32 • vacon
ELECTRICAL CONNECTION
Tel: +358-201-2121 • Fax: +358-201-212 205
5.6
Fuse selection
The table below shows typical cable sizes and types that can be used with the Vacon 8000 Solar in-
verter. The final selection should be made according to local regulations, cable installation condi-
tions and cable specification.
CAUTION! Maximum AC-side short-circuit breaking capacity I
cu
=30kA.
With optional AC-section I
cu
=50kA.
5.6.1
Fuses for inverters
Inverter
type
Nominal
current
[A]
Nominal
voltage
[V]
Braking
capacity
[kA]
Acting
behaviour
Fuse size
Suitable fuse type
(Cat. nr by Ferraz-
Shawmut
NXV0010
No fuses needed
NXV0015
NXV0020
NXV0025
NXV0030
NXV0040
160
1200
100
gPV
121
DC121GPV12C160E
NXV0050
200
1200
100
gPV
121
DC121GPV12C200E
NXV0080
315
810
125
aR
71 DIN110 PC71UD13C315D1A
NXV0100
400
810
125
aR
71 DIN110 PC71UD13C400D1A
Table 5-12. Fuse selection; suitable fuses for Vacon 8000 Solar inverter types
5.6.2
Fuse for measuring
Nominal
current
[A]
Nominal
voltage
[V]
Braking
capacity
[kA]
Acting
behaviour
Fuse
size
Suitable fuse type (Cat.
nr by Ferraz-Shawmut
4
1000
10
gPV
10*38
HP10M4
Table 5-13. Fuse selection, fuse for measuring