fault tracing
vacon • 85
24-hour support: +358 (0)201 212 575 • Email: [email protected]
9
Fault
code
Fault
Possible cause
Correcting measures
12
Brake chopper
supervision
no brake resistor installed
brake resistor is broken
brake chopper failure
Check brake resistor.
If the resistor is ok, the chopper is
faulty. Contact the nearest Vacon
distributor.
13
Inverter
undertemperature
Heatsink temperature is under –10 C
14
Inverter
overtemperature
Heatsink temperature is over 90 C or
77ºC (NX_6, FR6).
Overtemperature warning is issued
when the heatsink temperature exceeds
85 C (72ºC).
Check the correct amount and flow of
cooling air.
Check the heatsink for dust.
Check the ambient temperature.
Make sure that the switching frequency
is not too high in relation to ambient
temperature and motor load.
15
Motor stalled
Motor stall protection has tripped.
Check motor.
16
Motor over-
temperature
Motor overheating has been detected by
inverter motor temperature model.
Motor is overloaded.
Decrease the motor load.
If no motor overload exists, check the
temperature model parameters.
17
Motor underload
Motor underload protection has tripped.
18
Unbalance
Unbalance between power modules in
parallelled units.
Subcode in T.14:
S1 = Current unbalance
S2 = DC voltage unbalance
Should the fault re-occur, contact the
distributor near to you.
22
EEPROM
checksum fault
Parameter save fault
faulty operation
component failure
24
Counter fault
Values displayed on counters are
incorrect
25
Microprocessor
watchdog fault
faulty operation
component failure
Reset the fault and restart.
Should the fault re-occur, contact the
distributor near to you.
26
Start-up
prevented
Start-up of the drive has been
prevented.
Cancel prevention of start-up.
29
Thermistor fault
The thermistor input of option board has
detected increase of the motor
temperature
Check motor cooling and loading
Check thermistor connection
(If thermistor input of the option board is
not in use it has to be short circuited)
30
Safe disable
The input on OPTAF board has opened
Cancel Safe Disable if this can be done
safely.
31
IGBT temperature
(hardware)
IGBT Inverter Bridge overtemperature
protection has detected too high a short
term overload current
Check loading.
Check motor size.
32
Fan cooling
Cooling fan of the inverter does not
start, when ON command is given
Contact the nearest Vacon distributor.
34
CAN bus
communication
Sent message not acknowledged.
Ensure that there is another device on
the bus with the same configuration.
35
Application
Problem in application software.
Contact your distributor. If you are
application programmer check the
application program.
36
Control unit
NXS Control Unit can not control NXP
Power Unit and vice versa
Change control unit