0020209589_04 ecoTEC pro Installation and maintenance instructions
21
Open end of pipe direct into gulley below ground level but
above water level
Susceptible to siphonage, must terminate in a gulley
7.7.1.7 External termination into rain water down
pipe
≤ 3 m
Ø22mm
Ø 32mm
NB only combined foul/rainwater drain
7.7.1.8 Additional methods of introducing air breaks
1
2
3
1
Air break
2
Using a tundish
3
Using a pipe
7.7.1.9 Connection of condensate pump
Ø32mm
Ø22mm
≥ 3 m
Preferred option for external connection
7.8
Flue installation
7.8.1
Installing and connecting the air/flue pipe
1.
You can find out which air/flue pipes may be used by
consulting the enclosed set-up instructions for the
air/flue system.
2.
Observe the information on positioning the air/flue ter-
minal.
Condition
: Installation in damp rooms
▶
You must connect the product to a room-sealed air/flue
system. The combustion air must not be taken from the
installation site.
3.
Install the air/flue pipe using the set-up instructions.
7.8.2
Replacing the connector for the air/flue pipe
as required
1.
Replace the connector for the air/flue pipe as required.
The product-specific standard equipment is listed under
Technical data.
2.
Remove the connection piece for the air/flue pipe
–
this
is installed at the factory. (
3.
If required, install the connection piece for the air/flue
pipe, 80/125 mm diameter. (
7.8.2.1 Removing the connection piece for the
air/flue pipe
1.
2.
3.
1.
Insert a screwdriver into the slot between the measuring
stub pipes.
2.
Press the screwdriver carefully down
(1.)
.
3.
Turn the connection piece anticlockwise
(2.)
as far as it
will go and then remove it by pulling it upwards
(3.)
.
7.8.2.2 Installing the connection piece for the
air/flue pipe, 80/125 mm diameter
1.
Remove the connection piece for the air/flue pipe
–
this
is installed at the factory. (
2.
Insert the alternative connection piece. In doing so, pay
attention to the latching lugs.
3.
Turn the connection piece clockwise until it clicks into
position.