The auxiliary device section (ADS) includes the common line-up controls. This section can be
customized for all application and segment needs. There are three ADS sizes available.
As standard the ADS section has the following equipment:
1. Control for the circuit breaker with +ICB selected
2. Indication of the mains status (fault, pre-charging and ON)
3. Auxiliary power supply 24 V, 5 A
4. Auxiliary Transformer, 2500 VA 1-phase supply (in bottom of cabinet)
5. Terminals for control and monitoring
As pre-engineered standard options, we can provide the following:
• Emergency stop CAT0 (+PES)
• Emergency stop CAT1 (+PED)
• Insulation fault sensor (+PIF)
• Arc protection relay (+PAP)
• Cabinet heater (+ACH)
• Cabinet light (+ACL)
• Auxiliary voltage transformer 4000 VA (+AT4)
• Auxiliary voltage 110 V AC (+AT1)
• Auxiliary power supply 24 V, 10 A (+ADC)
• Cabling from the top (+CIT)
• Empty auxiliary 600 mm cabinet with door (+G60)
• UL approved design and components (+NAR)
• Customer specific option (+CSO)
+PAP will have sub units in selected sections if needed, please refer to the circuit diagrams.
Table 6. ADS section size
ADS type
Width x Height x Depth (mm)
ADS_400
400 x 2000 x 605
ADS_600
600 x 2000 x 605
ADS_800
800 x 2000 x 605