background image

52

Installation and maintenance instructions ecoTEC plus 0020238195_07

I

Commissioning Flow Chart

PRIOR TO CO AND COMBUSTION RATIO CHECK

The boiler manufacturer’s installation instructions should have been followed, gas type verified and gas 

supply pressure/rate checked as required prior to commissioning.

As part of the installation process, 

especially where a flue has been fitted by persons other than the 

boiler installer

, visually check the integrity of the whole flue system to confirm that all components are 

correctly assembled, fixed and supported. Check that manufacturer’s max. flue lengths have not been 

exceeded and all guidance has been followed (e.g. Gas Safe Technical Bulletin TB008).

The flue gas analyser should be of the correct type, as specified by BS 7967

Prior to its use, the flue gas analyser should have been maintained and calibrated as specified by the 

manufacturer. The installer must have the relevant competence for use of the analyser.

Check and zero the analyser IN FRESH AIR as per analyser manufacturer’s instructions.

NOTE

THE AIR GAS RATIO VALVE IS FACTORY 

SET AND MUST NOT BE ADJUSTED 

DURING COMMISSIONING UNLESS THIS 

ACTION IS RECOMMENDED FOLLOWING 

CONTACT WITH THE MANUFACTURER.

If any such adjustment is recommended and 

further checking of the boiler is required the 

installer/service engineer must be competent 

to carry out this work and to use the flue gas 

analyser accordingly.

If the boiler requires conversion to operate with 

a different gas family (e.g. conversion from 

natural gas to LPG) separate guidance will be 

provided by the boiler manufacturer

 CARRY OUT FLUE INTEGRITY CHECK USING ANALYSER

Insert analyser probe into air inlet test point and allow readings to stabilise.

NOTE

 - where no air inlet test point is provided then a flue integrity check 

with the analyser is not possible. The installer should verify that flue 

integrity has been visually checked in accordance with the  

“Prior to 

CO and combustion ratio check”

 box above before proceeding to the 

“Check CO and combustion ratio at maximum rate” 

stage below.

 

SET BOILER TO MINIMUM RATE

In accordance with boiler instructions, set boiler to operate at minimum rate (to 

minimum load condition). Allow sufficient time for combustion to stabilise.

NOTE 

- If manufacturer’s instructions do not specify how to set boiler to minimum 

rate contact Technical Helpline for advice.

CHECK CO AND COMBUSTION RATIO AT MINIMUM RATE

With boiler still set at minimum rate, insert analyser probe into flue gas sampling 

point. Allow readings to stabilise before recording.

NOTE 

- If no flue gas sampling point is present and the correct procedure is not 

specified in the manual, consult boiler manufacturer for guidance.

CHECK CO AND COMBUSTION RATIO AT MAX. RATE

With boiler still set at maximum rate, insert analyser probe into flue gas 

sampling point. Allow readings to stabilise before recording.

NOTE 

- If no flue gas sampling point is present and the correct procedure is 

not specified in the manual, consult boiler manufacturer for guidance.

SET BOILER TO MAXIMUM RATE

In accordance with boiler instructions, set boiler to operate at max. rate 

(full load condition). Allow sufficient time for combustion to stabilise.

NOTE - Do not insert analyser probe during this period to avoid 

possible “flooding” of sensor.

Is

CO less than 

350ppm and

CO/CO

2

 ratio

less than 0.004

Is

O

2

 

•

 20.6%

and

CO

2

 < 0.2%

Is

CO less than 

350ppm and

CO/CO

2

 ratio

less than 0.004

BOILER IS OPERATING SATISFACTORILY

no further actions required.

Ensure test points are capped, boiler case is correctly replaced and 

all other commissioning procedures are completed.

Complete Benchmark Checklist, recording CO and combustion ratio 

readings as required.

TURN OFF APPLIANCE AND CALL 

MANUFACTURER’S TECHNICAL HELPLINE 

FOR ADVICE.

THE APPLIANCE MUST NOT BE 

COMMISSIONED UNTIL PROBLEMS ARE 

IDENTIFIED AND RESOLVED.

 VERIFY FLUE INTEGRITY

Analyser readings indicate that combustion products 

and inlet air must be mixing. Further investigation of 

the flue is therefore required.

Check that flue components are assembled, fixed 

and supported as per boiler/flue manufacturer’s 

instructions.

Check that flue and flue terminal are not obstructed.

Is

CO

 

less than 

335ppm

and

CO/CO

2

 ratio less 

than 0.004

Is

O

2

 

•

 20.6%

and

CO

2

 < 0.2%

Check all seals around the appliance burner, 

internal flue seals, door and case seals. 

Rectify where necessary.

TURN OFF APPLIANCE AND CALL 

MANUFACTURER’S TECHNICAL HELPLINE 

FOR ADVICE.

THE APPLIANCE MUST NOT BE 

COMMISSIONED UNTIL PROBLEMS ARE 

IDENTIFIED AND RESOLVED. IF 

COMMISSIONING CANNOT BE FULLY 

COMPLETED, THE APPLIANCE MUST BE 

DISCONNECTED FROM THE GAS SUPPLY IN 

ACCORDANCE WITH THE GSIUR.

NOTE: 

Check and record CO and combustion ratio 

at both max. and min. rate before contacting the 

manufacturer.

 

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES

Содержание 0010015674

Страница 1: ...en Installation and maintenance instructions ecoTEC plus VU 6 6 5 OVZ H GB 0020238195_07 12 10 2020...

Страница 2: ...lementary water 26 9 3 Filling the condensate trap 27 9 4 Flushing the heating installation for the first time cold 27 9 5 Switching on the product 27 9 6 Running the installation assistants 27 9 7 Re...

Страница 3: ...Any direct use in industrial or commercial processes Any use other than those described in these instructions and any use that goes beyond what is described here 1 2 Qualification The person carrying...

Страница 4: ...cially available soft soap to aid installa tion 1 3 3 Electricity The power supply terminals L and N remain live even if the unit main switch is switched off To prevent electric shocks proceed as fol...

Страница 5: ...1 3 10 Safety devices Install the necessary safety devices in the installation 1 4 Regulations directives laws standards Observe the national regulations stand ards directives ordinances and laws 1 5...

Страница 6: ...illant group com Spares Enquiries Telephone 01773 596 615 To register your Vaillant appliance visit https self service vaillant co uk warranty registration Vaillant is a licensed member of the Benchma...

Страница 7: ...l effi ciency 89 8 89 8 89 7 89 7 89 7 Flue gas mass flow rate in heating mode at P min 2 08 g s 2 08 g s 2 31 g s 2 80 g s 3 30 g s 3 3 g s Flue gas mass flow rate in heating mode at P max 5 5 g s 6...

Страница 8: ...ata Heating VU 126 6 5 OVZ H GB VU 156 6 5 OVZ H GB VU 186 6 5 OVZ H GB VU 246 6 5 OVZ H GB VU 306 6 5 OVZ H GB VU 356 6 5 OVZ H GB Max flow temperature ad justment range default setting 75 C 10 to 80...

Страница 9: ...play the serial number in the display 5 4 Information on the data plate The data plate is mounted on the underside of the product at the factory The data plate keeps record of the country in which the...

Страница 10: ...estart the boiler press the reset button on the boiler interface If the boiler fails to resume normal operation and all external controls are calling for heat then call your Installation Servi cing co...

Страница 11: ...Rear air flue connection 6 Top air flue connection 6 3 Installation site This boiler is not suitable for outdoor installation This boiler may be installed in any room However if the boiler is being i...

Страница 12: ...lue gas systems for more information about the other possibilities and associated accessories Minimum fall 44 mm m Standard flue terminal kits have an in built fall back to the boiler to drain the con...

Страница 13: ...ding material Vertical flue clearance to combustible building material 500 mm 1 500 mm J Above below and either side of an opening door air vent or opening window 300 mm K Diagonally to an opening doo...

Страница 14: ...e from pluming depending on site conditions Terminals must be positioned so to avoid combustion products entering the building Support the flue at approximately one metre intervals and at a change of...

Страница 15: ...ard is required if persons could come into con tact with the terminal or the terminal could be subject to dam age If a terminal guard is required it must be positioned to provide minimum of 50 mm clea...

Страница 16: ...to ascertain the locations at which you need to drill holes 6 8 Wall mounting the product Note If you are using the rear air flue connection in stall the air flue pipe before you wall mount the produc...

Страница 17: ...0020238195_07 ecoTEC plus Installation and maintenance instructions 17 C D A B E 6 10 2 Installing the side section Refit the components in the reverse order...

Страница 18: ...11 kPa 110 mbar 7 2 Installing the heating pump Pressure loss in the product from the product 0 50 100 150 200 250 300 350 400 0 200 400 600 800 1000 1200 1400 1600 430 424 418 415 412 435 A B 1 2 A F...

Страница 19: ...nd BS 7074 Part 1 Example For an initial design pressure of 0 7 bar the minimum total vessel volume required is 0 063 x Total System Volume Note A higher initial design pressure requires a larger volu...

Страница 20: ...and the drain hose is not air tight Connect a condensate discharge pipe 21 5 mm not included in the scope of delivery to the drain hose 2 During installation remove all burs from inside of cut pipe w...

Страница 21: ...Seal 3 Plastic tube 100 mm diameter 4 Bottom of sealed tube 5 Limestone chippings 6 Hole depth 400 mm minimum Least preferred option must not terminate in rain water drain 7 8 1 6 Internal terminatio...

Страница 22: ...ck Continuous voltage is present at power sup ply terminals L and N even when the unit is switched off using the standby button Switch off the power supply Secure the power supply against being switch...

Страница 23: ...e nominal mains voltage is 230 V 3 Do not interrupt the mains supply with a time switch or programmer 4 Set up a fixed connection and install a partition with a contact gap of at least 3 mm e g fuses...

Страница 24: ...ontrol to the main plug BUS RT B off Burner off RT 24V BUS Remove the bridge from the 24V RT plug Condition 230 V 3 wire connection Ensure that the control is designed for a maximum nom inal current o...

Страница 25: ...ns for the in staller level is included in the table in the appendix Installer level Overview Page 38 8 2 Calling up the installer level 1 Only call up the installer level if you are a competent perso...

Страница 26: ...stipulate more stringent requirements the following applies You must treat the heating water in the following cases If the entire filling and supplementary water quantity dur ing the operating life o...

Страница 27: ...ly drain 4 Close the drain cocks 5 Refill the heating system with water 6 Close the filling valve and the cold water tap 9 5 Switching on the product Switch on the product via the main switch installe...

Страница 28: ...Start inst assistant You can restart the installation assistant at any time by call ing it up in the menu 9 8 Test programmes Menu Installer level Test programs As well as the installation assistants...

Страница 29: ...t the reference test point in the boiler be lower than indicated check if there is any blockage in the pipework or if the pipework is un dersized Condition Gas flow pressure not in the permissible ran...

Страница 30: ...w the product to operate for at least 15 minutes 4 Purge the heating installation 5 Call up the Live Monitor Menu Live Monitor Status codes Overview Page 43 If the product is working correctly the dis...

Страница 31: ...ed sticker which requests that the user reads the instructions to the front of the product in the end user s language Draw attention to the current issue of the Gas Safety Installation and Use Regulat...

Страница 32: ...CO at full load 9 0 1 0 vol 9 2 1 0 vol CO at full load 250 ppm 250 ppm CO CO 0 0031 0 0031 The value is OK The value is not OK you cannot start up the product Set the CO content Page 32 12 5 Setting...

Страница 33: ...exchanger 1 Check the heat exchanger for damage and dirt 2 If required clean and replace the heat exchanger 3 Protect the open electronics box from spraying water 1 4 Clean the ribs of the heat excha...

Страница 34: ...ction and maintenance work 1 Check the gas connection pressure gas flow pressure Page 29 2 Check the CO content Page 32 3 If required set the maintenance interval 4 Check the product for tightness Pag...

Страница 35: ...with the applicable standards We strongly recommend that you use original spare parts from the manufacturer as this guarantees fault free and safe operation of the product To receive information about...

Страница 36: ...electronics box 13 6 5 Replacing the PCB for the user interface B C C D A A 1 Open the electronics box Page 22 2 Pull the plug out of the PCB 3 Undo the clips on the PCB 4 Remove the PCB 5 Install the...

Страница 37: ...ally 10 If the gas flow rate lies outside of the tolerances specified in these in structions eliminate the fault in accordance with the regulations and the current technology Annually 11 Check the gen...

Страница 38: ...l Enter code 00 99 1 competent person code 17 Installer level List of faults F XX F XX Current value Installer level Test programs Gas type check Current value Liquid gas natural gas Installer level T...

Страница 39: ...r hood 5 External solenoid valve 6 External fault message 7 Solar pump not active 8 eBUS remote control not active 9 Legionella protection pump not active 10 Solar valve not active 2 Heating partial l...

Страница 40: ...Legionella protection pump not active 10 Solar valve not active 2 Contact data Phone number 0 9 End the installation assistant Yes No Fault lists are only displayed and can only be deleted if faults h...

Страница 41: ...stable d 23 Status of the heat de mand Current value off Heating off Summer mode on Heating on Not adjustable d 24 Status of the pressure switch 0 1 off Not switched on Switched Not adjustable d 25 St...

Страница 42: ...water off Function deactivated on Function activated 1 Adjustable d 67 Remaining burner anti cycling time setting under d 02 Current value min Not adjustable d 68 Number of unsuccessful ignitions at...

Страница 43: ...e Requirement S 21 Domestic hot water mode Fan prerun S 22 Domestic hot water mode Pump prerun S 23 Domestic hot water mode Burner ignition S 24 DHW mode Burner on S 25 DHW mode Pump fan overrun S 26...

Страница 44: ...e gas valve assembly mul tiple plug on PCB incorrectly plugged in break in cable harness ignition sys tem ignition transformer ignition cable ignition plug ignition electrode de fective ionisation flo...

Страница 45: ...verted flow and return temperature sensors have not been correctly installed F 85 Fault Temperature sensor The flow and or return temperature sensors have been installed on the same pipe incorrect pip...

Страница 46: ...X32 X90 X12 X35 X1 RT X21 L N L N 1 5 eBUS Burner off X106 M 4 3 2 1 N L 24V 230V 24V 230V 1 2 3 2 7 9 1 4 3 5 6 10 11 12 8 1 Main PCB 2 Interface PCB 3 Control system 4 Temperature sensor on the hea...

Страница 47: ...106 X32 X90 X12 X35 X1 RT X21 L N L N 1 5 eBUS Burner off X106 M 4 3 2 1 N L 24V 230V 24V 230V 1 2 3 2 7 9 1 4 3 5 6 10 11 12 8 1 Main PCB 2 Interface PCB 3 Control system 4 Temperature sensor on the...

Страница 48: ...r and they should be made aware it is ultimately their responsibility to register with the manufacturer within the allotted time period It is essential that the boiler is serviced in line with the man...

Страница 49: ...left at factory settings Yes No If no what is the maximum central heating output selected kW Dynamic gas inlet pressure mbar C Central heating return temperature C System correctly balanced rebalanced...

Страница 50: ...R delete as appropriate Date Engineer name Company name Telephone No Gas Safe registration No Max rate CO ppm CO CO CO Min rate CO ppm CO CO CO undertaken in accordance with manufacturers instructions...

Страница 51: ...R delete as appropriate Date Engineer name Company name Telephone No Gas Safe registration No Max rate CO ppm CO CO CO Min rate CO ppm CO CO CO undertaken in accordance with manufacturers instructions...

Страница 52: ...specify how to set boiler to minimum rate contact Technical Helpline for advice CHECK CO AND COMBUSTION RATIO AT MINIMUM RATE With boiler still set at minimum rate insert analyser probe into flue gas...

Страница 53: ...il Number 9 Gas flow rate 28 Gas group checking 19 Gas setting 28 Gas air mixture removing 32 Guarantee and Customer Service 6 H Handing over to the end user 31 Heat exchanger cleaning 33 Heat exchang...

Страница 54: ......

Страница 55: ......

Страница 56: ...lisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 492191 18 0 Fax 492191 18 2810 info vaillant de www vaillant de These instructions or parts thereof are protected by copyright...

Отзывы: