Appendix
0020159949_07 recoVAIR Installation and maintenance instructions
23
E
Check programmes
–
Overview
Prüfprogramme
Meaning
P.01 Bypass test
The bypass flap is actuated and moved to the closed and open position. In the event of a negative
test result,
Test not OK
is shown in the display. Then check that the bypass is connected correctly
and works correctly. If required, replace/clean components.
P.02 Test Frost prot. element
A defined volume flow is created by the ventilation unit and the frost protection element is switched
on. In the event of a negative test result,
Test not OK
is shown in the display. Check that the frost
protection element is connected correctly and works correctly. If required, replace components.
P.03 Initialisation measure
The ventilation unit runs through four ventilation levels, one after the other. The rotational speeds of
the ventilation levels are used as characteristic lines for monitoring the system efficiency. The check
programme must always be run through before the system efficiency function can be activated in the
configuration menu.
P.04 System efficiency test
The prerequisite is that check programme
P.03
has been executed once previously. To check the
system efficiency, four volume flows are created by the ventilation unit.
F
Maintenance messages
–
Overview
#
Message
Description
Maintenance work
Interval
1
M.800 Filter
change
The maintenance interval for
the filters was exceeded.
Maintaining the filters
At least twice annually
15
2
M.801 Mainten-
ance
The maintenance interval for
the product was exceeded.
Maintaining the product
At least annually
3
M.802 System ef-
ficiency impaired
The system efficiency is ad-
versely affected.
Increase/establish system effi-
ciency
As required
16
G
Technical data
VAR 260/4
VAR 260/4 E
VAR 360/4
VAR 360/4 E
Width
595 mm
595 mm
595 mm
595 mm
Depth
631 mm
631 mm
631 mm
631 mm
Height
885 mm
885 mm
885 mm
885 mm
Product with packaging
52.3 kg
56.3 kg
52.5 kg
56.5 kg
Product without packaging/ready for operation
41 kg
45 kg
41.2 kg
45.2 kg
Rated voltage/measuring voltage of the control circuit
230 V
230 V
230 V
230 V
Power frequency
50 Hz
50 Hz
50 Hz
50 Hz
Fuse, slow-blow
4 A
4 A
4 A
4 A
Power consumption
15 … 170 W
15 … 170 W
23 … 342 W
23 … 342 W
Max. power consumption (with frost protection element,
if available)
1,170 W
1,170 W
1,842 W
1,842 W
Current consumption
0.74 A
0.74 A
1.5 A
1.5 A
Minimum cross-section of the supply line
≥
1.5 mm
²
≥
1.5 mm
²
≥
1.5 mm
²
≥
1.5 mm
²
Protection class
1
1
1
1
Level of protection
IP10B
IP10B
IP10B
IP10B
Air connection area diameter (internal)
180 mm
180 mm
180 mm
180 mm
Air connection area diameter (external)
210 mm
210 mm
210 mm
210 mm
Heat exchanger material
Poly-
styrene/aluminium
grid
Poly-
styrene/aluminium
grid
Poly-
styrene/aluminium
grid
Poly-
styrene/aluminium
grid
Max. air volume flow
260 m
³
/h
260 m
³
/h
360 m
³
/h
360 m
³
/h
Nominal flow
115
… 200 m
³
/h
115
… 200 m
³
/h
175
… 277 m
³
/h
175
… 277 m
³
/h
Remaining delivery pressure at max. air volume flow
180 Pa
180 Pa
200 Pa
200 Pa
Specific power consumption at max. nominal flow and
external compression
0.3 W/(m
3
/h)
at 200 m
3
/h,
100 Pa
0.3 W/(m
3
/h)
at 200 m
3
/h,
100 Pa
0.38 W/(m
3
/h)
for 277 m
3
/h,
100 Pa
0.38 W/(m
3
/h)
for 277 m
3
/h,
100 Pa