Appendix
34
Installation and maintenance instructions ecoTEC exclusive 0020186710_06
Setting level
Values
Unit
Increment, select, explanation
Default
setting
Min.
Max.
Hydraulic operating mode
0
4
–
0: Without overflow
1: 40% (low loss head.)
2: 60% (low loss head.)
3: 100% (low loss head.)
4: With overflow
0
Pressure level
100
400
mbar
10
200
Target flow temp.
30
75
℃
1
–
DHW temperature
35
60
℃
1
Product with hot water generation
–
Green iQ
–
–
–
On, Off
On
Heating partial load
–
–
kW
Partial load only, full load only, auto
Auto
Auxiliary relay
1
10
–
1 = Circulation pump
2 = External pump
3 = Cylinder charging pump
4 = Extractor hood
5 = External solenoid valve
6 = External fault message
7 = Solar pump (not active)
8 = eBUS remote control (not active)
9 = Legionella protection pump (not active)
10 = Solar valve (not active)
2
Accessory relay 1
1
10
–
1 = Circulation pump
2 = External pump
3 = Cylinder charging pump
4 = Extractor hood
5 = External solenoid valve
6 = External fault message
7 = Solar pump (not active)
8 = eBUS remote control (not active)
9 = Legionella protection pump (not active)
10 = Solar valve (not active)
2
Accessory relay 2
1
10
–
1 = Circulation pump
2 = External pump
3 = Cylinder charging pump
4 = Extractor hood
5 = External solenoid valve
6 = External fault message
7 = Solar pump (not active)
8 = eBUS remote control (not active)
9 = Legionella protection pump (not active)
10 = Solar valve (not active)
2
Set the type of gas
0
2
–
0: Natural gas
1: Propane 50 mbar
2: Propane 30/37 mbar
–
Contact details
Phone number
–
0-9
–
End the installation assistant?
–
–
–
Yes, No
–
¹
Fault lists are only displayed, and can only be deleted, if faults have occurred.