillant ch www vaillant ch Vail...

Отзывы: