Copy parameters
The parameter copy function is used when the operator wants to copy one or all parameter groups
from one drive to another. All the parameter groups are first uploaded to the keypad, then the
keypad is connected to another drive and then the parameter groups are downloaded to it (or
possibly back to the same drive). For more information, see on Page 100.
Before any parameters can be successfully copied from one drive to another, the Active Front End
has to be stopped when the parameters are downloaded to it:
The parameter copy menu (S6.3) contains four functions:
Parameter sets (S6.3.1)
The user can reload the factory default parameter values and store and load two customised
parameter sets (all parameters included in the application).
On the Parameter sets page (S6.3.1), press Menu button right to enter the edit mode. The text
LoadFactDef begins to blink and you can confirm the loading of factory defaults by pressing the
Enter button. The drive resets automatically.
Alternatively, you can choose any other storing or loading functions with the Browser buttons.
Confirm with the Enter button. Wait until 'OK' appears on the display.