5 Installation

10

Installation and maintenance instructions eloBLOCK 0020265768_01

5.2

Connecting the expansion relief valve

1

1.

Use an intake funnel to connect a drain line to the outlet

(1)

of the expansion relief valve.

2.

Route as short a drain line as possible at a downward
gradient away from the product.

3.

Connect the drain line to an odour trap on an outflow or
route the drain line to the outside.

4.

Terminate the drain line in such a way that escaping
water or steam cannot cause injury to persons or dam-
age to cables and electronic components.

5.

When the drain is routed to the outside, ensure that the
end of the line is visible.

5.3

Electrical installation

Only qualified electricians are allowed to carry out the elec-
trical installation.

The cross-section of the connection wires is calculated by
the planner based on the installation conditions (e.g. cable
length, total input power for the product, etc.).

Danger!
Risk of death from electric shock!

Switch off the power supply.

Secure the power supply against being
switched on again.

Ensure that the nominal mains voltage complies with the
technical data and that the power supply is sinusoidal.

Connect the product using a fixed connection and a par-
tition with a contact gap of at least 3 mm (e.g. fuses or
power switches) (

Page 24).

Route a three-phase power supply cable that complies
with the relevant standards through the grommet and into
the product.

Power supply cable: Flexible line

In addition, install an on/off switch (on-site) in the power
supply adjacent to the product.

Clearance: 10 cm

Ensure that the on/off switch completely disconnects the
L and N lines.

5.3.1

Connecting the power supply cable

1

1.

Install the enclosed duct screw connection for the
power supply's grommet

(1)

.

2.

Route the mains feed line through the grommet on the
rear right of the underside of the product. (

Page 5)

3.

Strip approx. 2-3 cm of the mains feed line and strip the
insulation from the conductors.

4.

Connect the connection cable to the relevant screw
terminals. (

Page 24)

5.

Ensure that the connection cable is mechanically fixed
in place in the screw terminals.

5.3.2

Setting operation with two electricity tariffs

1.

Remove the bridge at terminal X2 (ESC). (

Page 24)

2.

Connect the contact on the ripple control signal receiver
to terminal X2 (ESC).

5.3.3

Connecting the earth cable

1.

Connect the earth cable to the earth connection on
the product and to a suitable earth connection on the
house installation in order to prevent short circuits in the
product (e.g. caused by the penetration of water).

2.

Connect the earth cable to the earth connection on the
product's front cover.

Содержание eloBLOCK VE 12 /14 EU I

Страница 1: ...allation and maintenance instructions eloBLOCK VE 14 EU I FI fi Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 492191 18 0 Fax 492191 18 2810 info vaillant de www vaillan...

Страница 2: ...leak tightness 14 7 Adapting the product to the heating installation 14 8 Handing the product over to the end user 14 9 Troubleshooting 14 9 1 Eliminating faults 14 9 2 Eliminating faults in the pump...

Страница 3: ...nance instructions for the product and any other system com ponents installing and setting up the product in ac cordance with the product and system ap proval compliance with all inspection and main t...

Страница 4: ...rsons are particularly at risk even at lower temperatures Select a moderate set target temperature Inform the operator about the risk of scald ing when the anti Legionella function is switched on 1 4...

Страница 5: ...0010023696 VE 28 14 EU I 0010023697 3 Product description 3 1 Product design 1 2 3 4 5 6 14 13 12 11 10 9 8 7 1 Automatic air vent 2 NTC sensor 3 Contactor 4 Printed circuit board 5 Contactor 6 Power...

Страница 6: ...inlet and outlet for the heating water and the electric connection are located on the underside of the product The product is designed for wall installation To achieve a higher output several products...

Страница 7: ...3 either 4 5 Wall mounting the product 1 Check whether the wall has sufficient load bearing ca pacity to bear the operational weight of the product 2 Check if the supplied fixing material may be used...

Страница 8: ...above illustration 4 7 Installing and removing the side casing 4 7 1 Removing the side casing B A D C Caution Risk of material damage caused by mech anical deformation Removing both side sections may...

Страница 9: ...ial damage caused by residues in the pipelines Welding remnants sealing residues dirt or other residues in the pipelines may damage the product Flush the heating installation thoroughly before install...

Страница 10: ...par tition with a contact gap of at least 3 mm e g fuses or power switches Page 24 Route a three phase power supply cable that complies with the relevant standards through the grommet and into the pro...

Страница 11: ...relay An external load shedding relay can control the product s power depending on the mains load in the building If the mains supply is under an excessive load the product s power automatically decre...

Страница 12: ...and technical rules do not stipulate more stringent requirements the following applies You must treat the heating water in the following cases If the entire filling and supplementary water quantity d...

Страница 13: ...2 MPa 1 0 2 0 bar is displayed If the heating installation is to supply several storeys a higher filling pressure may be required If the pressure falls short by 0 08 MPa 0 8 bar a pressure sensor sign...

Страница 14: ...a fault occurs in the pump this is shown by the pump s status LED Use the table in the appendix to eliminate the fault Pump status LED Page 23 If you are unable to eliminate the fault contact Customer...

Страница 15: ...s fixing screw 1 on the underside of the product 6 Carefully turn the pump clockwise so that it can be re moved from the product 7 When you install the new pump use new seals O rings coated with a wa...

Страница 16: ...on relief valve and use the safety clip to secure it in place 3 Check that the new expansion relief valve is seated firmly and check it for tightness 10 8 Replace the pressure sensor 2 1 3 1 Remove th...

Страница 17: ...e PCB and the display 2 Replace the PCB and the display 3 Plug all of the connection cables into their original slots 4 Check all of the connections using the connection dia gram Page 24 5 Connect the...

Страница 18: ...allation and maintenance instructions eloBLOCK 0020265768_01 13 Customer service Validity Finland Vaillant Asiakaspalvelumme yhteystiedot l ytyv t takapuolella mainitun osoitteen alta tai WWW sivulta...

Страница 19: ...only be accessed after entering a password In the diagnostics mode you can change various parameters to adapt the product to the heating installation Since the code table is used for various products...

Страница 20: ...omestic hot water mode stage 2 2 Automatic heating mode pump prerun overrun stage 1 domestic hot water mode stage 2 3 Always stage 2 4 Automatic heating mode pump prerun overrun stage 1 domestic hot w...

Страница 21: ...D 081 Operating hours domestic hot water generation In hours h Not ad justable D 082 Number of heating cycles in heating mode x 100 3 corresponds to 300 Number of heating cycles Not ad justable D 083...

Страница 22: ...nics defective F 010 Short circuit Temperature sensor NTC Plug on sensor has a short to earth at the housing Short circuit in the cable harness Sensor defective F 013 Short circuit Cylinder temperatur...

Страница 23: ...ature sensor measures 3 C The fault is automatically reset if T C 4 C No fault is displayed if the sensor is defective F 180 Welded relay The fault is displayed if a welded relay has been detected fiv...

Страница 24: ...ly main connection block 5 Contactor 1 6 Power supply for external VR 40 module 7 Safety cut out 8 Heating pump 9 Connection for 3 port diverter valve 10 RE 14 relay for heating pump 11 RE 15 3 port d...

Страница 25: ...Power supply for external VR 40 module 7 Safety cut out 8 Heating pump 9 Connection for 3 port diverter valve 10 RE 14 relay for heating pump 11 RE 15 3 port diverter valve 12 RE 16 relay for contacto...

Страница 26: ...ly for external VR 40 module 7 Safety cut out 8 Heating pump 9 Connection for 3 port diverter valve 10 RE 14 relay for heating pump 11 RE 15 3 port diverter valve 12 RE 16 relay for contactor 13 RE 13...

Страница 27: ...if necessary X Check the purging valve the expansion relief valve the 3 way diverter valve the heat exchanger and all of the hydraulic components X Safety test Check all of the sensors thermostats and...

Страница 28: ...ristic values of the VRC DCF outdoor temperature sensor Temperature C Resistance ohms 25 2167 20 2067 15 1976 10 1862 5 1745 0 1619 5 1494 10 1387 15 1246 20 1128 25 1020 30 920 35 831 40 740 K Charac...

Страница 29: ...8 l 8 l 8 l Flow return heating connections G 3 4 G 3 4 G 3 4 G 3 4 Boiler dimension width 410 mm 410 mm 410 mm 410 mm Boiler dimension height 740 mm 740 mm 740 mm 740 mm Unit dimensions depth 315 mm...

Страница 30: ...10 K 1 548 l h 1 806 l h 2 064 l h 2 408 l h Pump remaining feed head at T 10 K 24 kPa 240 mbar 20 kPa 200 mbar 16 5 kPa 165 0 mbar 11 kPa 110 mbar Number of immersion heaters pcs x kW 3 x 6 3 x 7 4 x...

Страница 31: ...ont casing 8 Frost 4 H Handing the product over to the end user 14 Hot water temperature Risk of scalding 4 I Inspection work 14 27 Installation site 4 Intended use 3 M Maintenance 14 Maintenance work...

Страница 32: ...Berghauser Strasse 40 42859 Remscheid Tel 492191 18 0 www vaillant info These instructions or parts thereof are protected by copyright and may be reproduced or distributed only with the manufacturer...

Отзывы: