Installer's Quick Guide - aroTHERM plus 11/2020
4
aroTHERM output
35°C flow
40°C flow
45°C flow
50°C flow
55°C flow
Output
SCOP
Output
SCOP
Output
SCOP
Output
SCOP
Output
SCOP
3.5kW
-5°C
4.2
4.41
4.1
4.03
4
3.65
3.9
3.37
3.8
3.10
-3°C
4.6
4.4
4.3
4.2
4
0°C
4.7
4.7
4.6
4.5
4.4
2°C
4.9
4.9
4.9
4.7
4.6
5kW
-5°C
6.3
4.48
6
4.13
5.6
3.77
5.5
3.41
5.4
3.06
-3°C
6.8
6.4
6.1
5.9
5.8
0°C
6.9
6.7
6.6
6.4
6.2
2°C
7.1
7
6.9
6.7
6.5
7kW
-5°C
8.2
4.36
8.1
4.13
8
3.91
7.5
3.65
7
3.39
-3°C
8.8
8.6
8.4
7.9
7.4
0°C
9.5
9.3
9.1
8.6
8.1
2°C
10
9.8
9.6
9
8.5
10kW
-5°C
9.9
5.03
9.7
4.58
9.4
4.13
9.1
3.85
8.8
3.58
-3°C
10.7
10.3
10
9.6
9.2
0°C
11.9
11.6
11.3
10.7
10.2
2°C
12.8
12.5
12.1
11.5
10.9
12kW
-5°C
13.1
4.88
12.8
4.55
12.5
4.21
11.7
3.92
10.8
3.63
-3°C
13.9
13.4
12.9
12.1
11.2
0°C
15.2
14.6
14.1
13.2
12.3
2°C
16
15.5
14.9
13.9
13
Plan your work …
Select the correct aroTHERM plus to fit your needs
Performance data
When designing a heating system that utilises a heat pump, there are a number of design factors that need to be considered.
Heat loss
MCS recommend using the MIS 3005 installation standard for designing a heat pump system. Systems should be specified
at peak winter requirements, depending on location, to ensure year round comfort as detailed in the table below.
SCOP data
MIS 3005 design temperatures
Hourly dry-bulb temperature (/
o
C)
equal to or exceeded for % of
the hours in a year
99%
Belfast
-1.2
Birmingham
-3.4
Cardiff
-1.6
Edinburgh
-3.4
Glasgow
-3.9
London
-1.8
Manchester
-2.2
Plymouth
-0.2
A room-by-room heating requirement check will then need to be carried out at the set outside temperature in order to
understand the heating needs of the total property.