4 Set-up
8
Installation and maintenance instructions recoVAIR 0020159949_07
▶
If particular acoustic requirements are in place at the
installation site, you should take corresponding on-site
measures to prevent noise.
4.4
Installing the product on the wall
min. 1120
Caution.
Risk of material damage caused by con-
densate.
If the condensate cannot drain from the
product, this may damage the product and
condensate may leak out of the product and
onto the floor.
▶
Install the fixing bracket with the correct
horizontal and vertical alignment.
1.
Drill the holes for the fixing screws.
–
Installation height of the fixing bracket:
≥
1,120 mm
2.
Insert the rawl plugs into the drilled holes.
3.
Screw the fixing bracket to the wall, tared.
–
Installation position: Horizontal
–
Taring the fixing bracket: Using the slotted holes in
the fixing bracket
–
Spirit level
Danger!
Risk of injury caused by a heavy weight
when mounting the product.
The product weighs 41 kg. If you are mount-
ing the product, the product may easily slide
out of your hands and cause injuries.
▶
Make sure that the product is mounted by
at least two people.
4.
Position the product on the fixing bracket and mount the
product.
4.5
Connecting the condensate siphon/dry
siphon and condensate drain pipework
1.
Connect the condensate siphon/dry siphon to the
product (
→
Installation instructions for the condensate
siphon/dry siphon, accessories).
–
Condensate discharge pipe downward gradient
(descending from the product): > 5°
min. 20
1
A
B
Danger!
Risk of damage to health caused by incor-
rectly connected condensate drain pipe-
work!
In the interests of hygiene, the condensate
drain pipework must not be directly connec-
ted to the waste-water piping.
▶
Connect the condensate discharge to the
second siphon.