APPENDIX 1 - VACON® IO DATA DESCRIPTION
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Table 216. Process data output mapping defaults for VACON
®
20 (standard application)
*Scaling is based on drive nominal power. Scaling can be seen from Table 217.
Table 217. Current scaling based on nominal power
Default process data out mapping can be changed in standard applications.
Table 218. FB Process data out mapping
1) Only in applications and option boards supporting fast or extended communication modes with
VACON
®
NXP. See Chapter 16 "Appendix 6 - Fieldbus option board communication".
2) Multipurpose application.
3) Currently only in
VACON
®
100 family internal protocols.
PD Out
Mapped Application Data
ID
Unit
Scale
1
Frequency reference
25
Hz
0.01 Hz
2
Output reference
1
Hz
0.01 Hz
3
Motor speed
2
rpm
1rpm
4
Motor voltage
6
V
0.1 V
5
Motor torque
4
%
0.1%
6
Motor current
3
A
Varies*
7
Motor power
5
%
0.1%
8
DC link voltage
7
V
1 V
Nominal power
Current scale
< 5 kW
0.01 A
5-100 kW kW
0.1 A
> 100 kW
1 A
Parameter name
Drives
VACON
®
100
family
VACON
®
NXP
2)
VACON
®
20
VACON
®
20 X/
CP
Path
ID
Path
ID
Path
ID
Path
ID
FB DataOut 1 Selection
P3.6.1
852
P2.9.3
852
P10.1
852
P11.1
852
FB DataOut 2 Selection
P3.6.2
853
P2.9.4
853
P10.2
853
P11.2
853
...
...
...
...
...
...
...
...
...
FB DataOut 8 Selection
P3.6.8
859
P2.9.10
859
P10.8
859
P11.8
859
FB DataOut 9 Selection
1), 3)
P3.6.9
890
P2.9.12
558
-
-
-
-
FB DataOut 10 Selection
1), 3)
P3.6.10
891
P2.9.13
559
-
-
-
-
...
...
...
...
...
-
-
-
-
FB DataOut 16 Selection
1), 3)
P3.6.16
897
P2.9.18
565
-
-
-
-