6 Start-up
12
Installation and maintenance instructions atmoMAG 0020273765_00
1
2
▶
Start up the product with the product casing attached.
▶
Turn the temperature selector
(1)
clockwise as far as it
goes and turn the rotary power switch
(2)
anti-clockwise
as far as it goes in order to set the lowest water volume
and the maximum gas volume.
▶
Open a hot water tap.
▶
Ensure that the water pressure is at least 0.13 MPa
(1.3 bar) during the test.
▶
Operate the product until a steady state is reached (ap-
prox. 10 minutes).
▶
Block off the flue gas route with a Vaillant flue gas re-
strictor, for example. Also observe the documentation
enclosed with the flue gas restrictors.
◁
The flue gas sensor must automatically interrupt the
gas supply within two minutes.
▶
Close the hot water tap.
▶
Allow the flue gas sensor to cool for at least 10 minutes.
▶
Start up the product again.
1
▶
Clear any faults from the product by opening the hot wa-
ter tap again and switch the product on and off again by
pressing the main switch
(1)
a second time.
▶
If the fault clearance does not work or the product is re-
peatedly blocked by a safety device, check the product or
contact Vaillant Customer Service.
▶
In this case, shut down the product.
6.6
Checking the gas flow pressure
1
▶
Close the gas stopcock.
▶
Unscrew the sealing screw
(1)
from the test nipple on the
gas valve assembly.
▶
Remove the seal.
▶
Connect a manometer to the test nipple on the gas valve
assembly.
▶
Open the gas stopcock.
▶
Start up the product in accordance with the operating
instructions and draw off domestic hot water.
▶
Measure the gas flow pressure.
Applicability:
Germany
OR Austria
Gas family
Permissible gas flow pres-
sure
Liquid gas
G31
4.25
–
5.75 kPa
(42.5
–
57.5 mbar)
Conditions
: Gas connection pressure not in the permissible range
Danger!
Risk of material damage and operating
faults caused by incorrect gas flow pres-
sure.
If the gas flow pressure lies outside the per-
missible range, this can cause operating
faults in and damage to the product.
▶
Do not make any adjustments to the
product.
▶
Check the gas installation.
▶
Do not start up the product.
▶
If you are unable to eliminate the fault, contact the gas
supply company.
▶
Close the gas stopcock.
▶
Remove the manometer.