X5 AC Drive User’s Manual
Chapter 6: Using Macro Mode / Quick Start
DPD00089A
-
67 -
© 2009 Vacon Incorporated All Rights Reserved
Table 6-5: Pump with PI Application Macro
(Core Factory Application from Table 6-1,
plus
the following
parameters)
Para. #
Parameter Name
Default
See Page
203
Stop Key Remote
Coast
204
Ref Select
Vin1
205
Vin1 Config
0-10 V
206
Vin1 Offset
0.00%
207
Vin1 Span
100.00%
208
Cin Config
0-20 mA 50
209
Cin Offset
0.0%
210
Cin Span
100.0%
211
Vin2 Config
0-10 V
212
Vin2 Offset
0.00%
213
Vin2 Span
100.00%
401
Ramp Select
ART-Strt/RS
406
DC Inject Config
DC at Stop
501
V/Hz Select
Pump Fxd
504
Skip Freq Band
0.2 Hz
505
Skip Freq 1
0.0 Hz
608
Restart Number
0
609
Restart Delay
60 sec
702
Imet Config
Current Out
703
Imet Span
100.0%
704
Imet Offset
0.0%
721
DI1 Configure
Preset 1
722
DI2 Configure
Preset 2
723
DI3 Configure
Preset 3
724
DI4 Configure
Ref Switch
725
DI5 Configure
PI Enable
803
PWM Frequency
16.0 kHz
804
Display Mode
Output Freq
850
PI Configure
No PI
851
PI Feedback
Vin1
852
PI Prop Gain
0
853
PI Int Gain
0
854
PI Feed Gain
1000
857
PI High Corr
100.00
858
PI Low Corr
0.00%
Содержание X5
Страница 1: ...X5 AC Drive user s manual ...
Страница 4: ......
Страница 125: ...X5 AC Drive User s Manual Chapter 7 X5 Parameters DPD00089A 123 2009 Vacon Incorporated All Rights Reserved ...
Страница 126: ...X5 AC Drive User s Manual Chapter 7 X5 Parameters DPD00089A 124 2009 Vacon Incorporated All Rights Reserved ...
Страница 138: ......
Страница 140: ......