![Vacon NX OPTC3 Скачать руководство пользователя страница 42](http://html2.mh-extra.com/html/vacon/nx-optc3/nx-optc3_user-manual_4788865042.webp)
4 0 • va c o n
f a u l t t r a c k i n g
Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205
8
8.
FAULT TRACKING
The tabl e bel ow pr esents the faults r elated to the Pr ofibus option boar d. For mor e infor mation, see
al so Vacon NXS/P User Manual , Chapter 10.
The Pr ofibus opt ion boar d st at us LEDs have been descr ibed in mor e detail in Chapter 4.4.
Faul t
code
Faul t
Possibl e cause
Cor r ecting m easur es
37
Device change
Option boar d changed.
Reset
38
Device added
Option boar d added.
Reset
39
Device r emoved
Option boar d r emoved.
Reset
40
Device un-
known
Unknown option boar d.
53
Fieldbus fault
The data connection between the Pr ofibus
Master and the Pr ofibus option boar d is
br oken
Check the installation.
If installation is cor r ect contact the
near est Vacon distr ibutor .
54
Slot fault
Defective option boar d or slot
Check the boar d and slot.
Contact the near est Vacon distr ibutor .
Table 8- 1. Pr ofibus option boar d faults
You can define with par am eter s how the AC dr ive r eacts to cer tain faul ts:
Code
Par am eter
Min
Max
Unit
Step
Default
ID
Not e
P2.7.22
Response to fieldbus
fault
0
3
1
0 733
0=No r esponse
1=War ning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
P2.7.23
Response to slot
fault
0
3
1
0 734
0=No r esponse
1=War ning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
Table 8- 2. AC drive r esponses to faults
Содержание NX OPTC3
Страница 1: ...vacon nx ac drives optc3 c5 profibus dp option board user manual...
Страница 2: ......