Brake Chopper Application – Parameter lists
vacon • 11
24-hour s358 (0)40 8371 150 • Email: [email protected]
3.7 Protections
(Menu
G2
Æ
G2.6)
Code
Parameter
Default
Min
Max
Unit
ID
Note
P2.6.1
0
3
739
Number of PT100
inputs in use at OPT-
B8 option board.
Visible only when the
option board has
been installed
P2.6.2
110
-30
200
°C
1347
Select the
temperature for PT100
sensor above which
PT100 alarm is
generated in the drive.
P2.6.3
120
PT100
Alarm
limit
(P2.6.2)
300 °C
1348
Select the
temperature for PT100
sensor above which
PT100 fault is
generated in the drive
P2.6.4
0
2
1351
Response to
thermistor
overtemperature.
0=No Action,
1=Warning,
2=Fault
P2.6.5
0
2
701
Response to External
fault.
0=No action,
1=Warning,
2=Fault
Table 3-9. Protections G2.6
3.8
Keypad control (Control keypad: Menu M3)
Code
Parameter
Default
Min
Max
Unit
ID
Description
P3.1
0 0 1
125
0=I/O terminal (default)
1=Fieldbus
Table 3-10. Keypad control parameters M3
3.9
System menu (Control keypad: Menu M6)
For parameters and functions related to the general use of the frequency converter, such as
application and language selection, customised parameter sets or information about the hardware
and software, see Chapter 7.3.6 in the Vacon NX User's Manual.
3.10 Expander boards (Control keypad: Menu M7)
The M7 menu shows the expander and option boards attached to the control board and board-
related information. For more information, see Chapter 7.3.7 in the Vacon NX User's Manual.