Appendix
40
Installation and maintenance instructions ecoTEC exclusive 0020186710_06
Code
Parameter
Values
Unit
Increment, select, explanation
Default
setting
Own
setting
Min.
Max.
D.130
Hydraulic operating mode
0
4
–
0: Without bypass valve
1: 40% (low loss head.)
2: 60% (low loss head.)
3: 100% (low loss head.)
4: With bypass valve
0
D.131
Differential pressure
primary circuit
Current value
mbar
–
–
Not ad-
justable
D.132
Multi-occupancy
0
1
–
0: Off
1: On
0
D
Status codes
–
Overview
Status code
Parameter
Meaning
Heating mode
S.00
Heating: No heat demand
Heating: No heat demand
S.01
Heating mode: Fan start-up
Heating mode: Fan start-up
S.02
Heating mode: Pump pre-run
Heating mode: Pump pre-run
S.03
Heating mode: Ignition
Heating mode: Ignition
S.04
Heating mode: Burner on
Heating mode: Burner on
S.05
Heating mode: Pump/fan overrun
Heating mode: Pump/fan overrun
S.06
Heating mode: Fan overrun
Heating mode: Fan overrun
S.07
Heating mode: Pump overrun
Heating mode: Pump overrun
S.08
Heating mode: Anti-cycling time
Heating mode: Remaining anti-cycling time
S.09
Heating mode: Measuring program
Heating mode: Measuring program
Cylinder charging mode
S.20
DHW demand
DHW demand
S.21
DHW mode: Fan start-up
DHW mode: Fan start-up
S.22
DHW mode: Pump pre-run
DHW mode: Pump pre-run
S.23
DHW mode: Ignition
DHW mode: Ignition
S.24
DHW mode: Burner on
DHW mode: Burner on
S.25
DHW mode: Pump/fan overrun
DHW mode: Pump/fan overrun
S.26
DHW mode: Fan overrun
DHW mode: Fan overrun
S.27
DHW mode: Pump overrun
DHW mode: Pump overrun
S.28
DHW anti-cycling time
Hot water burner anti-cycling time
S.29
DHW mode: Measuring program
DHW mode: Measuring program
Others
S.30
No heat demand: Controller
Room thermostat (RT) is blocking heating mode
S.31
No heat demand: Summer mode
Summer mode active or no heat requirement from eBUS
controller
S.32
Waiting time deviation: Fan speed
Waiting period because of fan speed deviation
S.33
Waiting time: Air monitor
Waiting period: Air pressure sensor/switch reports that
the pressure signal is too low
S.34
Heating mode: Frost protection
Frost protection mode active
S.36
Target value for ext. controller lower than 20 °C
Reference setting for continuous controller 7-8-9 or
eBUS controller is < 20°C and blocks the heating mode
S.37
Waiting time: Deviation in fan speed
Waiting time: Fan failure in operation
S.39
Contact thermostat triggered
"Burner off contact" has responded (e.g. contact thermo-
stat or condensate pump)
S.40
Comfort protection active
Comfort protection mode is active: Product running with
limited heating comfort
S.41
Water pressure too high
Water pressure > 2.8 bar