Adapting the boiler to the heating installation
52
Installation and maintenance instructions ecoTEC plus 0020116700_01
11
Code
Parameter
Adjustable values
Factory
setting
Your own
setting
D.060
Number of temperature limiter shut-
downs
Number of shutdowns
Not adjustable
D.061
Number of ignition device cutoffs
Number of unsuccessful ignitions in the last attempt
Not adjustable
D.064
Average ignition time
In seconds
Not adjustable
D.065
Maximum ignition time
In seconds
Not adjustable
D.067
Remaining burner anti-cycling time
In minutes
Not adjustable
D.068
Unsuccessful ignitions at 1st attempt
Number of unsuccessful ignitions
Not adjustable
D.069
Unsuccessful ignitions at 2nd attempt
Number of unsuccessful ignitions
Not adjustable
D.070
Setting diverter valve position
Normal operating mode
Mid-position (parallel operation)
Continuous heating adjustment
Normal oper-
ating mode
D.071
Target value maximum heating flow
temperature
40 to 80 °C
75 °C
D.072
Internal pump overrun after cylinder
charging
Adjustable from 0 - 10 minutes in increments of 1
minute
2 mins
D.073
Warm start target offset
Adjustable from -15 K to 5 K
0
D.075
Max. charging time for domestic hot
water cylinder without independent con-
trol system
20 - 90 min
45 mins
D.076
Device specific number
1 = VU 612
3 = VU 615
4 = VU 618
9 = VU 624
14 = VU 630
20 = VU 637
6 = VUW 824
10 = VUW 831
17 = VUW 837
Not adjustable
D.077
Limit on cylinder charging output
in kW
Limit on cylinder charging output
in kW
D.078
Limit on cylinder charging temperature
in °C
55 °C - 80 °C
Note: The chosen value must be at least 15 K or 15 °C
above the set cylinder target value.
75 °C
D.080
Operating hours, heating
In hours (h)
Not adjustable
D.081
Operating hours, hot water generation
In hours (h)
Not adjustable
D.082
Number of burner start-ups in heating
mode
Number of start-ups
Not adjustable
D.083
Number of burner start-ups in hot water
mode
Number of start-ups
Not adjustable
D.084
Maintenance indicator: Number of hours
until the next maintenance
Setting range: 0 to 3000 hrs and "---" for deactivated
"---"
D.088
Start delay for hot water draw-off detec-
tion via impeller (VUW boilers only)
1.5 l/min and no delay,
3.7 l/min and 2 s delay
2.0 l/min and
no delay
D.090
Status of digital controller
recognised, not recognised
Not adjustable
11.1 Diagnosis codes (continued)