2
2.2
Main incoming section
The main incoming section (MIS) includes the main incoming device. The main incoming device and
size is dependent on the required current of the complete line-up.
As standard the MIS section has the following equipment (see Figure 1):
1. Air circuit breaker
2. Mains connections
3. Digital multi instrument with field bus connection
4. Pre-charging components for AFE
As pre-engineered standard options we can provide the following:
•
Cabling from the top (+CIT)
•
Earth Switch (+ILE)
•
Current transducers (+ITR)
•
UL approved design and components (+NAR)
•
Arc detection (+ADU)
•
Cabinet heater (+ACH)
•
Cabinet light (+ACL)
+ILE requires an additional section.
Table 6. Available MIS sizes
MIS type
Input current
Width x Height x Depth (mm)
MIS_630
630 A
400 x 2000 x 605
MIS_800
800 A
600 x 2000 x 605
MIS_1000
1000 A
600 x 2000 x 605
MIS_1250
1250 A
600 x 2000 x 605
MIS_1600
1600 A
600 x 2000 x 605
MIS_2000
2000 A
600 x 2000 x 605
MIS_2500
2500 A
600 x 2000 x 605
MIS_3200
3200 A
800 x 2000 x 605
MIS_4000
4000 A
800 x 2000 x 605
MIS_5000
5000 A
800 x 2000 x 605