TROUBLESHOOTING
Service Manual M4 - M10
11.07.2002
Page
46
F36
Check value on monitoring page v14
F36 ANALOGUE INPUT Iin
Clear fault memory
Replace control board with functioning one
according to instructions on section 9.3.6.
Replace defective parts as recommended in
spare part lists
Make corrective measures to external control
circuit
I<4mA
Measure actual value of signal in current loop
Actual value =
Monitored value
Load software into Control board according to
instructions on section 12.5.3 and set
parameters
YES
YES
NO
NO