8
Installer's Quick Guide - aroTHERM plus 11/2020
8
Installation and R290 clearances
1 m
1 m
1 m
1 m
1 m
1 m
1 m
0,5 m
2,3 m
0,5 m 1 m
1,2 m
0,5 m
0,5 m
0,5 m
0,5 m
0,5 m
1 m
2,3
m
1,6 m
0,5
m
0,5
m
0,5
m
0,25 m
0,25 m
0,5 m
0,5 m
0,1 m
0,5 m
0,25
m
When placing the unit you must be aware of drains and
openings.
In the unlikely event of a refrigerant leak the gas needs to be
allowed to disperse to stop the risk of the gas igniting.
Follow the diagrams below to ensure adequate clearance.
C
D
A
B
Minimum clearances
Unit
Dimension
A
mm
2100
B
mm
3100
C
mm
200/250
D
mm
1000
C
D
A
B
There must be no ignition sources, such as plug sockets,
lamps or rotary insolation switches in the protective zone.
Air vents to void areas and air tight drains can be within the
protective zone.
Protective zone