Installation and maintenance instructions ecoCRAFT 0020055744_08
20
5.9.4 Connecting
a
controller
Connecting a VRC 430 control unit (controller out-
side the electronics box)
A weather-controlled outside temperature controller
with modulating burner control can be used to control
the heating installation.
The Vaillant VRC 430 controller must be connected via
the "Bus" connection (red plug) in accordance with
Fig. 5.8. The bridge between the terminals 3 and 4
should remain intact (lilac plug).
The sensors and the system components that are not
listed in Section 5.10.2 are connected to the controller.
The electrical connection to the Vaillant heating control
unit is shown in Fig. 5.7.
Further information can be obtained from the regulator
instructions.
Before opening the electronics box, switch off the sup-
ply to the unit and secure it against unintentional
switching on.
Cylinder sensor
ϑ
Heating
water
pump
Charging
pump
Network
Boiler
Bus
red
+
-
0 - DCF- AF
DCF / AF
X41
AF
Edge connector
red
1
0
0
RF
DCF
blue
6
FB
X13
X18
X1
Pump
1
green
Network
tur-
quoise
white
purple
Pump
2
grey
red
Bus
VRC 430
Fig. 5.8 Connecting a VRC 430 control unit
VRC 430, VRC 630, VRS 620 control units
• Connect the 2 wires of the "Bus" connections (red
plug) to the connections of the same name in the con-
troller on the VRC 630, VRS 620 or on the VRC 430 if
it is mounted externally.
• Alternatively, plug the VRC 430 controller into the op-
erating screen on the boiler (internal mounting).
5 Installation