Description of parameters
vacon • 13
24-hour s358 (0)40 8371 150 • Email: [email protected]
4.2 Input
signals
4.2.1 Digital
Inputs
2.2.1.1
Fault Reset (ID1208)
Input selection for Fault Resetting. The transition from Off to On will reset the fault if the
cause of the fault has been removed.
0 = Not used
1 = DIN1
2 = DIN2
3 = DIN3
4 = DIN4
5 = DIN5
6 = DIN6
2.2.1.2
External fault (ID1214)
This parameter defines if the BCU monitors status of the External fault input. With
External fault it is possible to trig a fault 51. Response to the fault can be defined with
the parameter
See parameter
2.2.1.3
Run Enable (ID1212)
This parameter is used for choosing the input for external Run Enable signal. If the
option “0 = Not used” have been selected the Run Enable signal is always on.
See parameter
2.2.1.4
KLIXON Input (ID1209)
This parameter is used for choosing the input for KLIXON type temperature sensor. The
function of this input is Normally Closed so the fault “60 = KLIXON” is generated when
the input goes low.
See parameter