Installation
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Figure 52. Jumper selections for OPTA1
NOTE!
If you change the AI/AO signal contents, also change the related board parameter in menu
M7.
A B C D
A B C D
A B C D
A B C D
A B C D
A B C D
Jumper block X1:
AI1 mode
AI1 mode: 0...20mA; Current input
Jumper block X2:
AI2 mode
= Factory default
A B C D
AI1 mode: 0...20mA; Current input
Jumper block X6:
AO1 mode
AO1 mode: 0....20mA; Current output
AO1 mode: Voltage output; 0...10V
AI1 mode: Voltage input; 0...10V
AI2 mode:Voltage input; 0...10V
A B C D
AI1 mode: Voltage input; 0...10V
differential
AI2 mode: Voltage input; 0...10V
differential
A B C D
AI1 mode: Voltage input; -0...10V
AI2 mode: Voltage input; -10...10V
A B C D
Jumper block X3:
CMA and CMB grounding
CMB connected to GND
CMA connected to GND
CMB isolated from GND
CMA isolated from GND
CMB and CMA
internally connected together,
isolated from GND