15
Instructions for installation and servicing ecoTEC
3.9 Electrical
supply
A 230 V, ~ 50 Hz single phase electricity supply fused to
3 Amp. must be provided in accordance with the latest
edition of BS 7671 (IEE Wiring Regulations) and any other
local regulations that may apply. In IE reference should
be made to the current edition of the ETCI rules. The
method of connection to the mains electricity supply
must provide a means of completely isolating the boiler
and its ancillary controls. Isolation is preferably by the
use of a fused three pin plug and unswitched shuttered
socket outlet, both complying with the requirements of
BS 1363. Alternatively, a 3 Amp. fused double pole switch
with a 3 mm contact separation on both poles may be
used.
Danger!
This appliance must be earthed.
3.10 Guide to system requirements
3.10.1 Water circulation system
Detailed recommendations for the water circulation sys-
tem are given in BS 6798 and BS 5449: Part 1 (for small
bore and micro bore central heating systems). Pipework
not forming part of the useful heating surface should be
insulated to help prevent heat loss and possible freezing,
particularly where pipes are run through roof spaces
and ventilated underfloor spaces. Draining taps must be
located in accessible positions which permit the draining
of the whole system including the boiler and the hot
water system. Draining taps should be at least 1/2 in.
BSP nominal size and be in accordance with BS 2879.
The boiler is suitable for use with minibore or microbore
systems. Copper tubing to BS 2871: Part 1 should be used
for water carrying pipework. All capillary joints in all
DHW pipework must be made with lead free solder.
Particularly where a new boiler is to be fitted to an exist-
ing system, it is good practice that the system is thor-
oughly cleansed.
Important:
To prevent the formation of deposits and pre-
vent serious damage to the appliance and sys-
tem, cleansers must be used carefully and must
be completely removed by thoroughly flushing
the system. Cleansers should only be left in
systems for a maximum of 24 hours.
This cleansing must take place prior to the fitting of the
new boiler and be in accordance with BS 7593. For
advice on the application of system cleansers contact
Sentinel, Betz Dearborn Ltd. Widnes, Cheshire, WA8
8UD. Tel: 0151 420 9595, or Fernox, Alpha Fry
Technologies, Tandem House, Marlow Way, Croydon, CR0
4XS. Tel 0870 8700362.
3.10.2 Filling and preparing heating system
The system can be filled using the built in filling loop
(ecoTEC plus combination boilers only) or via a separate
filling point fitted at a convenient position on the heat-
ing circuit. The connection must be removed when filling
is completed. Where local Water Authority regulation
does not allow temporary connection, a sealed system
filler pump with break tank must be used. The heating
system will not be filled automatically from the domestic
hot water side. (Alternative methods of filling sealed sys-
tems are given in BS 5449).
3.10.3 Pressure relief valve
A pressure relief valve is provided with the boiler. This
safety device is required on all sealed C.H. systems and
is preset at 3 bar and provided with a 15 mm compres-
sion connection for a discharge pipe, which must be of
no less than 15 mm in diameter. The pressure relief valve
must not be used for draining purposes.
3.10.4 Pressure gauge
This is factory fitted to the boiler and indicates the pri-
mary circuit pressure to facilitate filling and testing.
3.10.5 Expansion vessel
ecoTEC boilers incorporate a 10 litre expansion vessel
which is suitable for a sealed heating system with a max-
imum water content of 100 litres.
If the nominal capacity of the built in expansion vessel is
not sufficient for the heating system (for instance in
case of modernisation of old open systems) an addition-
al expansion vessel can be installed external to the boil-
er. It should be fitted in the return pipe as close as possi-
ble to the boiler in accordance with BS 5449: Part 1.
Guidance on the sizing of an additional expansion vessel
is given in Table 3.5.
General requirements 3
Содержание ecoTEC plus 612
Страница 54: ...Supplied By www heating spares co Tel 0161 620 6677...
Страница 55: ...Supplied By www heating spares co Tel 0161 620 6677...
Страница 56: ...Supplied By www heating spares co Tel 0161 620 6677 839592_05 GB 08 2006...
Страница 58: ...Supplied By www heating spares co Tel 0161 620 6677 834449_09GB_082006 qxd 10 08 2006 12 20 Seite 2...
Страница 92: ...Supplied By www heating spares co Tel 0161 620 6677 36 834449_09GB_082006 qxd 10 08 2006 12 20 Seite 36...
Страница 116: ...Supplied By www heating spares co Tel 0161 620 6677 60 834449_09GB_082006 qxd 10 08 2006 12 20 Seite 60...
Страница 117: ...Supplied By www heating spares co Tel 0161 620 6677 61 834449_09GB_082006 qxd 10 08 2006 12 20 Seite 61...
Страница 118: ...Supplied By www heating spares co Tel 0161 620 6677 62 834449_09GB_082006 qxd 10 08 2006 12 20 Seite 62...
Страница 119: ...Supplied By www heating spares co Tel 0161 620 6677 63 834449_09GB_082006 qxd 10 08 2006 12 20 Seite 63...
Страница 120: ...Supplied By www heating spares co Tel 0161 620 6677 834449_09 GB 082006 834449_09GB_082006 qxd 10 08 2006 12 20 Seite 64...
Страница 122: ...Supplied By www heating spares co Tel 0161 620 6677...
Страница 124: ...Supplied By www heating spares co Tel 0161 620 6677 0020010870 01 GB 03 2006 2...
Страница 142: ...Supplied By www heating spares co Tel 0161 620 6677 0020010870 01 GB 03 2006 20...
Страница 162: ...Supplied By www heating spares co Tel 0161 620 6677 Notes 0020010870 01 GB 03 2006 40...
Страница 163: ...Supplied By www heating spares co Tel 0161 620 6677...
Страница 179: ...Supplied By www heating spares co Tel 0161 620 6677 15 Instructions for use ecoTEC...
Страница 180: ...Supplied By www heating spares co Tel 0161 620 6677 16 Instructions for use ecoTEC...
Страница 181: ...Supplied By www heating spares co Tel 0161 620 6677 20 C 20 C 15 C 5 C bar bar VRT VRC i F P...
Страница 182: ...Supplied By www heating spares co Tel 0161 620 6677...
Страница 183: ...Supplied By www heating spares co Tel 0161 620 6677 19 Instructions for use ecoTEC...
Страница 184: ...Supplied By www heating spares co Tel 0161 620 6677 838402_04 GB 08 2006...