16 Fault finding
16.3 Fault Codes
Fault codes take priority over all other display functions
in the event of a system fault occurring.
Code Description
Comment
F1
Ignition fault (lockout)
No gas; Insufficient gas; Incorrect gas valve adjustment; Electrode defect;
Failed to light
Ignition lead defect; Electronic igniter defective; Check air inlet duct;
Check connections to igniter unit
F4
Ignition fault (lockout)
As above
Went out when lit
F5
Overheat fault
Overheat stat operated; Maximum temperature exceeded;
Check thermistor connections; Air in system with thermistor at maximum
setting; Faulty overheat stat connection; Check that pump is wired into
appliance and not from programmer. This would cause no pump overrun
F6
Central heating flow NTC fault
Flow NTC cable defective/broken NTC faulty
Flow thermistor not fitted correctly, Check pipe work configuration
F10
Central heating return NTC fault
Return NTC cable defective/broken NTC faulty
Check that thermistor attached correctly to pipe.
F11
No reception by main board
Connection fault between main PCB and interface; Faulty interface;
Faulty main PCB (processor), Check fan
F12
No reception by the local user interface
As F.11
F13
Main board fault
As F.11
F14
Central heating flow t° > 95° C
System fault; Possible external pump failure; Check NTC on flow
Check that pump is wired into appliance and not from programmer.
This would cause no pump overrun
F16
Flame detection fault
(flame presence >5 s after burner stop)
Gas valve defective
F17
Power supply <170 V
Check electrical supply / polarity, Check fan
F18
Local user interface fault
Connections; Faulty interface
F19
Central heating NTC unplugged
Check NTC connection
F20
MMI software incompatible with IRIS software
Possible connection fault
F24
Central heating return t° >90°C
System fault; Possible external pump failure; Check NTC on return;
Check that pump is wired into appliance and not from programmer.
This would cause no pump overrun.
F25
Maximum temperature rise slope
Possible external pump failure; Air in system restricting movement of water.
Insufficient circuit flow
F26
Maximum delta t
Check NTC on return; System fault – too restrictive?; Possible pump failure
16.2 Fault Memory
The fault memory stores details of the five most recent
faults. To display the fault memory, proceed as follows;
• With the interface in ‘normal’ mode, press and hold the
‘mode’ button (
) for 10 seconds until a flashing ‘0’
appears.
• Press the ‘mode’ button again.
• The 5 fault memory screens are now available to be
viewed, memory 1 being the most recent. Within each
memory screen, 5 additional screens provide further
information to assist the installer/engineer.
To cancel the fault memory mode proceed as follows;
• Press and hold the ‘mode’ button for 10 seconds until
the screen returns to the ‘user’ mode.
No. Memory screen type
Comments
1
Fault code
Fault code 1 – 26 (see page 34 – ‘Fault finding’)
2
Burner phase
Working phase
3
DHW temperature
No function
4
CH flow temperature
°C at time of fault
5
Tank temperature
No function
Содержание ecoMAX pro 18E
Страница 37: ...Instructions for Use Installation and Servicing ecoMAX pro 37 Declaration of Conformity 17...
Страница 38: ...Instructions for Use Installation and Servicing ecoMAX pro 38...
Страница 39: ...Instructions for Use Installation and Servicing ecoMAX pro 39...
Страница 40: ...0020005557_04 GB 08 2006 Subject to alteration...