Appendix
0020214491_01 ecoTEC plus Installation and maintenance instructions
33
Code Parameter
Values or explanations
Default set-
ting
Own setting
D.72
Pump overrun after cylinder charging
Adjustable from 0 to 600 seconds
80 s
D.75
Max. charging time for domestic hot
water cylinder without independent
control system
20 - 90 min
45 minutes
D.76
Unit variant: Device-specific number
(DSN)
.. 656/4
‑
5 = 47
D.77
Limit on cylinder charging output in
kW
Adjustable cylinder charging output in kW
Maximum
output
D.78
Cylinder charging temperature limit
(target flow temperature in cylinder
charging mode) in °C
55 °C-85 °C
80
℃
D.80
Operating hours, heating
in hrs
¹
Not
adjustable
D.81
Operating hours, hot water genera-
tion
in hrs
¹
Not
adjustable
D.82
Number of burner start-ups in heat-
ing mode
Number of burner start-ups /100 (3 equals 300)
¹
Not
adjustable
D.83
Number of burner start-ups in hot
water mode
Number of burner start-ups /100 (3 equals 300)
¹
Not
adjustable
D.84
Maintenance indicator: Number of
hours until the next maintenance
Adjustment range: 0 to 3000 hrs and "-" for deactivated
300 equals 3000 hrs
„-”
D.90
Status of digital controller
0 = Not recognised (eBUS address
≤
10)
1 = Recognised
Not
adjustable
D.91
Status of DCF with external temper-
ature sensor connected
0 = No reception
1 = Reception
2 = Synchronised
3 = Valid
Not
adjustable
D.93
Product type setting (device specific
number)
Setting range: 0 to 99
.. 656/4
‑
5 = 47
D.96
Default setting
Reset all adjustable parameters to factory setting
0 = No
1 = Yes
0
D.97
Activating the installer level
Service code 17
D.98
Telephone: Competent person
Programmable telephone number
1.
Five-digit numbers are saved for diagnostics codes 80 to 83. If you select D.80, for example, only the first two digits of the number
will be displayed (e.g. 10). Pressing
switches the display to the last three digits (e.g. 947). In this example, the number of oper-
ating hours for the heating is 10947 hrs. Pressing the
again causes the display to switch back to the diagnostics code that was
called up.
B
Inspection and maintenance work
–
Overview
The table below lists the manufacturer requirements with respect to minimum inspection and maintenance intervals. If na-
tional regulations and directives require shorter inspection and maintenance intervals, you should observe these instead of
the intervals listed in the table.
No.
Work
Inspection
(annual)
Mainten-
ance
(At least
every
two years)
1
Check the flue pipe for leak-tightness and to ensure that it is fastened correctly. Make sure that
it is not blocked or damaged and has been installed in accordance with the relevant Installation
Manual.
X
X
2
Check the general condition of the product. Remove dirt from the product and from the vacuum
chamber.
X
X
3
Visually inspect the general condition of the compact thermal module. In doing so, pay particular
attention to signs of corrosion, rust and other defects. If you notice any damage, carry out main-
tenance work.
X
X
4
Check the gas flow pressure at maximum heat input. If the gas flow pressure is not within the
correct range, carry out maintenance work.
X
X