ELECTRICAL CONNECTION
vacon • 27
24-hour support: +358 (0)201 212 575 • Email: [email protected]
5.3.2
Option board OPTA2
Description:
Standard Vacon NX frequency converter relay board with two relay outputs
Allowed slots:
B
Type ID:
16690
Terminals:
Two terminal blocks; Screw terminals (M3); No coding
Jumpers:
None
Board parameters:
None
I/O terminals on OPTA2
Terminal
Parameter reference
on keypad and NCDrive
Technical information
21
22
23
RO1/normal closed
RO1/common
RO1/normal open
DigOUT:B.1
Relay output 1 (NO/NC)
Switching capacity
24VDC/8A
250VAC/8A
125VDC/0.4A
Min. switching load
5V/10mA
24
25
26
RO2/normal closed
RO2/common
RO2/normal open
DigOUT:B.2
Relay output 2 (NO/NC)
Switching capacity
24VDC/8A
250VAC/8A
125VDC/0.4A
Min. switching load
5V/10mA
Table 5-8. OPTA2 I/O terminals